General information
Status display | Green LED on front panel |
Terminals | Robust connector |
RDY relay contact | Normally open contact |
Certifications |
Terminal block
Connection cross section | |
Flexible | 0.2 to 2.5 mm² / 22 to 12 AWG |
Inflexible | 0.2 to 2.5 mm² / 22 to 12 AWG |
Input
Input voltage |
AC 85-132 / 176-264V (switchable), 47-63Hz DC 210-375V |
Input current | <2.6 A (switch position 115 V) <BR/><1.4 A (switch position 230 V) |
External overcurrent protection |
Not required, unit equipped with internal fuse Recommendation: Fuse supply lines (circuit breaker) |
Transient immunity | Transient resistance according to VDE 0160 / W2 |
Output (including logic)
Output noise suppression | Unit complies with EN 61000-6-3 (class B) |
Output power | 120W |
Nominal voltage | 24 VDC |
Protection functions | Output protected against short circuit, open line and overload |
Permissible output load | 5 A |
Overvoltage protection | Typ. 29 V |
Efficiency, reliability
Efficiency | Typ. 89 % (230 VAC, 24 V / 5 A) |
MTBF | 480,000 h |
Losses | Typ. 14.8 W (230 VAC, 24 V / 5 A) |
Ambient conditions
Temperature | |
Operation | -10 to 70°C |
Storage | -25 to 85°C |
Relative humidity | |
Operation | Max. 95% |
Mechanical properties
Installation | Easy snap-on mounting onto the DIN rail |
Dimensions | |
Width | 64 mm |
Height | 124 mm |
Depth | 102 mm (+ rail) |
Weight | 620 g |
Ventilation/Cooling | Normal convection, no fan required |
Material number:
0PS105.2Description:
24 VDC Power Supply, 1 phase, 5 A, Redundant within parallel operation, Input 115/230 VAC, Manual Select, DIN Rail Mounting
Documentation | Version (Date) | Download |
---|---|---|
Datasheet 0PS105.2 | PDF / 339 KB |