Short description
I/O module | IO-Link master with 4 IO-Link interfaces |
General information
B&R ID code | 0xCAAE |
Status indicators | IO-Link operating state, bus function, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
IO-Link operating state | Yes, using LED status indicator and software |
C/Q status | Yes, using LED status indicator and software |
I/Q status | Yes, using software |
Connection type | |
X2X Link | M12, B-coded |
Inputs | M12, A-coded |
I/O power supply | M8, 4-pin |
Cable specification | |
Cable type | 4-pin sensor cable, unshielded |
Cable length | Max. 20 m |
Line capacitance | Max. 3 nF |
Loop resistance | Max. 6 Ω |
Power consumption | |
Internal I/O | 0.5 W |
X2X Link power supply | 0.75 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
I/O power supply
Nominal voltage | 24 VDC |
Voltage range | 24 VDC ±25% |
Integrated protection | Reverse polarity protection |
Sensor/Actuator power supply
Voltage | I/O power supply minus voltage drop for short-circuit protection |
Voltage drop for short-circuit protection at 0.5 A | Max. 0.3 V |
Power consumption | Max. 12 W per IO-Link interface |
Short-circuit proof | Yes |
Overload protection | |
Switch-off delay | Configurable using software |
Switch-off duration | Configurable using software |
IO-Link in master mode
Transfer rates | |
COM1 | 4.8 kbaud |
COM2 | 38.4 kbaud |
COM3 | 230.4 kbaud |
Limit values for COM3 | |
Max. connection capacity | 22 nF (cable + IO-Link device) |
Max. load | 96 Ω / 250 mA |
Data format | 1 start bit, 8 data bits, 1 parity bit (even), 1 stop bit |
Bus level | 24 VDC (active), 0 VDC (resting voltage) |
IO-Link in master mode or in SIO mode "digital output"
Variant | Bipolar, positive and negative switching |
Peak short-circuit current | <1.3 A |
Residual voltage | <0.7 VDC at nominal current 0.25 A |
Switching voltage | I/O power supply minus voltage drop for short-circuit protection and semiconductor switch |
Voltage drop on semiconductor switch | Max. 0.5 VDC at 0.25 A |
Switching delay | |
0 → 1 | <10 µs |
1 → 0 | <10 µs |
Overload protection of C/Q output | |
Overcurrent threshold | Configurable using software |
Switch-off duration | Configurable using software |
Insulation voltage between IO-Link and bus | 500 Veff |
IO-Link in SIO mode "Digital output"
Nominal voltage | 24 VDC |
Nominal output current | 0.25 A |
Total nominal current | Max. 1 A |
Output circuit | Sink or source |
Switching frequency (resistive load) | Max. 500 Hz |
Output protection | Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads |
IO-Link in SIO mode "digital input"
Nominal voltage | 24 VDC |
Input filter | |
Hardware | 300 ns |
Input circuit | Sink |
Input voltage | 24 VDC -15% / +20% |
Input current at 24 VDC | Typ. 4.0 mA |
Input resistance | Typ. 6 kΩ |
Switching threshold | |
Low | <5 VDC |
High | >15 VDC |
Insulation voltage between IO-Link and bus | 500 Veff |
IO-Link I/Q interface (digital input)
Nominal voltage | 24 VDC |
Input voltage | 24 VDC -15% / +20% |
Input current at 24 VDC | Typ. 3.8 mA |
Input filter | |
Hardware | ≤60 µs |
Software | Default 1 ms, configurable between 0 and 25.5 ms |
Input circuit | Sink |
Input resistance | Typ. 6.3 kΩ |
Switching threshold | |
Low | <5 VDC |
High | >15 VDC |
Insulation voltage between channel and bus | 500 Veff |
Electrical properties
Electrical isolation | Bus isolated from IO-Link |
Operating conditions
Mounting orientation | |
Any | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP67 |
Ambient conditions
Temperature | |
Operation | -25 to 60°C |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95% |
Storage | 5 to 95% |
Transport | 5 to 95% |
Mechanical properties
Dimensions | |
Width | 53 mm |
Height | 85 mm |
Depth | 42 mm |
Weight | 200 g |
Torque for connections | |
M8 | Max. 0.4 Nm |
M12 | Max. 0.6 Nm |
型番:
X67DS438A説明:
- 4 IO-Link channels (Port Class A)
- Each IO-Link channel can be configured as a digital input or output (SIO mode)
- Additional digital input per IO-Link connection
- 24 VDC and GND for sensor/actuator supply
- NetTime timestamps: IO-Link data
The module is an IO-Link master that allows intelligent sensor and actuators to be connected in accordance to the IO-Link standard. The module can be used to operate up to 4 IO-Link devices. All IO-Link channels can also be operated in SIO mode if desired and thus used as digital inputs or outputs. The module also has 4 additional digital inputs, which can be used independent of the IO-Link channel configuration.
Automation Studio HW アップグレード | バージョン (日付) | ダウンロード |
---|---|---|
V3.0 HW Upgrade (X67DS438A) | EXE / 4 MB | |
V4.1 HW Upgrade (X67DS438A) | EXE / 5 MB |
E-CAD(ElectroまたはEPLANテンプレート) | バージョン (日付) | ダウンロード |
---|---|---|
X67 EPLAN P8 from V2.4 | EXE / 105 MB |
M-CAD (Mechan.Templates) | バージョン (日付) | ダウンロード |
---|---|---|
3D File DXF/STEP X67 | ZIP / 4 MB |
ドキュメンテーション | バージョン (日付) | ダウンロード |
---|---|---|
Data sheet X67DS438A | PDF / 2 MB | |
Installation- / EMC-Guide | PDF / 20 MB | |
X67 System User´s Manual | PDF / 6 MB |