Short description
Bus controller | POWERLINK (V1/V2) controlled node |
General information
Inputs/Outputs | 8 CAN interfaces |
Insulation voltage between channel and bus | 500 Veff |
Nominal voltage | 24 VDC |
B&R ID code | |
Bus controller | 0xED84 |
Status indicators | TX/RX per CAN interface, supply voltage, bus function |
Diagnostics | |
Outputs | Yes, using LED status indicator and software |
Power supply | Yes, using LED status indicator and software |
Support | |
Dynamic node allocation (DNA) | Yes |
Connection type | |
Fieldbus | M12, D-coded |
Inputs/Outputs | 8x M12, A-coded |
I/O power supply | M8, 4-pin |
Power consumption | |
Internal I/O | 2.5 W |
Certifications | |
CE | Yes |
UKCA | Yes |
EAC | Yes |
Fieldbus
Interfaces
Sensor/Actuator power supply
Voltage | 9 to 32 V |
Voltage drop for short-circuit protection at 0.5 A | Max. 2 VDC |
Summation current | Max. 1.6 A (200 mA per channel) |
Short-circuit proof | Yes |
Power supply
Nominal voltage | 24 VDC |
Voltage range | 9 to 32 VDC |
Reverse polarity protection | Yes |
Electrical properties
Electrical isolation |
POWERLINK isolated from channel Channel not isolated from channel |
Operating conditions
Mounting orientation | |
Any | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP67 |
Ambient conditions
Temperature | |
Operation | -25 to 60°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Mechanical properties
Dimensions | |
Width | 53 mm |
Height | 155 mm |
Depth | 42 mm |
Torque for connections | |
M8 | Max. 0.4 Nm |
M12 | Max. 0.6 Nm |
Référence produit:
X67BC8780.L12Description:
- POWERLINK
- 8 CAN interfaces
- M12 connections
- Integrated hub for efficient cabling
This bus controller makes it possible to connect 8 CAN interfaces to the POWERLINK network. The CAN interfaces are operated via an integrated hub, which increases the total cable length defined by classical CAN bus topology.
POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The Ethernet POWERLINK Standardization Group (EPSG) ensures openness and continuous development: www.ethernet-powerlink.org.
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V4.3 HW Upgrade (X67BC8780.L12) | EXE / 5 MB |
Certifications | Version (date) | Téléchargement |
---|---|---|
EU Declaration ATEX X67 | PDF / 191 KB | |
EU Declaration PLC X67 | PDF / 674 KB | |
UK Declaration PLC X67 | PDF / 469 KB |
Documentation | Version (date) | Téléchargement |
---|---|---|
Data sheet X67BC8780.L12 | PDF / 1 MB | |
Installation- / EMC-Guide | PDF / 20 MB | |
POWERLINK Bus Controller User's Manual | PDF / 2 MB | |
X67 System User´s Manual | PDF / 6 MB |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X67 EPLAN P8 from V2.4 | EXE / 105 MB |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
STEP File X67BC8xxx.L12 | ZIP / 1 MB |