Verze | Jazyk | Operační systém | Datum | Velikost | Typ | Stáhnout |
---|---|---|---|---|---|---|
2.12.0.0 | * | 08.10.2020 | 2 MB | EXE | AS3.0_HW_X20cBC1083.exe | |
Popis |
V3.0 HW Upgrade (X20cBC1083) Revision information X20cBC1083 Version 2.12.0.0: ID: 703010 FW Update of the X2X modules connected to the X20IF1091-1 at each startup (Rev. >= I0) Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(431), 1\57879_4.fw(431), 1\57879_5.fw(431) Version 2.11.1.0: ID: 695155 Support for automatic DNA configuration from AS 4.9.1 Channel description changed: No Configuration description changed: Yes Firmware changed: No ID: 695455 Module documentation revised Data sheet V2.49 Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\57879_3.fw(430), 1\57879_4.fw(430) Version 2.11.0.0: ID: 664385 Adaptations for Automation Studio 4.8 Channel description changed: No Configuration description changed: No Firmware changed: No ID: 664400 DNA: Hub of PLK BC active until first IDENT_REQUEST Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 665765 / Support ID: 400266182, 400285939 ModuleOk of IO module FALSE after warm restart even though the module is working as expected Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 665845 Accessing non-cyclic registers with AsIOAcc while ModuleOk = FALSE preventsmodule from starting/communicating Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 666210 Module documentation revised Data sheet V2.48 Channel description changed: No Configuration description changed: No Firmware changed: No ID: 678955 Support HW-variant 4 Channeldescription changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(430), 1\57879_4.fw(430) Version 2.9.0.0: ID: 623855 Optimization of synchronization between X20BC1083 and X20IF1091-1 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 628940 Optimization of hub behavior Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 628965 Wrong serial number in SystemDump when X20IF1091-1 is used on a X20BC1083 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 629020 Ring redundancy: Cannot address the CN that closes the ring Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 629085 DNA: BC as head-end station switching hub off again Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 629170 Shortened preamble of Ethernet frame leading to incorrectly detected CRC errors Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(427) Version 2.8.0.0: ID: 619155 DNA: PLK hub forwarding for the next node not enabled in rare cases Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 619190 Outputs of I/O modules behind the bus coupler not working in some cases if poll-response chaining active Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 623065 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(426) Version 2.7.0.0: ID: 586750 / Support ID: 400241376 Temporary toggling of data point ModuleOk if I/O modulefails Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(424) Version 2.6.0.0: ID: 572710 Corrected L/A LEDs for hardware revision H0 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574320 / Support ID: 0, 400235528, 400235970 Unable to start netX IF card on X20BC1083 in isolated cases Channel description changed: No Configuration description changed:No Firmware changed: Yes ID: 574325 / Support ID: 400230671 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(423) Version 2.5.6.0: ID: 551130 Startup time optimizations Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(421) Version 2.5.5.0: ID: 545100 NetX Firmware update bug fix Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(420) Version 2.5.4.0: ID: 540325 / SupportID: 400202320 BC sporadically not going into Operational due to X2X-bus problems at startup Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(419) Version 2.5.3.0: ID: 523495 / Support ID: 400205694 safety modules not switching to operational state SDO streaming connectionvia UDP is not always established when PLC and SafeLogic are booted together. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(417) Version 2.5.2.0: ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752 First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s. Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494195 / Support ID: 400191269 X20BC1083 with disabled netX modules is not booting - Error 32162 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494200 / Support ID: 400189834 X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(415) Version 2.5.0.0: ID: 467890 Restart of the netX interface card If PLK-failure the netX interface card is reset by the Bus Controller Channeldescription changed: No Configuration description changed: No Firmware changed: Yes ID: 468100 / Support ID: 400178654 Safety modules in connection with PLK BCs, with only input datapoints, are not initialized.by SL Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468105 / Support ID: 400177243 X2X FW update of several X2X modules is not working Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468110 optimization of X2X FW updates Channeldescription changed: No Configuration description changed: No Firmware changed: Yes ID: 468540 CiR support Channel descriptionchanged: No Configuration description changed: Yes Firmware changed: No Firmware: 1\57879_3.fw(413) Version 1.3.0.0: ID: 460115 / Support ID: 400168329 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 460235 / Support ID: 400150525 Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(411) Version 1.2.0.0: ID: 439110 / Support ID: 400150496 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 439215 / Support ID: 400128436 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(400) Version 1.1.0.0: ID: 402430 X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed. When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change. The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing. Channel description changed: Yes Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(300) Version 1.0.0.1: ID: 343245 Support X20cBC1083 Support for Automation Studio Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\57879_3.fw(210) |
