Short description
| I/O module |
2x M12 interface each with 2 safe type A digital inputs and 2 pulse outputs, 24 VDC, 2x standardized 8-pin M12 device interface each with 1 digital input without safety function and 2 safe type A digital inputs and 2 pulse outputs, 24 VDC and 1 digital output without safety function, 24 VDC, 0.6 A and 1 device power supply, 24 VDC, 2 A |
General information
Safety characteristics
| Note | See section "Safety characteristics". |
24 VDC output
| Output voltage | 24 VDC -15% / +20% |
| Output current | 2 A |
I/O power supply
| Nominal voltage | 24 VDC |
| Voltage range | 18 to 30 VDC |
| Integrated protective function | Reverse polarity protection |
Digital inputs
Safe digital inputs
Digital outputs
| Quantity | 2 |
| Variant | FET, positive switching, output level readable |
| Nominal voltage | 24 VDC |
| Switching voltage | I/O power supply minus voltage drop due to RDS(on) |
| Max. switching frequency | See section "Inrush current behavior for output channels". |
| Nominal output current | 0.6 A |
| Total nominal current | 1.2 A |
| Output protection | See section "Inrush current behavior for output channels". |
| Leakage current when the output is switched off | <500 μA |
| RDS(on) | 300 mΩ |
| Peak short-circuit current | See section "Inrush current behavior for output channels". |
| Braking voltage when switching off inductive loads | 50 VDC |
| Insulation voltage between channel and bus | 500 Veff |
| Max. capacitive load | 100 nF |
| Peak output current | 1 A |
Pulse outputs
Operating conditions
| Mounting orientation | |
| Any | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP67 |
Mechanical properties
| Dimensions | |
| Width | 53 mm |
| Height | 85 mm |
| Depth | 42 mm |
| Weight | 190 g |
| Torque for connections | |
| M8 | Max. 0.4 Nm |
| M12 | Max. 0.6 Nm |
型番:
X67SI8103説明:
- 8 safe digital inputs, sink circuit
- 2 pulse outputs - available on all 4 female connectors
- 2 standard inputs, sink circuit
- 2 standard outputs, source circuit
- Device supply
- Software input filter configurable for each channel
- Standardized 8-pin M12 device interface
This module is equipped with 8 safe digital inputs. They are designed for a nominal voltage of 24 VDC.
The module can be used to read various digital signals in safety-related applications up to PL e or SIL 3.
The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.
| Automation Studio HW アップグレード | バージョン (日付) | ダウンロード |
|---|---|---|
| V3.0 HW Upgrade (X67SI8103) | EXE / 3 MB | |
| V4.0 HW Upgrade (X67SI8103) | EXE / 3 MB | |
| V4.6 HW Upgrade (X67SI8103) | EXE / 2 MB | |
| V6.0 HW Upgrade (X67SI8103) | EXE / 980 KB |
| M-CAD (Mechan.Templates) | バージョン (日付) | ダウンロード |
|---|---|---|
| 3D file DFX/STEP X67SI8103 | ZIP / 3 MB |
| ツール / ユーティリティ / 例 | バージョン (日付) | ダウンロード |
|---|---|---|
| Sistema (VDMA) library | ZIP / 5 KB |
| ドキュメンテーション | バージョン (日付) | ダウンロード |
|---|---|---|
| Data sheets SafeIO and SafeLogic | PDF / 29 MB | |
| Integrated safety technology user's manual | PDF / 59 MB | |
| X67 System User´s Manual | PDF / 19 MB |