DWL@DWL10000857178

Версия Язык
Операционная система
Дата
Размер
Тип Загрузка
1.1.0.0 * 22.05.2026 845 кБ EXE AS6_HW_X20DOF321.exe
Описание V6.0 HW Upgrade (X20DOF321)

Revision information X20DOF321

Version 1.1.0.0:

ID: TDYD-10682
Incorrectly configured modules were not identified on the X2X bus in certain circumstances.
A dynamic hardware configuration is used for various customer applications.In this case, a default configuration is simply created in AS and the actual configuration is read out after the system has started up. Due to a hardware change of several I/Omodules, only a cyclic size of 12 bytes (previously 31 bytes) is accepted in the bootloader. If a module with more cyclic data (e.g. a safety module) is now configured, this module can no longer be identified on the bus. As a workaround, these "large" modules can be configured on other X2X slots. This problem can only be corrected with a new bootloader, which can onlybe delivered via production. Production will be switched to the new software accordingly.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\10538_11.fw(160), 1\10538_20.fw(230)

Version 1.0.0.0:

ID: 728830
Support X20DOF321 HW11
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 749100
Support X20DOF321 HW20
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\10538_11.fw(160), 1\10538_20.fw(210)