2.5.3.0 * 11.03.2024 3 MB EXE AS4_HW_X90SL104.48-S1.exe
Popis V4.7 HW Upgrade (X90SL104.48-S1)

Revision information X90SL104.48-S1

Version 2.5.3.0:

ID: 776925 / Support ID: 400409795
Temperature failures fixed
Temperature failures at approx. 60°C ambient temperature have been fixed.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\62661_1.fw(579), 11\62661_1.fw(579)

Version 2.5.1.1:

ID: 697860
"CLEAR DATA" Safe Commissioning Options
"CLEAR DATA" did not delete the data for Safe Commissioning Options with data types SAFEINT, SAFEDINT and SAFEDWORD.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 727335 / Support ID: 400353463
Safe Commissioning Options without SAFEBOOL
Logger message "external machine options discrepancy" was triggered by mistake when Safe Commissioning Options where used without using any channel SafeCommissioningOptionsBITxxx
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 736430
online project compare
Activation of SafeDESIGNER option "Download project source to SL (online project compare)" didn't have any effect (requires mappSafety 5.15).
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(577), 11\62661_1.fw(577)

Version 2.5.0.0:

ID: 715805
Improved stability during boot-up
Improved stability during boot-up
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 718050
SafeDESIGNER Variable status
improve performance
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 718845
Fix HWX description of SafeLOGIC-to-CPU communication
Fix HWX description of SafeLOGIC-to-CPU communication
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(576)

Version 2.4.0.0:

ID: 708520 / Support ID: 400335786
Increase maximum switching frequency
The maximum switching frequency is increased to the value of the data sheet
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(575)

Version 2.3.0.1:

ID: 691170
increased some system limits
Inreased flag counter, number of force variables and sizes of input/output buffers (see technical data).
ATTENTION: SafeDESIGNER project must berecompiled and downloaded!
It is recommended to perform a SafeKEY-FORMAT before upgrading to this version.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 691175
Increased some system limits
Double flag memory and flag counter to 256kB respectively 16384 flags.
Triple memory for safe input data to 6kB.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 703755 / Support ID: 400335138
"Safe digital outputs" have to be used within SafeDIGNER application
Channels configured as " Safe digital output" in Automation Studio can onlybe switched on, if it is also used in SafeDESIGNER application
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 708235
CANopen Safety support
Module supports CANopen Safety
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 711370
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\62661_1.fw(574)

Version 2.2.0.1:

ID: 663695
Support of Safe Commissioning Options
ATTENTION:
- requires AR E4.71 or A4.72 orhigher
- if used at least one Safe Commissioning Option with data type BOOL must beused also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671740
Configurable test interval for inputs
The test interval for inputs is configurable via the parameter "Test interval of input signal path"
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: No

ID: 675650
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(573)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.5.2.0 * 01.03.2023 3 MB EXE AS4_HW_X90SL104.48-S1.exe
Popis V4.7 HW Upgrade (X90SL104.48-S1)

Revision information X90SL104.48-S1

Version 2.5.2.0:

ID: 763990 / Support ID: 400394920
SafeDomain to SafeDomain communication with differing "Process data transfer rate" setting
SafeDomain to SafeDomain communication could not be established if"Process data transfer rate" setting differed between Managing and Connected SafeDomain.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\62661_1.fw(578), 11\62661_1.fw(578)

Version 2.5.1.1:

ID: 697860
"CLEAR DATA"Safe Commissioning Options
"CLEAR DATA" did not delete the data for SafeCommissioning Options with data types SAFEINT, SAFEDINT and SAFEDWORD.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 727335 / Support ID: 400353463
Safe Commissioning Options without SAFEBOOL
Logger message "external machine options discrepancy" was triggered by mistake when Safe Commissioning Options where used without using any channel SafeCommissioningOptionsBITxxx
Channeldescription changed: No
Configuration description changed: No
Firmware changed: No

ID: 736430
online project compare
Activation of SafeDESIGNER option "Download project source to SL (online project compare)" didn't have any effect (requires mappSafety 5.15).
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(577), 11\62661_1.fw(577)

Version 2.5.0.0:

ID: 715805
Improved stability during boot-up
Improvedstability during boot-up
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 718050
SafeDESIGNER Variable status
improve performance
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 718845
Fix HWX description of SafeLOGIC-to-CPU communication
Fix HWX description of SafeLOGIC-to-CPU communication
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(576)

Version 2.4.0.0:

ID: 708520 / Support ID: 400335786
Increase maximum switching frequency
The maximum switching frequency is increased to the value of the data sheet
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(575)

Version 2.3.0.1:

ID: 691170
increased some system limits
Inreased flag counter, number of force variables and sizes of input/output buffers (see technical data).
ATTENTION: SafeDESIGNER project must be recompiled and downloaded!
It is recommended to perform a SafeKEY-FORMAT before upgrading to this version.
Channel description changed: No
Configurationdescription changed: Yes
Firmware changed: Yes

ID: 691175
Increased some system limits
Double flag memory and flag counter to 256kBrespectively 16384 flags.
Triple memory for safe input data to 6kB.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 703755 / Support ID: 400335138
"Safedigital outputs" have to be used within SafeDIGNER application
Channels configured as " Safe digital output" in Automation Studio can onlybe switchedon, if it is also used in SafeDESIGNER application
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 708235
CANopen Safety support
Module supports CANopen Safety
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 711370
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\62661_1.fw(574)

Version 2.2.0.1:

ID: 663695
Support of Safe Commissioning Options
ATTENTION:
- requires AR E4.71 or A4.72 or higher
- if used at least one Safe Commissioning Option with data type BOOL must beused also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671740
Configurable test interval for inputs
The test interval forinputs is configurable via the parameter "Test interval of input signal path"
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 675650
SafeDOMAIN-to-SafeDOMAINcommunication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(573)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.5.1.1 * 08.09.2022 2 MB EXE AS4_HW_X90SL104.48-S1.exe
Popis V4.7 HW Upgrade (X90SL104.48-S1)

Revision information X90SL104.48-S1

Version 2.5.1.1:

ID: 697860
"CLEAR DATA" Safe Commissioning Options
"CLEAR DATA" did not delete the data for Safe Commissioning Options with data types SAFEINT, SAFEDINT and SAFEDWORD.
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes

ID: 727335 / Support ID: 400353463
Safe Commissioning Options without SAFEBOOL
Logger message "external machine options discrepancy"was triggered by mistake when Safe Commissioning Options where used without using any channel SafeCommissioningOptionsBITxxx
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 736430
online project compare
Activation of SafeDESIGNER option "Download project source to SL (online project compare)" didn't have any effect (requires mappSafety 5.15).
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(577), 11\62661_1.fw(577)

Version 2.5.0.0:

ID:715805
Improved stability during boot-up
Improved stability during boot-up
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 718050
SafeDESIGNER Variable status
improve performance
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 718845
Fix HWX description of SafeLOGIC-to-CPU communication
Fix HWX description of SafeLOGIC-to-CPU communication
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(576)

Version 2.4.0.0:

ID: 708520/ Support ID: 400335786
Increase maximum switching frequency
The maximum switching frequency is increased to the value of the data sheet
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(575)

Version 2.3.0.1:

ID: 691170
increased some system limits
Inreased flag counter, number of force variables and sizes of input/output buffers (see technicaldata).
ATTENTION: SafeDESIGNER project must be recompiled and downloaded!
It is recommended to perform a SafeKEY-FORMAT before upgrading to this version.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 691175
Increased some system limits
Double flag memory and flag counter to 256kB respectively 16384 flags.
Triple memory for safe input data to 6kB.
Channel descriptionchanged: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 703755 / Support ID: 400335138
"Safe digital outputs" have to be used within SafeDIGNER application
Channels configured as " Safe digital output" in Automation Studio can onlybe switched on, if it is alsoused in SafeDESIGNER application
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 708235
CANopen Safety support
Module supports CANopen Safety
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 711370
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\62661_1.fw(574)

Version 2.2.0.1:

ID: 663695
Support of Safe Commissioning Options
ATTENTION:
- requires AR E4.71 or A4.72 or higher
- if used at least one Safe Commissioning Option with data type BOOL must beused also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671740
Configurable test interval for inputs
The test interval for inputs is configurable via the parameter "Test interval of input signal path"
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 675650
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(573)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.5.0.0 * 07.06.2021 1 MB EXE AS4_HW_X90SL104.48-S1.exe
Popis V4.7 HW Upgrade (X90SL104.48-S1)

Revision information X90SL104.48-S1.48-S1

Version 2.5.0.0:

ID: 715805
Improved stability during boot-up
Improved stability during boot-up
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 718050
SafeDESIGNER Variable status
improve performance
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 718845
Fix HWX description ofSafeLOGIC-to-CPU communication
Fix HWX description of SafeLOGIC-to-CPU communication
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(576)

Version 2.4.0.0:

ID: 708520 / Support ID: 400335786
Increase maximum switching frequency
The maximum switching frequency is increased to the value of the data sheet
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(575)

Version 2.3.0.1:

ID: 691170
increased some system limits
Inreased flag counter, number of force variables and sizes of input/output buffers (see technical data).
ATTENTION: SafeDESIGNER project must be recompiled and downloaded!
It is recommended to perform a SafeKEY-FORMAT before upgrading to this version.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 691175
Increased some system limits
Double flag memory and flag counter to 256kB respectively 16384 flags.
Triple memory for safe input data to 6kB.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 703755 / Support ID: 400335138
"Safe digital outputs" have to be used within SafeDIGNER application
Channels configured as " Safe digital output" in Automation Studio can onlybe switched on, if it is also used in SafeDESIGNER application
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 708235
CANopen Safety support
Module supports CANopen Safety
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 711370
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\62661_1.fw(574)

Version 2.2.0.1:

ID: 663695
Support of Safe Commissioning Options
ATTENTION:
- requires AR E4.71 or A4.72 or higher
- if used at least one Safe Commissioning Option withdata type BOOL must be used also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671740
Configurable test interval for inputs
The test interval for inputs is configurable via the parameter "Test interval of input signal path"
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 675650
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(573)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.4.0.0 * 10.03.2021 1 MB EXE AS4_HW_X90SL104.48-S1.exe
Popis V4.7 HW Upgrade (X90SL104.48-S1)

Revision information X90SL104.48-S1.48-S1

Version 2.4.0.0:

ID: 708520 / Support ID: 400335786
Increase maximum switching frequency
The maximum switching frequency is increased to the value of the data sheet
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\62661_1.fw(575)

Version 2.3.0.1:

ID: 691170
increased some system limits
Inreased flag counter, number of force variables and sizes of input/output buffers (see technical data).
ATTENTION: SafeDESIGNER project must be recompiled and downloaded!
It is recommended to perform a SafeKEY-FORMAT before upgrading to this version.
Channel description changed: No
Configuration description changed: Yes
Firmware changed:Yes

ID: 691175
Increased some system limits
Double flag memory and flag counter to 256kB respectively 16384 flags.
Triple memory for safe input data to 6kB.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 703755 / Support ID: 400335138
"Safe digital outputs" have to be used within SafeDIGNER application
Channels configured as " Safe digital output" in Automation Studio can onlybe switched on, if it is also used in SafeDESIGNER application
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 708235
CANopen Safety support
Module supports CANopen Safety
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 711370
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\62661_1.fw(574)

Version 2.2.0.1:

ID: 663695
Support of Safe Commissioning Options
ATTENTION:
- requires AR E4.71 or A4.72 or higher
- if used at least one Safe Commissioning Option with data type BOOL must beused also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671740
Configurable test interval for inputs
The test interval for inputs is configurable via the parameter "Test interval of input signal path"
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 675650
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(573)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.3.0.1 * 04.12.2020 1 MB EXE AS4_HW_X90SL104.48-S1.exe
Popis V4.7 HW Upgrade (X90SL104.48-S1)

Revision information X90SL104.48-S1

Version 2.3.0.1:

ID: 691170
increased some system limits
Inreased flag counter, number of force variables and sizes of input/outputbuffers (see technical data).
ATTENTION: SafeDESIGNER project must be recompiled and downloaded!
It is recommended to perform a SafeKEY-FORMAT beforeupgrading to this version.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 691175
Increased some system limits
Double flag memory and flag counter to 256kB respectively 16384 flags.
Triple memory for safe input data to 6kB.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 703755 / Support ID: 400335138
"Safe digital outputs" have to be used within SafeDIGNER application
Channels configured as " Safe digital output" in Automation Studio can onlybe switched on, if it is also used in SafeDESIGNER application
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 708235
CANopen Safety support
Module supports CANopen Safety
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 711370
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\62661_1.fw(574)

Version 2.2.0.1:

ID: 663695
Support of Safe Commissioning Options
ATTENTION:
- requires AR E4.71 or A4.72 or higher
- if used at least one Safe Commissioning Option with data type BOOL must beused also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671740
Configurable test interval for inputs
The test interval for inputs is configurable via the parameter "Test interval of input signal path"
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 675650
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(573)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.2.0.1 * 07.07.2020 1 MB EXE AS4_HW_X90SL104.48-S1.exe
Popis V4.7 HW Upgrade (X90SL104.48-S1)

Revision information X90SL104.48-S1

Version 2.2.0.1:

ID: 663695
Support of Safe Commissioning Options
ATTENTION:
- requires AR E4.71 or A4.72 or higher
- if used at least one Safe Commissioning Option with data type BOOL must beused also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671740
Configurable test interval for inputs
The test interval for inputs is configurable via the parameter "Test interval of input signal path"
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 675650
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\62661_1.fw(573)