DWL@DWL10000857178
| 仕様版 | 言語 | オペレーティングシステム | 日付 | サイズ | タイプ | ダウンロード |
|---|---|---|---|---|---|---|
| 1.1.0.0 | * | 2026/05/22 | 845 KB | EXE | AS6_HW_X20DOF321.exe | |
| 説明 |
V6.0 HW Upgrade (X20DOF321) Revision information X20DOF321 Version 1.1.0.0: ID: TDYD-10682 Incorrectly configured modules were not identified on the X2X bus in certain circumstances. A dynamic hardware configuration is used for various customer applications.In this case, a default configuration is simply created in AS and the actual configuration is read out after the system has started up. Due to a hardware change of several I/Omodules, only a cyclic size of 12 bytes (previously 31 bytes) is accepted in the bootloader. If a module with more cyclic data (e.g. a safety module) is now configured, this module can no longer be identified on the bus. As a workaround, these "large" modules can be configured on other X2X slots. This problem can only be corrected with a new bootloader, which can onlybe delivered via production. Production will be switched to the new software accordingly. Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\10538_11.fw(160), 1\10538_20.fw(230) Version 1.0.0.0: ID: 728830 Support X20DOF321 HW11 Channel description changed: No Configuration description changed: No Firmware changed: Yes ID: 749100 Support X20DOF321 HW20 Channel description changed: No Configuration description changed: No Firmware changed: Yes Firmware: 1\10538_11.fw(160), 1\10538_20.fw(210) |
|||||