|||||
Verze | Jazyk | Operační systém | Datum | Velikost | Typ | Stáhnout |
2.11.0.0 | * | 10.02.2020 | 1 MB | EXE | AS3.0_HW_X20cBC1083.exe | |
Popis |
V3.0 HW Upgrade (X20cBC1083) Revision information X20cBC1083 Version 2.11.0.0: ID: 664385 Adaptations for Automation Studio 4.8 Channel description changed: No Configuration description changed: No Firmware changed: No ID: 664400 DNA: Hub of PLK BC active until first IDENT_REQUEST Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 665765 /Support ID: 400266182, 400285939 ModuleOk of IO module FALSE after warm restart even though the module is working as expected Channel descriptionchanged: No Configuration description changed: No Firmware changed:Yes ID: 665845 Accessing non-cyclic registers with AsIOAcc while ModuleOk = FALSE preventsmodule from starting/communicating Channel description changed: No Configuration description changed: No Firmwarechanged: Yes ID: 666210 Module documentation revised Data sheet V2.48 Channel description changed: No Configuration description changed: No Firmware changed: No ID: 678955 Support HW-variant 4 Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(430), 1\57879_4.fw(430) Version 2.9.0.0: ID: 623855 Optimization of synchronization between X20BC1083 and X20IF1091-1 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 628940 Optimization of hub behavior Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 628965 Wrong serial number in SystemDump when X20IF1091-1 is used on a X20BC1083 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 629020 Ring redundancy: Cannot address the CN that closes the ring Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 629085 DNA: BC as head-end station switching huboff again Channel description changed: No Configuration descriptionchanged: No Firmware changed: Yes ID: 629170 Shortened preamble of Ethernet frame leading to incorrectly detected CRC errors Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(427) Version 2.8.0.0: ID: 619155 DNA: PLK hub forwarding for the next node not enabled inrare cases Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 619190 Outputs of I/O modules behind the bus coupler not working in some cases if poll-response chaining active Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 623065 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(426) Version 2.7.0.0: ID: 586750 / Support ID: 400241376 Temporary toggling of data point ModuleOk if I/O module fails Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(424) Version 2.6.0.0: ID: 572710 Corrected L/A LEDsfor hardware revision H0 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574320 / Support ID: 0, 400235528, 400235970 Unable to start netX IF card on X20BC1083 in isolated cases Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574325 / Support ID: 400230671 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(423) Version 2.5.6.0: ID: 551130 Startup time optimizations Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(421) Version 2.5.5.0: ID: 545100 NetX Firmware update bug fix Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(420) Version 2.5.4.0: ID: 540325 / Support ID: 400202320 BC sporadically not going into Operational due to X2X-bus problems at startup Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(419) Version 2.5.3.0: ID: 523495 / Support ID: 400205694 safety modules not switching to operational state SDO streaming connection via UDP is not always established when PLC and SafeLogic are booted together. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(417) Version 2.5.2.0: ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752 First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s. Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494195 / Support ID: 400191269 X20BC1083 with disabled netX modules is not booting - Error 32162 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494200 / Support ID: 400189834 X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(415) Version 2.5.0.0: ID: 467890 Restart of the netX interface card If PLK-failure the netX interface card is reset by the Bus Controller Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468100 / Support ID: 400178654 Safety modules in connection with PLK BCs, with only input datapoints,are not initialized.by SL Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468105 / Support ID: 400177243 X2X FW update of several X2X modules is not working Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468110 optimization of X2X FW updates Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468540 CiR support Channel description changed: No Configuration description changed: Yes Firmware changed: No Firmware: 1\57879_3.fw(413) Version 1.3.0.0: ID: 460115 / Support ID: 400168329 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 460235 / Support ID: 400150525 Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(411) Version 1.2.0.0: ID: 439110 / Support ID: 400150496 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 439215 / Support ID: 400128436 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(400) Version 1.1.0.0: ID: 402430 X2XLink-BC: StationAtBusEnd does not change, when emptybackplanes are addedor removed. When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change. The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implementedto update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing. Channel description changed: Yes Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(300) Version 1.0.0.1: ID: 343245 Support X20cBC1083 Support for Automation Studio Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\57879_3.fw(210) |
