Lütfen ülke ve dil seçiniz

Short description
I/O module IO-Link master with 4 IO-Link interfaces
General information
B&R ID code 0xCAAE
Status indicators IO-Link operating state, bus function, module status
Diagnostics
Module run/error Yes, using status LED and software
IO-Link operating state Yes, using status LED and software
C/Q status Yes, using status LED and software
I/Q status Yes, using software
Connection type
X2X Link M12, B-coded
Inputs M12, A-coded
I/O power supply M8, 4-pin
Cable specification
Cable type 4-pin sensor cable, unshielded
Cable length Max. 20 m
Line capacitance Max. 3 nF
Loop resistance Max. 6 Ω
Power consumption
Internal I/O 0.5 W
X2X Link power supply 0.75 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
I/O power supply
Nominal voltage 24 VDC
Voltage range 24 VDC ±25%
Integrated protection Reverse polarity protection
Sensor/Actuator power supply
Voltage I/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 A Max. 0.3 V
Power consumption Max. 12 W per IO-Link interface
Short-circuit proof Yes
Overload protection
Switch-off delay Configurable using software
Switch-off duration Configurable using software
IO-Link in master mode
Transfer rates
COM1 4.8 kbaud
COM2 38.4 kbaud
COM3 230.4 kbaud
Limit values for COM3
Max. connection capacity 22 nF (cable + IO-Link device)
Max. load 96 Ω / 250 mA
Data format 1 start bit, 8 data bits, 1 parity bit (even), 1 stop bit
Bus level 24 VDC (active), 0 VDC (resting voltage)
IO-Link in master mode or in SIO mode "digital output"
Variant Bipolar, positive and negative switching
Peak short-circuit current <1.3 A
Residual voltage <0.7 VDC at nominal current 0.25 A
Switching voltage I/O power supply minus voltage drop for short-circuit protection and semiconductor switch
Voltage drop on semiconductor switch Max. 0.5 VDC at 0.25 A
Switching delay
0 → 1 <10 µs
1 → 0 <10 µs
Overload protection of C/Q output
Overcurrent threshold Configurable using software
Switch-off duration Configurable using software
Insulation voltage between IO-Link and bus 500 Veff
IO-Link in SIO mode "Digital output"
Nominal voltage 24 VDC
Nominal output current 0.25 A
Total nominal current Max. 1 A
Output circuit Sink or source
Switching frequency (resistive load) Max. 500 Hz
Output protection Thermal cutoff if overcurrent or short circuit occurs, integrated protection for switching inductances
IO-Link in SIO mode "digital input"
Nominal voltage 24 VDC
Input filter
Hardware 300 ns
Input circuit Sink
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Typ. 4.0 mA
Input resistance Typ. 6 kΩ
Switching threshold
Low <5 VDC
High >15 VDC
Insulation voltage between IO-Link and bus 500 Veff
IO-Link I/Q interface (digital input)
Nominal voltage 24 VDC
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Typ. 3.8 mA
Input filter
Hardware ≤60 µs
Software Default 1 ms, configurable between 0 and 25.5 ms
Input circuit Sink
Input resistance Typ. 6.3 kΩ
Switching threshold
Low <5 VDC
High >15 VDC
Insulation voltage between channel and bus 500 Veff
Electrical properties
Electrical isolation Bus isolated from IO-Link
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%
Storage 5 to 95%
Transport 5 to 95%
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 200 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Malzeme Numarası:
X67DS438A
Açıklama:
  • 4 IO-Link channels (Port Class A)
  • Each IO-Link channel can be configured as a digital input or output (SIO mode)
  • Additional digital input per IO-Link connection
  • 24 VDC and GND for sensor/actuator supply
  • NetTime timestamps: IO-Link data

The module is an IO-Link master that allows intelligent sensor and actuators to be connected in accordance to the IO-Link standard. The module can be used to operate up to 4 IO-Link devices. All IO-Link channels can also be operated in SIO mode if desired and thus used as digital inputs or outputs. The module also has 4 additional digital inputs, which can be used independent of the IO-Link channel configuration.

Automation Studio Donanım Güncellemeleri Version (Date) Download
V3.0 HW Upgrade (X67DS438A) EXE / 4 MB
V4.1 HW Upgrade (X67DS438A) EXE / 4 MB
Dokümantasyon Version (Date) Download
Data sheet X67DS438A PDF / 1 MB
X67 System User´s Manual PDF / 19 MB
E-CAD (Elektrik veya EPLAN Taslakları) Version (Date) Download
X67 EPLAN P8 from V2.4 EXE / 105 MB
M-CAD (Mekanik Taslaklar) Version (Date) Download
3D File DXF/STEP X67 ZIP / 1 MB
Sertifikalar Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
E115267 UL CoC X67 PDF / 84 KB
TÜV 05 ATEX 7201 X PDF / 129 KB

Lütfen ülke ve dil seçiniz

B&R Logo