Short description
I/O module 4 inputs for potentiometer displacement gauge
General information
B&R ID code 0x9957
Status indicators Channel status, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Input Yes, using LED status indicator and software
Connection type
X2X Link M12, B-coded
Inputs 4x M12, A-coded
I/O power supply M8, 4-pin
Power consumption
Bus 0.75 W
Internal I/O 2 W
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Potentiometer power supply
Short-circuit proof Yes
Potentiometer supply voltage Upot 4.5 V / Max. 50 mA
Voltage drop for short-circuit protection at 50 mA Max. 0.13 VDC
Potentiometer, displacement gauge
Input type Single-ended input in the range of 0 to Upot
Digital converter resolution 15-bit
Measurement sensor 0.5 to 10 kΩ, potentiometer
Conversion time <200 µs for all channels
Output format INT (16-bit 2s complement)
Short-circuit protection Upot Yes
Influence of cable length Twisted and shielded conductors, cable length as short as possible, cable routing separate from load circuits, without intermediate terminal to sensor
Common-mode range 0 to Upot
Insulation voltage between input and bus 500 Veff
Quantization; LSB value (14-bit) 275 µV
Conversion procedure Sample & Hold
Output of digital value
Open circuit on GND 0x7FFF
Open circuit on slider 0x7FFF
Open circuit on Upot 0x0000
Valid range of values 0x0000 - 0x7FFF
Input filter
Cutoff frequency 10 kHz
Slope 60 dB/Dec.
Electrical properties
Electrical isolation Bus isolated from analog input
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 195 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Référence produit:
X67AI4850
Description:
  • 4 inputs for potentiometer displacement gauge

The module is a 4-channel analog input module. It is used to evaluate potentiometer displacement gauges.

Automation Studio HW Upgrades Version (date) Téléchargement
V2.6 HW Upgrade (X67AI4850) EXE / 1 Mo
V3.0 HW Upgrade (X67AI4850) EXE / 458 Ko
V3.0 HW Upgrade (X67AI4850) EXE / 2 Mo
V4.0 HW Upgrade (X67AI4850) EXE / 2 Mo
Certifications Version (date) Téléchargement
244665 CSA HazLoc CoC X20, X67 PDF / 158 Ko
E115267 UL CoC X67 PDF / 155 Ko
EU Declaration ATEX X67 PDF / 191 Ko
EU Declaration PLC X67 PDF / 674 Ko
TÜV 05 ATEX 7201 X PDF / 5 Mo
UK Declaration PLC X67 PDF / 469 Ko
X20, X67 KC certificates PDF / 6 Mo
Documentation Version (date) Téléchargement
Data sheet X67AI4850 PDF / 590 Ko
X67 System User´s Manual PDF / 6 Mo
E-CAD (modèles Electro ou EPLAN) Version (date) Téléchargement
X67 EPLAN P8 from V2.4 EXE / 105 Mo
M-CAD (modèles mécaniques) Version (date) Téléchargement
3D File DXF/STEP X67 ZIP / 4 Mo

Veuillez sélectionner un pays et une langue