|||||
Verze | Jazyk | Operační systém | Datum | Velikost | Typ | Stáhnout |
2.9.0.0 | * | 15.02.2019 | 1 MB | EXE | AS3.0_HW_X20cBC1083.exe | |
Popis |
V3.0 HW Upgrade (X20cBC1083) Revision information X20cBC1083 Version 2.9.0.0: ID: 623855 Optimization of synchronization between X20BC1083 and X20IF1091-1 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 628940 Optimization of hub behavior Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 628965 Wrong serial number in SystemDump when X20IF1091-1 is used on a X20BC1083 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 629020 Ring redundancy: Cannot address the CN that closes the ring Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 629085 DNA: BC as head-end station switching hub off again Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 629170 Shortened preamble of Ethernet frame leading to incorrectly detected CRC errors Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(427) Version 2.8.0.0: ID: 619155 DNA: PLK hub forwarding for the next node not enabled in rare cases Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 619190 Outputs of I/O modules behind the bus coupler not working in some cases if poll-response chaining active Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 623065 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(426) Version 2.7.0.0: ID: 586750 / Support ID: 400241376 Temporary toggling of data point ModuleOk if I/O modulefails Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(424) Version 2.6.0.0: ID: 572710 Corrected L/A LEDs for hardware revision H0 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574320 / Support ID: 0, 400235528, 400235970 Unable to start netX IF card on X20BC1083 in isolated cases Channel description changed: No Configuration description changed:No Firmware changed: Yes ID: 574325 / Support ID: 400230671 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(423) Version 2.5.6.0: ID: 551130 Startup time optimizations Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(421) Version 2.5.5.0: ID: 545100 NetX Firmware update bug fix Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(420) Version 2.5.4.0: ID: 540325 / SupportID: 400202320 BC sporadically not going into Operational due to X2X-bus problems at startup Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(419) Version 2.5.3.0: ID: 523495 / Support ID: 400205694 safety modules not switching to operational state SDO streaming connectionvia UDP is not always established when PLC and SafeLogic are booted together. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(417) Version 2.5.2.0: ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752 First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s. Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494195 / Support ID: 400191269 X20BC1083 with disabled netX modules is not booting - Error 32162 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494200 / Support ID: 400189834 X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(415) Version 2.5.0.0: ID: 467890 Restart of the netX interface card If PLK-failure the netX interface card is reset by the Bus Controller Channeldescription changed: No Configuration description changed: No Firmware changed: Yes ID: 468100 / Support ID: 400178654 Safety modules in connection with PLK BCs, with only input datapoints, are not initialized.by SL Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468105 / Support ID: 400177243 X2X FW update of several X2X modules is not working Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468110 optimization of X2X FW updates Channeldescription changed: No Configuration description changed: No Firmware changed: Yes ID: 468540 CiR support Channel descriptionchanged: No Configuration description changed: Yes Firmware changed: No Firmware: 1\57879_3.fw(413) Version 1.3.0.0: ID: 460115 / Support ID: 400168329 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 460235 / Support ID: 400150525 Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(411) Version 1.2.0.0: ID: 439110 / Support ID: 400150496 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 439215 / Support ID: 400128436 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(400) Version 1.1.0.0: ID: 402430 X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed. When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change. The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing. Channel description changed: Yes Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(300) Version 1.0.0.1: ID: 343245 Support X20cBC1083 Support for Automation Studio Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\57879_3.fw(210) |
|||||
Verze | Jazyk | Operační systém | Datum | Velikost | Typ | Stáhnout |
2.8.0.0 | * | 05.12.2018 | 1 MB | EXE | AS3.0_HW_X20cBC1083.exe | |
Popis |
