1.9.2.0 * 20/11/2023 2 Mo EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.9.2.0:

ID: 705165
Not possible to use both connectors on X20IF2181-2 when is used as Ethernetdevice
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\50099_0.pci(59148), 1\50099_1.pci(59138), 1\50099a0.epl(231), 1\50099a1.epl(231)

Version 1.9.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.8.0.0:

ID: 693960
POWERLINK: Operating mode "Ethernet"
If a POWERLINKinterface was operated in operating mode "Ethernet" and connected to a POWERLINK network in this mode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(59148), 1\50099_1.pci(59138), 1\50099a0.epl(231), 1\50099a1.epl(231)

Version 1.7.1.0:

ID: 698355
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.7.0.0:

ID: 676435
Support HW-variant 1
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.6.0.0:

ID: 675020
CPURED: Bus controller shows ModuleOK = FALSE during CPU redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099a0.epl(229)

Version 1.5.0.0:

ID: 603760 / Support ID: 400253132
Controller redundancy and ring redundancy:
When using controller redundancy and ring redundancy, the redundancy switchover or the opening or closing of the ring could lead to the failure of CNs, especially with larger network expansions.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629330
Module documentation revised
Data sheet V1.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(58124), 1\50099a0.epl(227)

Version 1.4.0.0:

ID: 573700
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56586), 1\50099a0.epl(221)

Version 1.3.3.0:

ID: 542405 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330), 1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
When the ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version >= C4.26 or A4.33 is also needed for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to fail of CN´s
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy:POWERLINK cycle time violation caused by configured but unconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID:457680
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54791), 1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controlled node" mode: Cross-communication wasn't working.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.9.0.0 * 23/07/2021 1 Mo EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.9.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.8.0.0:

ID: 693960
POWERLINK: Operating mode "Ethernet"
If a POWERLINK interface was operatedin operating mode "Ethernet" and connected to a POWERLINK network in this mode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(59148), 1\50099_1.pci(59138), 1\50099a0.epl(231), 1\50099a1.epl(231)

Version 1.7.1.0:

ID: 698355
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.7.0.0:

ID: 676435
Support HW-variant 1
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.6.0.0:

ID: 675020
CPURED: Bus controller shows ModuleOK = FALSE during CPU redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099a0.epl(229)

Version 1.5.0.0:

ID: 603760 / Support ID: 400253132
Controller redundancy and ring redundancy:
When using controller redundancy and ring redundancy, the redundancy switchover or the opening orclosing of the ring could lead to the failure of CNs, especially with larger network expansions.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629330
Module documentation revised
Data sheet V1.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(58124), 1\50099a0.epl(227)

Version 1.4.0.0:

ID: 573700
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56586), 1\50099a0.epl(221)

Version 1.3.3.0:

ID: 542405 / Support ID: 400204420
POWERLINK V2: no asynchronousframes in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in thefirmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330), 1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
When the ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version &gt;= C4.26 or A4.33 is also needed for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to fail of CN´s
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy: POWERLINK cycle time violation caused by configured but unconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 457680
IP packetswith multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54791), 1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controlled node" mode: Cross-communication wasn't working.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.8.0.0 * 22/06/2021 1 Mo EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.8.0.0:

ID: 693960
POWERLINK: Operating mode "Ethernet"
If a POWERLINK interface was operated in operating mode "Ethernet" andconnected to a POWERLINK network in this mode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(59148), 1\50099_1.pci(59138), 1\50099a0.epl(231), 1\50099a1.epl(231)

Version 1.7.1.0:

ID: 698355
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.7.0.0:

ID: 676435
Support HW-variant 1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.6.0.0:

ID: 675020
CPURED: Bus controller shows ModuleOK = FALSE during CPU redundancy switchover
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes
Firmware: 1\50099_0.pci(58636), 1\50099a0.epl(229)

Version 1.5.0.0:

ID: 603760 / Support ID: 400253132
Controller redundancy and ring redundancy:
When using controller redundancy and ring redundancy, the redundancy switchover or the opening or closing of the ring could lead to the failure of CNs, especially with larger network expansions.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629330
Module documentation revised
Data sheet V1.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(58124),1\50099a0.epl(227)

Version 1.4.0.0:

ID: 573700
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56586), 1\50099a0.epl(221)

Version 1.3.3.0:

ID: 542405 / Support ID:400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that noasynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330), 1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
When the ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version &gt;= C4.26 or A4.33 is also needed for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to fail of CN´s
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configurationdescription changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy: POWERLINK cycle time violation caused by configured butunconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 457680
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54791),1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controlled node" mode: Cross-communication wasn't working.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.7.1.0 * 25/08/2020 1 Mo EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.7.1.0:

ID: 698355
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.7.0.0:

ID: 676435
Support HW-variant 1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.6.0.0:

ID: 675020
CPURED: Bus controller shows ModuleOK = FALSE during CPU redundancy switchover
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099a0.epl(229)

Version 1.5.0.0:

ID: 603760 / Support ID: 400253132
Controller redundancy and ring redundancy:
When using controller redundancy and ring redundancy, the redundancy switchover or the opening or closing of the ring could lead to the failure of CNs, especially with larger networkexpansions.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629330
Module documentation revised
Data sheet V1.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(58124), 1\50099a0.epl(227)

Version 1.4.0.0:

ID: 573700
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56586), 1\50099a0.epl(221)

Version 1.3.3.0:

