Short description
Bus controller OPC UA server
General information
B&R ID code 0xEAFB
Status indicators Module status, bus function
Diagnostics
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator and software
Power consumption
Bus 2.5 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
EAC Yes
Interfaces
Fieldbus OPC UA server
Variant 2x shielded RJ45 (switch)
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex Yes
Autonegotiation Yes
Auto-MDI/MDIX Yes
Min. cycle time
Fieldbus 10 ms
X2X Link 2 ms
Synchronization between bus systems possible Yes
Electrical properties
Electrical isolation OPC UA isolated from bus and I/O
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 or X20PS9402 separately.
Order 1x bus base X20BB80 separately.
Pitch 37.5+0.2 mm
Materialnummer:
X20BC008U
Beskrivning:
  • Protocol: OPC UA
  • I/O configuration via OPC UA
  • 10 ms minimum cycle time
  • Integrated switch for wiring multiple slaves
  • 100 Mbit/s full-duplex mode
  • Up to 1440 bytes of input data and up to 1440 bytes of output data possible
  • Integrated web page for firmware updates
  • OPC UA diagnostics and module diagnostics at runtime via OPC UA clients

This bus controller provides OPC UA server functions. This allows any OPC UA clients access to read or write data from I/O modules connected to the bus controller.

Obligatoriska tillbehör
System modules for bus controllers
X20BB80 X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20PS9400 X20 power supply module, for bus controller and internal I/O power supply X2X Link power supply
X20PS9402 X20 power supply module, for bus controller and internal I/O power supply, X2X Link supply, supply not galvanically isolated
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Certifikat Version (datum) Ladda ner
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
UK Declaration PLC X20 PDF / 151 KB
Dokumentation Version (datum) Ladda ner
Data sheet X20BC008U PDF / 796 KB
Installation- / EMC-Guide PDF / 20 MB
OPC UA Bus Controller User's manual PDF / 9 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Electro eller EPLAN mallar) Version (datum) Ladda ner
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. mallar) Version (datum) Ladda ner
3D File STEP/DXF X20BC and X20IF Module ZIP / 1 MB
Mjukvaruuppdateringar Version (datum) Ladda ner
Firmwareupgrade X20BC008U ZIP / 493 KB

Välj land och språk

B&R Logo