Normally open contact and normally closed contact, max. 30 VDC, max. 1 A
Certifications
CE
Yes
UKCA
Yes
CRA (Cyber Resilience Act)
Evaluation ongoing
UL
cULus E115267 Industrial control equipment
DNV
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck)
CCS
Yes
LR
ENV3
KR
Yes
ABS
Yes
BV
EC31B Temperature: 5 - 55°C Vibration: 0.7 g EMC: Bridge and open deck
Electrical properties
Power consumption
0.5 W
Operating conditions
Pollution degree per EN 61131-2
Pollution degree 2
Ambient conditions
Temperature
Operation
0 to 60°C
Storage
-20 to 60°C
Transport
-20 to 60°C
Relative humidity
Operation
5 to 90%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical properties
Weight
Approx. 30 g
Material number:
5AC901.ISIO-00
Description:
Connections for the reset button and power buttons on the PC
Connection for LED "Power" on the PC
1 normally closed contact, 1 normally open contact of the ready relay
Control of the ready relay functions using MTCX commands
Compatible with APC910/PPC900, APC3x00/PPC3x00 and APC4100
The ready relay function of IF option 5AC901.ISIO-00 can be controlled using the MTCX. Corresponding commands must be issued by the MTCX in order to switch the ready relay.
In addition to the ready relay function, the reset and power button as well as the power LED of a B&R PC can be routed externally.