ID: 542405 / Support ID: 400204420
POWERLINK V2: no asynchronous framesin mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330), 1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
When the ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version &gt;= C4.26 or A4.33 is also needed for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to fail of CN´s
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy: POWERLINK cycle time violation caused by configured but unconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 457680
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54791), 1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controlled node" mode: Cross-communication wasn't working.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.7.0.0 * 18/03/2020 1 Mo EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.7.0.0:

ID: 676435
Support HW-variant 1
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes
Firmware: 1\50099_0.pci(58636), 1\50099_1.pci(58625), 1\50099a0.epl(229), 1\50099a1.epl(229)

Version 1.6.0.0:

ID: 675020
CPURED: Bus controller shows ModuleOK = FALSE during CPU redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099a0.epl(229)

Version 1.5.0.0:

ID: 603760 / Support ID: 400253132
Controller redundancy and ring redundancy:
When using controller redundancy and ring redundancy, the redundancy switchover or the opening or closing of the ring could lead to the failure of CNs, especially with larger network expansions.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629330
Module documentation revised
Data sheet V1.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(58124), 1\50099a0.epl(227)

Version 1.4.0.0:

ID: 573700
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56586), 1\50099a0.epl(221)

Version 1.3.3.0:

ID: 542405 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330),1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
When the ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version&gt;= C4.26 or A4.33 is alsoneeded for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to fail of CN´s
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy: POWERLINK cycle time violation caused by configured but unconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: Yes

ID: 457680
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54791), 1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channel description changed:No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controlled node" mode: Cross-communication wasn't working.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.6.0.0 * 31/01/2020 1,017 Ko EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.6.0.0:

ID: 675020
CPURED: Bus controller shows ModuleOK = FALSE during CPU redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(58636), 1\50099a0.epl(229)

Version 1.5.0.0:

ID: 603760 / Support ID: 400253132
Controller redundancy and ring redundancy:
When using controller redundancy and ring redundancy, the redundancy switchover or the opening or closing of the ring could lead to the failure of CNs, especially with larger network expansions.
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes

ID: 629330
Module documentation revised
Data sheet V1.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(58124), 1\50099a0.epl(227)

Version 1.4.0.0:

ID: 573700
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56586), 1\50099a0.epl(221)

Version 1.3.3.0:

ID: 542405 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330), 1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
Whenthe ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version &gt;= C4.26 or A4.33 is alsoneeded for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to fail of CN´s
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy: POWERLINK cycle time violation caused by configured but unconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 457680
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54791), 1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controlled node" mode: Cross-communication wasn't working.
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.5.0.0 * 12/02/2019 972 Ko EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.5.0.0:

ID: 603760 / Support ID: 400253132
Controller redundancy and ring redundancy:
When using controller redundancy and ring redundancy, the redundancy switchover or the opening or closing of the ring could lead to the failure of CNs, especially with larger network expansions.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 629330
Module documentation revised
Data sheet V1.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(58124), 1\50099a0.epl(227)

Version 1.4.0.0:

ID: 573700
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56586), 1\50099a0.epl(221)

Version 1.3.3.0:

ID: 542405 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330), 1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
When the ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version &gt;= C4.26 or A4.33 is also needed for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to failof CN´s
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy: POWERLINK cycle time violation caused by configured but unconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 457680
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configurationdescription changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54791), 1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controlled node" mode: Cross-communication wasn't working.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed:No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.4.0.0 * 14/06/2018 952 Ko EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.4.0.0:

ID: 573700
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56586), 1\50099a0.epl(221)

Version 1.3.3.0:

ID: 542405 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330), 1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
When the ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version &gt;= C4.26 or A4.33 is also needed for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to fail of CN´s
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy: POWERLINK cycle time violation caused by configured but unconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 457680
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54791), 1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controlled node" mode: Cross-communication wasn't working.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
1.3.3.0 * 14/07/2017 952 Ko EXE AS4_HW_X20IF2181-2.exe
Description V4.0 HW Upgrade (X20IF2181-2)

Revision information X20IF2181-2

Version 1.3.3.0:

ID: 542405 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56330), 1\50099a0.epl(220)

Version 1.3.2.0:

ID: 516685
Controller redundancy + ring redundancy:
When the ring is broken, the "Switchover level" changes to "Major bump switchover possible". Automation Runtime version &gt;= C4.26 or A4.33 is also needed for this.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(56074), 1\50099a0.epl(219)

Version 1.3.1.0:

ID: 489720
Controller – Redundanz + Ringredundanz:
The combination of Controller – Redundanz + Ringredundanz with change of the ring state could lead to fail of CN´s
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 501000
Module documentation revised
Data sheet V1.13
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 503435
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(55818), 1\50099a0.epl(218)

Version 1.2.1.0:

ID: 454445
Controller redundancy: POWERLINK cycle time violation caused by configured but unconnected controlled nodes during redundancy switchover
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 457680
IP packets with multicast addresses not received by POWERLINK interface(problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes
Firmware: 1\50099_0.pci(54791), 1\50099a0.epl(214)

Version 1.2.0.0:

ID: 444980
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(54023), 1\50099a0.epl(211)

Version 1.0.1.0:

ID: 348342 / Support ID: 400127489
"controllednode" mode: Cross-communication wasn't working.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\50099_0.pci(52998), 1\50099a0.epl(207)

Version 1.0.0.1:

ID: 263045
First version.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\50099_0.pci(52227), 1\50099a0.epl(204)
Loading
Retour à la liste

Veuillez sélectionner un pays et une langue

B&R Logo