V3.0 HW Upgrade (X20cBC1083) Revision information X20cBC1083 Version 2.8.0.0: ID: 619155 DNA: PLK hub forwarding for the next node not enabled in rare cases Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 619190 Outputs of I/O modules behind the bus coupler not working in some cases if poll-response chaining active Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 623065 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(426) Version 2.7.0.0: ID: 586750 / Support ID: 400241376 Temporary toggling of data point ModuleOk if I/O module fails Channel description changed:No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(424) Version 2.6.0.0: ID: 572710 Corrected L/A LEDs for hardware revision H0 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574320 / Support ID: 0, 400235528, 400235970 Unable to start netXIF card on X20BC1083 in isolated cases Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574325 / Support ID: 400230671 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware:1\57879_3.fw(423) Version 2.5.6.0: ID: 551130 Startup time optimizations Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(421) Version 2.5.5.0: ID: 545100 NetX Firmware update bug fix Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(420) Version 2.5.4.0: ID: 540325 / Support ID: 400202320 BC sporadically not going into Operational due to X2X-bus problems at startup Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(419) Version 2.5.3.0: ID:523495 / Support ID: 400205694 safety modules not switching to operational state SDO streaming connection via UDP is not always established when PLC and SafeLogic are booted together. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(417) Version 2.5.2.0: ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752 First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s. Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494195 / Support ID: 400191269 X20BC1083 with disabled netX modules is not booting - Error 32162 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494200 / Support ID: 400189834 X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(415) Version 2.5.0.0: ID: 467890 Restart of the netX interface card If PLK-failure the netX interface card is reset by the Bus Controller Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468100 / Support ID: 400178654 Safety modules in connection with PLK BCs, with onlyinput datapoints, are not initialized.by SL Channel description changed:No Configuration description changed: No Firmware changed: Yes ID: 468105 / Support ID: 400177243 X2X FW update of several X2X modules is not working Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468110 optimization of X2X FW updates Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468540 CiR support Channel description changed: No Configuration description changed: Yes Firmware changed: No Firmware: 1\57879_3.fw(413) Version 1.3.0.0: ID: 460115 / Support ID: 400168329 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 460235 /Support ID: 400150525 Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(411) Version 1.2.0.0: ID: 439110 / Support ID:400150496 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 439215 / Support ID: 400128436 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-oncycles Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(400) Version 1.1.0.0: ID: 402430 X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed. When empty backplanesare plugged or unplugged on the end of the X2XLink thediagnostic data point "StationAtBusEnd" die not change. The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing. Channel description changed: Yes Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(300) Version 1.0.0.1: ID: 343245 Support X20cBC1083 Support for Automation Studio Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\57879_3.fw(210) |
|||||
Verze | Jazyk | Operační systém | Datum | Velikost | Typ | Stáhnout |
2.7.0.0 | * | 17.04.2018 | 1 MB | EXE | AS3.0_HW_X20cBC1083.exe | |
Popis |
V3.0 HW Upgrade (X20cBC1083) Revision information X20cBC1083 Version 2.7.0.0: ID: 586750 / Support ID: 400241376 Temporary toggling of data point ModuleOk if I/O module fails Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(424) Version 2.6.0.0: ID: 572710 Corrected L/A LEDs for hardware revision H0 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574320 / Support ID: 0, 400235528, 400235970 Unable to start netX IF card on X20BC1083 in isolated cases Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574325 / Support ID: 400230671 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(423) Version 2.5.6.0: ID: 551130 Startuptime optimizations Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(421) Version 2.5.5.0: ID: 545100 NetX Firmware update bug fix Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(420) Version 2.5.4.0: ID: 540325 / Support ID: 400202320 BC sporadically not going into Operational due to X2X-bus problems at startup Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(419) Version 2.5.3.0: ID: 523495 / Support ID: 400205694 safety modules not switching to operational state SDO streaming connection via UDP is not always established when PLC and SafeLogic are booted together. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(417) Version 2.5.2.0: ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752 First POWERLINK UDP ASndSDO transfert after long time takes up to 5s. Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494195 / Support ID: 400191269 X20BC1083 with disabled netX modules is not booting - Error 32162 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494200 / Support ID: 400189834 X20IF1091-1 + X20BC1083 + X20IF10E1-1 causeservice of PLC and error 30023 in logger Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(415) Version 2.5.0.0: ID: 467890 Restart of the netX interface card If PLK-failure the netX interface card isreset by the Bus Controller Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468100 / Support ID: 400178654 Safety modules in connection with PLK BCs, with only input datapoints, are not initialized.by SL Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468105 / Support ID: 400177243 X2X FW update of several X2X modules is not working Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468110 optimization of X2X FW updates Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468540 CiR support Channel description changed: No Configuration description changed: Yes Firmware changed: No Firmware: 1\57879_3.fw(413) Version 1.3.0.0: ID: 460115 / Support ID: 400168329 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 460235 / Support ID: 400150525 Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(411) Version 1.2.0.0: ID: 439110 / Support ID: 400150496 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel descriptionchanged: No Configuration description changed: No Firmware changed:Yes ID: 439215 / Support ID: 400128436 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration descriptionchanged: No Firmware changed: Yes Firmware: 1\57879_3.fw(400) Version 1.1.0.0: ID: 402430 X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed. When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change. The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problemalso occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing. Channel description changed: Yes Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(300) Version 1.0.0.1: ID: 343245 Support X20cBC1083 Support for Automation Studio Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\57879_3.fw(210) |
|||||
Verze | Jazyk | Operační systém | Datum | Velikost | Typ | Stáhnout |
2.6.0.0 | * | 09.02.2018 | 1 MB | EXE | AS3.0_HW_X20cBC1083.exe | |
Popis |
V3.0 HW Upgrade (X20cBC1083) Revision information X20cBC1083 Version 2.6.0.0: ID: 572710 Corrected L/A LEDs for hardware revision H0 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 574320 / Support ID: 0, 400235528, 400235970 Unable to start netX IF card on X20BC1083 in isolated cases Channel description changed: No Configuration description changed:No Firmware changed: Yes ID: 574325 / Support ID: 400230671 Error 30285 with error code 0x8047 after changing the netX configuration Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(423) Version 2.5.6.0: ID: 551130 Startup time optimizations Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(421) Version 2.5.5.0: ID: 545100 NetX Firmware update bug fix Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(420) Version 2.5.4.0: ID: 540325 / SupportID: 400202320 BC sporadically not going into Operational due to X2X-bus problems at startup Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(419) Version 2.5.3.0: ID: 523495 / Support ID: 400205694 safety modules not switching to operational state SDO streaming connectionvia UDP is not always established when PLC and SafeLogic are booted together. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(417) Version 2.5.2.0: ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752 First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s. Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494195 / Support ID: 400191269 X20BC1083 with disabled netX modules is not booting - Error 32162 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 494200 / Support ID: 400189834 X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(415) Version 2.5.0.0: ID: 467890 Restart of the netX interface card If PLK-failure the netX interface card is reset by the Bus Controller Channeldescription changed: No Configuration description changed: No Firmware changed: Yes ID: 468100 / Support ID: 400178654 Safety modules in connection with PLK BCs, with only input datapoints, are not initialized.by SL Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468105 / Support ID: 400177243 X2X FW update of several X2X modules is not working Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 468110 optimization of X2X FW updates Channeldescription changed: No Configuration description changed: No Firmware changed: Yes ID: 468540 CiR support Channel descriptionchanged: No Configuration description changed: Yes Firmware changed: No Firmware: 1\57879_3.fw(413) Version 1.3.0.0: ID: 460115 / Support ID: 400168329 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 460235 / Support ID: 400150525 Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(411) Version 1.2.0.0: ID: 439110 / Support ID: 400150496 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 439215 / Support ID: 400128436 I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(400) Version 1.1.0.0: ID: 402430 X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed. When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change. The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing. Channel description changed: Yes Configuration description changed: No Firmware changed: Yes Firmware: 1\57879_3.fw(300) Version 1.0.0.1: ID: 343245 Support X20cBC1083 Support for Automation Studio Channel description changed: No Configuration description changed: No Firmware changed: No Firmware: 1\57879_3.fw(210) |