2.12.0.0 * 08.10.2020 2 MB EXE AS3.0_HW_X20cBC1083.exe
Popis V3.0 HW Upgrade (X20cBC1083)

Revision information X20cBC1083

Version 2.12.0.0:

ID: 703010
FW Update of the X2X modules connected to the X20IF1091-1 at each startup (Rev. >= I0)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(431), 1\57879_4.fw(431), 1\57879_5.fw(431)

Version 2.11.1.0:

ID: 695155
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 695455
Module documentation revised
Data sheet V2.49
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57879_3.fw(430), 1\57879_4.fw(430)

Version 2.11.0.0:

ID: 664385
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 664400
DNA: Hub of PLK BC active until first IDENT_REQUEST
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 665765 / Support ID: 400266182, 400285939
ModuleOk of IO module FALSE after warm restart even though the module is working as expected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 665845
Accessing non-cyclic registers with AsIOAcc while ModuleOk = FALSE preventsmodule from starting/communicating
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 666210
Module documentation revised
Data sheet V2.48
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 678955
Support HW-variant 4
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(430), 1\57879_4.fw(430)

Version 2.9.0.0:

ID: 623855
Optimization of synchronization between X20BC1083 and X20IF1091-1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628940
Optimization of hub behavior
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628965
Wrong serial number in SystemDump when X20IF1091-1 is used on a X20BC1083
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629020
Ring redundancy: Cannot address the CN that closes the ring
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629085
DNA: BC as head-end station switching hub off again
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629170
Shortened preamble of Ethernet frame leading to incorrectly detected CRC errors
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(427)

Version 2.8.0.0:

ID: 619155
DNA: PLK hub forwarding for the next node not enabled in rare cases
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 619190
Outputs of I/O modules behind the bus coupler not working in some cases if poll-response chaining active
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 623065
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(426)

Version 2.7.0.0:

ID: 586750 / Support ID: 400241376
Temporary toggling of data point ModuleOk if I/O modulefails
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(424)

Version 2.6.0.0:

ID: 572710
Corrected L/A LEDs for hardware revision H0
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574320 / Support ID: 0, 400235528, 400235970
Unable to start netX IF card on X20BC1083 in isolated cases
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes

ID: 574325 / Support ID: 400230671
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(423)

Version 2.5.6.0:

ID: 551130
Startup time optimizations
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(421)

Version 2.5.5.0:

ID: 545100
NetX Firmware update bug fix
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(420)

Version 2.5.4.0:

ID: 540325 / SupportID: 400202320
BC sporadically not going into Operational due to X2X-bus problems at startup
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(419)

Version 2.5.3.0:

ID: 523495 / Support ID: 400205694
safety modules not switching to operational state
SDO streaming connectionvia UDP is not always established when PLC and SafeLogic are booted together.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(417)

Version 2.5.2.0:

ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752
First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494195 / Support ID: 400191269
X20BC1083 with disabled netX modules is not booting - Error 32162
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494200 / Support ID: 400189834
X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(415)

Version 2.5.0.0:

ID: 467890
Restart of the netX interface card
If PLK-failure the netX interface card is reset by the Bus Controller
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468100 / Support ID: 400178654
Safety modules in connection with PLK BCs, with only input datapoints, are not initialized.by SL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468105 / Support ID: 400177243
X2X FW update of several X2X modules is not working
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468110
optimization of X2X FW updates
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468540
CiR support
Channel descriptionchanged: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57879_3.fw(413)

Version 1.3.0.0:

ID: 460115 / Support ID: 400168329
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 460235 / Support ID: 400150525
Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(411)

Version 1.2.0.0:

ID: 439110 / Support ID: 400150496
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 439215 / Support ID: 400128436
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(400)

Version 1.1.0.0:

ID: 402430
X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed.
When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change.
The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(300)

Version 1.0.0.1:

ID: 343245
Support X20cBC1083
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57879_3.fw(210)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.11.0.0 * 10.02.2020 1 MB EXE AS3.0_HW_X20cBC1083.exe
Popis V3.0 HW Upgrade (X20cBC1083)

Revision information X20cBC1083

Version 2.11.0.0:

ID: 664385
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 664400
DNA: Hub of PLK BC active until first IDENT_REQUEST
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 665765 /Support ID: 400266182, 400285939
ModuleOk of IO module FALSE after warm restart even though the module is working as expected
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes

ID: 665845
Accessing non-cyclic registers with AsIOAcc while ModuleOk = FALSE preventsmodule from starting/communicating
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes

ID: 666210
Module documentation revised
Data sheet V2.48
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 678955
Support HW-variant 4
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(430), 1\57879_4.fw(430)

Version 2.9.0.0:

ID: 623855
Optimization of synchronization between X20BC1083 and X20IF1091-1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628940
Optimization of hub behavior
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628965
Wrong serial number in SystemDump when X20IF1091-1 is used on a X20BC1083
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629020
Ring redundancy: Cannot address the CN that closes the ring
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629085
DNA: BC as head-end station switching huboff again
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: Yes

ID: 629170
Shortened preamble of Ethernet frame leading to incorrectly detected CRC errors
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(427)

Version 2.8.0.0:

ID: 619155
DNA: PLK hub forwarding for the next node not enabled inrare cases
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 619190
Outputs of I/O modules behind the bus coupler not working in some cases if poll-response chaining active
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 623065
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(426)

Version 2.7.0.0:

ID: 586750 / Support ID: 400241376
Temporary toggling of data point ModuleOk if I/O module fails
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(424)

Version 2.6.0.0:

ID: 572710
Corrected L/A LEDsfor hardware revision H0
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574320 / Support ID: 0, 400235528, 400235970
Unable to start netX IF card on X20BC1083 in isolated cases
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574325 / Support ID: 400230671
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(423)

Version 2.5.6.0:

ID: 551130
Startup time optimizations
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(421)

Version 2.5.5.0:

ID: 545100
NetX Firmware update bug fix
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(420)

Version 2.5.4.0:

ID: 540325 / Support ID: 400202320
BC sporadically not going into Operational due to X2X-bus problems at startup
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(419)

Version 2.5.3.0:

ID: 523495 / Support ID: 400205694
safety modules not switching to operational state
SDO streaming connection via UDP is not always established when PLC and SafeLogic are booted together.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(417)

Version 2.5.2.0:

ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752
First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494195 / Support ID: 400191269
X20BC1083 with disabled netX modules is not booting - Error 32162
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494200 / Support ID: 400189834
X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(415)

Version 2.5.0.0:

ID: 467890
Restart of the netX interface card
If PLK-failure the netX interface card is reset by the Bus Controller
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468100 / Support ID: 400178654
Safety modules in connection with PLK BCs, with only input datapoints,are not initialized.by SL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468105 / Support ID: 400177243
X2X FW update of several X2X modules is not working
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468110
optimization of X2X FW updates
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468540
CiR support
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57879_3.fw(413)

Version 1.3.0.0:

ID: 460115 / Support ID: 400168329
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 460235 / Support ID: 400150525
Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(411)

Version 1.2.0.0:

ID: 439110 / Support ID: 400150496
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 439215 / Support ID: 400128436
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(400)

Version 1.1.0.0:

ID: 402430
X2XLink-BC: StationAtBusEnd does not change, when emptybackplanes are addedor removed.
When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change.
The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implementedto update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(300)

Version 1.0.0.1:

ID: 343245
Support X20cBC1083
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57879_3.fw(210)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.9.0.0 * 15.02.2019 1 MB EXE AS3.0_HW_X20cBC1083.exe
Popis V3.0 HW Upgrade (X20cBC1083)

Revision information X20cBC1083

Version 2.9.0.0:

ID: 623855
Optimization of synchronization between X20BC1083 and X20IF1091-1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628940
Optimization of hub behavior
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628965
Wrong serial number in SystemDump when X20IF1091-1 is used on a X20BC1083
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629020
Ring redundancy: Cannot address the CN that closes the ring
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629085
DNA: BC as head-end station switching hub off again
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629170
Shortened preamble of Ethernet frame leading to incorrectly detected CRC errors
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(427)

Version 2.8.0.0:

ID: 619155
DNA: PLK hub forwarding for the next node not enabled in rare cases
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 619190
Outputs of I/O modules behind the bus coupler not working in some cases if poll-response chaining active
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 623065
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(426)

Version 2.7.0.0:

ID: 586750 / Support ID: 400241376
Temporary toggling of data point ModuleOk if I/O modulefails
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(424)

Version 2.6.0.0:

ID: 572710
Corrected L/A LEDs for hardware revision H0
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574320 / Support ID: 0, 400235528, 400235970
Unable to start netX IF card on X20BC1083 in isolated cases
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes

ID: 574325 / Support ID: 400230671
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(423)

Version 2.5.6.0:

ID: 551130
Startup time optimizations
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(421)

Version 2.5.5.0:

ID: 545100
NetX Firmware update bug fix
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(420)

Version 2.5.4.0:

ID: 540325 / SupportID: 400202320
BC sporadically not going into Operational due to X2X-bus problems at startup
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(419)

Version 2.5.3.0:

ID: 523495 / Support ID: 400205694
safety modules not switching to operational state
SDO streaming connectionvia UDP is not always established when PLC and SafeLogic are booted together.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(417)

