Short description
Bus controller POWERLINK (V1/V2) controlled node
General information
Inputs/Outputs 6 digital inputs, 6 digital outputs (not configurable), inputs with additional function, 1 analog channel
Insulation voltage between channel and bus 500 Veff
Nominal voltage 24 VDC
B&R ID code
Bus controller 0x046C
Internal I/O module 0x04A8
Sensor/Actuator power supply 0.5 A summation current
Status indicators I/O function per channel, supply voltage, bus function
Diagnostics
Outputs Yes, using LED status indicator and software
I/O power supply Yes, using LED status indicator and software
Support
Dynamic node allocation (DNA) Yes
Connection type
Fieldbus M12, D-coded
X2X Link M12, B-coded
Inputs/Outputs 8x M12, A-coded
I/O power supply M8, 4-pin
Power output 15 W X2X Link power supply for I/O modules
Power consumption
Fieldbus 2.5 W
Internal I/O 0.6 W
X2X Link power supply 17.25 W at maximum power output for connected I/O modules
Certifications
CE Yes
UKCA Yes
Interfaces
Fieldbus POWERLINK (V1/V2) controlled node
Type Type 2
Variant 2x M12 interface (hub), 2x female connector on module
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex No
Autonegotiation Yes
Auto-MDI/MDIX Yes
Hub propagation delay 0.96 to 1 µs
Min. cycle time
Fieldbus 200 μs
X2X Link 250 μs
Synchronization between bus systems possible Yes
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Power consumption
Sensor/Actuator power supply Max. 12 W
Sensor/Actuator power supply
Voltage I/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 A Max. 2 VDC
Summation current Max. 0.5 A
Short-circuit proof Yes
Digital inputs
Input characteristics per EN 61131-2 Type 1
Input voltage 18 to 30 VDC
Input current at 24 VDC Typ. 4 mA
Input circuit Sink
Input resistance Typ. 6 kΩ
Switching threshold
Low <5 VDC
High >15 VDC
Edge detection / Time measurement
Counter size 16-bit
Counter frequency
Internal 10 kHz
Pulse length >200 µs with 200 µs pause between pulses
Signal form Square wave pulse
Measurement type Propagation delay measurement between output and corresponding feedback input
Analog inputs
Input 0 to 20 mA
Input type Differential input
Digital converter resolution 12-bit
Conversion time 200 µs
Output format INT
Output format
Current 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 μA
Load <300 Ω
Input protection Protection against wiring with supply voltage
Permissible input signal Max. ±30 mA
Output of digital value during overload
Undershoot 0x0000
Overshoot 0x7FFF
Conversion procedure Successive approximation
Max. error
Gain 0.1%
Offset 0.05%
Max. gain drift 0.013 %/°C
Max. offset drift 0.02 %/°C
Common-mode rejection
DC >50 dB
50 Hz >50 dB
Common-mode range ±2 V
Crosstalk between channels >70 dB
Nonlinearity <0.1%
Insulation voltage between input and bus 500 Veff
Voltage drop at 20 mA Typ. 4.5 V
Input filter
Cutoff frequency 1 kHz
Slope 40 dB
Digital outputs
Variant Current-sourcing FET
Switching voltage I/O power supply minus residual voltage
Nominal output current 0.5 A
Total nominal current 8 A
Output circuit Source
Output protection Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply
Diagnostic status Output monitoring with 10 ms delay
Leakage current when the output is switched off 5 µA
Switching on after overload shutdown Approx. 10 ms (depends on the module temperature)
RDS(on) 150 mΩ
Residual voltage <0.3 V at 0.5 A nominal current
Peak short-circuit current <12 A
Switching delay
0 → 1 <400 µs
1 → 0 <400 µs
Switching frequency
Resistive load Max. 100 Hz
Inductive load See section "Switching inductive loads".
Braking voltage when switching off inductive loads 50 VDC
Electrical properties
Electrical isolation Bus isolated from POWERLINK and channel
Channel not isolated from channel
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 155 mm
Depth 42 mm
Weight 360 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Material number:
X67BC8513.L12-1
Description:
  • POWERLINK V1/V2
  • Integrated hub for economical wiring
  • 12 digital channels, configurable as inputs or outputs
  • 1 analog input, 0 to 20 mA, 12-bit
  • M8 connection type
  • I/O configuration and firmware update via the fieldbus
  • Integrated connection to the local expansion via X2X Link for up to 250 additional modules
  • Configurable I/O cycle (starting at 200 µs)

The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler.

Additional X2X Link I/O nodes (X67 modules or other modules based on X2X Link) can be connected using the integrated X2X Link connection. Mechanically, POWERLINK is connected via an IP67-rated standard D-coded M12 Ethernet connector.

POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org.

Automation Studio HW Upgrades Version (Date) Download
V4.0 HW Upgrade (X67BC8513.L12-1) EXE / 2 MB
Certificates Version (Date) Download
EU Declaration ATEX X67 PDF / 191 KB
EU Declaration PLC X67 PDF / 674 KB
UK Declaration PLC X67 PDF / 469 KB
Documentation Version (Date) Download
Data sheet X67BC8513.L12-1 PDF / 6 MB
Installation- / EMC-Guide PDF / 20 MB
POWERLINK Bus Controller User's Manual PDF / 2 MB
X67 System User´s Manual PDF / 6 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
Makro-/Artikeldaten 4.0.1 (X67BC8513.L12-1) EXE / 1 MB

Please choose country and language