Version 2.5.2.0:

ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752
First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494195 / Support ID: 400191269
X20BC1083 with disabled netX modules is not booting - Error 32162
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494200 / Support ID: 400189834
X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(415)

Version 2.5.0.0:

ID: 467890
Restart of the netX interface card
If PLK-failure the netX interface card is reset by the Bus Controller
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468100 / Support ID: 400178654
Safety modules in connection with PLK BCs, with only input datapoints, are not initialized.by SL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468105 / Support ID: 400177243
X2X FW update of several X2X modules is not working
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468110
optimization of X2X FW updates
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468540
CiR support
Channel descriptionchanged: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57879_3.fw(413)

Version 1.3.0.0:

ID: 460115 / Support ID: 400168329
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 460235 / Support ID: 400150525
Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(411)

Version 1.2.0.0:

ID: 439110 / Support ID: 400150496
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 439215 / Support ID: 400128436
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(400)

Version 1.1.0.0:

ID: 402430
X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed.
When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change.
The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(300)

Version 1.0.0.1:

ID: 343245
Support X20cBC1083
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57879_3.fw(210)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.8.0.0 * 05.12.2018 1 MB EXE AS3.0_HW_X20cBC1083.exe
Popis V3.0 HW Upgrade (X20cBC1083)

Revision information X20cBC1083

Version 2.8.0.0:

ID: 619155
DNA: PLK hub forwarding for the next node not enabled in rare cases
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 619190
Outputs of I/O modules behind the bus coupler not working in some cases if poll-response chaining active
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 623065
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(426)

Version 2.7.0.0:

ID: 586750 / Support ID: 400241376
Temporary toggling of data point ModuleOk if I/O module fails
Channel description changed:No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(424)

Version 2.6.0.0:

ID: 572710
Corrected L/A LEDs for hardware revision H0
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574320 / Support ID: 0, 400235528, 400235970
Unable to start netXIF card on X20BC1083 in isolated cases
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574325 / Support ID: 400230671
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware:1\57879_3.fw(423)

Version 2.5.6.0:

ID: 551130
Startup time optimizations
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(421)

Version 2.5.5.0:

ID: 545100
NetX Firmware update bug fix
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(420)

Version 2.5.4.0:

ID: 540325 / Support ID: 400202320
BC sporadically not going into Operational due to X2X-bus problems at startup
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(419)

Version 2.5.3.0:

ID:523495 / Support ID: 400205694
safety modules not switching to operational state
SDO streaming connection via UDP is not always established when PLC and SafeLogic are booted together.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(417)

Version 2.5.2.0:

ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752
First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494195 / Support ID: 400191269
X20BC1083 with disabled netX modules is not booting - Error 32162
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494200 / Support ID: 400189834
X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(415)

Version 2.5.0.0:

ID: 467890
Restart of the netX interface card
If PLK-failure the netX interface card is reset by the Bus Controller
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468100 / Support ID: 400178654
Safety modules in connection with PLK BCs, with onlyinput datapoints, are not initialized.by SL
Channel description changed:No
Configuration description changed: No
Firmware changed: Yes

ID: 468105 / Support ID: 400177243
X2X FW update of several X2X modules is not working
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468110
optimization of X2X FW updates
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468540
CiR support
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57879_3.fw(413)

Version 1.3.0.0:

ID: 460115 / Support ID: 400168329
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 460235 /Support ID: 400150525
Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(411)

Version 1.2.0.0:

ID: 439110 / Support ID:400150496
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 439215 / Support ID: 400128436
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-oncycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(400)

Version 1.1.0.0:

ID: 402430
X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed.
When empty backplanesare plugged or unplugged on the end of the X2XLink thediagnostic data point "StationAtBusEnd" die not change.
The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(300)

Version 1.0.0.1:

ID: 343245
Support X20cBC1083
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57879_3.fw(210)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.7.0.0 * 17.04.2018 1 MB EXE AS3.0_HW_X20cBC1083.exe
Popis V3.0 HW Upgrade (X20cBC1083)

Revision information X20cBC1083

Version 2.7.0.0:

ID: 586750 / Support ID: 400241376
Temporary toggling of data point ModuleOk if I/O module fails
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(424)

Version 2.6.0.0:

ID: 572710
Corrected L/A LEDs for hardware revision H0
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574320 / Support ID: 0, 400235528, 400235970
Unable to start netX IF card on X20BC1083 in isolated cases
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574325 / Support ID: 400230671
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(423)

Version 2.5.6.0:

ID: 551130
Startuptime optimizations
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(421)

Version 2.5.5.0:

ID: 545100
NetX Firmware update bug fix
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(420)

Version 2.5.4.0:

ID: 540325 / Support ID: 400202320
BC sporadically not going into Operational due to X2X-bus problems at startup
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(419)

Version 2.5.3.0:

ID: 523495 / Support ID: 400205694
safety modules not switching to operational state
SDO streaming connection via UDP is not always established when PLC and SafeLogic are booted together.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(417)

Version 2.5.2.0:

ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752
First POWERLINK UDP ASndSDO transfert after long time takes up to 5s.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494195 / Support ID: 400191269
X20BC1083 with disabled netX modules is not booting - Error 32162
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494200 / Support ID: 400189834
X20IF1091-1 + X20BC1083 + X20IF10E1-1 causeservice of PLC and error 30023 in logger
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(415)

Version 2.5.0.0:

ID: 467890
Restart of the netX interface card
If PLK-failure the netX interface card isreset by the Bus Controller
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468100 / Support ID: 400178654
Safety modules in connection with PLK BCs, with only input datapoints, are not initialized.by SL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468105 / Support ID: 400177243
X2X FW update of several X2X modules is not working
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468110
optimization of X2X FW updates
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468540
CiR support
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57879_3.fw(413)

Version 1.3.0.0:

ID: 460115 / Support ID: 400168329
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 460235 / Support ID: 400150525
Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(411)

Version 1.2.0.0:

ID: 439110 / Support ID: 400150496
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes

ID: 439215 / Support ID: 400128436
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(400)

Version 1.1.0.0:

ID: 402430
X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed.
When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change.
The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problemalso occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(300)

Version 1.0.0.1:

ID: 343245
Support X20cBC1083
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57879_3.fw(210)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.6.0.0 * 09.02.2018 1 MB EXE AS3.0_HW_X20cBC1083.exe
Popis V3.0 HW Upgrade (X20cBC1083)

Revision information X20cBC1083

Version 2.6.0.0:

ID: 572710
Corrected L/A LEDs for hardware revision H0
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 574320 / Support ID: 0, 400235528, 400235970
Unable to start netX IF card on X20BC1083 in isolated cases
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes

ID: 574325 / Support ID: 400230671
Error 30285 with error code 0x8047 after changing the netX configuration
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(423)

Version 2.5.6.0:

ID: 551130
Startup time optimizations
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(421)

Version 2.5.5.0:

ID: 545100
NetX Firmware update bug fix
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(420)

Version 2.5.4.0:

ID: 540325 / SupportID: 400202320
BC sporadically not going into Operational due to X2X-bus problems at startup
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(419)

Version 2.5.3.0:

ID: 523495 / Support ID: 400205694
safety modules not switching to operational state
SDO streaming connectionvia UDP is not always established when PLC and SafeLogic are booted together.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(417)

Version 2.5.2.0:

ID: 493895 / Support ID: 400103115, 400101850, 400154063, 400190752
First POWERLINK UDP ASnd SDO transfert after long time takes up to 5s.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494195 / Support ID: 400191269
X20BC1083 with disabled netX modules is not booting - Error 32162
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 494200 / Support ID: 400189834
X20IF1091-1 + X20BC1083 + X20IF10E1-1 cause service of PLC and error 30023 in logger
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(415)

Version 2.5.0.0:

ID: 467890
Restart of the netX interface card
If PLK-failure the netX interface card is reset by the Bus Controller
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468100 / Support ID: 400178654
Safety modules in connection with PLK BCs, with only input datapoints, are not initialized.by SL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468105 / Support ID: 400177243
X2X FW update of several X2X modules is not working
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468110
optimization of X2X FW updates
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 468540
CiR support
Channel descriptionchanged: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57879_3.fw(413)

Version 1.3.0.0:

ID: 460115 / Support ID: 400168329
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 460235 / Support ID: 400150525
Error 114834 "Fehler interner SLX-Kommandokanal" bei CPU PowerCycle wenn SLX hinter BC
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(411)

Version 1.2.0.0:

ID: 439110 / Support ID: 400150496
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 439215 / Support ID: 400128436
I/O modules behind POWERLINK bus controllers no longer achieving Operational mode after multiple power-on cycles
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(400)

Version 1.1.0.0:

ID: 402430
X2XLink-BC: StationAtBusEnd does not change, when empty backplanes are added or removed.
When empty backplanes are plugged or unplugged on the end of the X2XLink the diagnostic data point "StationAtBusEnd" die not change.
The data point die change when IO Modules were removed or added. A new handshake between Automation Runtime and firmware was implemented to update the "StationAtBusEnd" faster. The same problem also occurs with modules where the X2XLink is supplied with power, but the supply for the IO is missing.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57879_3.fw(300)

Version 1.0.0.1:

ID: 343245
Support X20cBC1083
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57879_3.fw(210)