cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNV
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCS
Yes
LR
ENV1
KR
Yes
ABS
Yes
BV
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
KC
Yes
B&R ID code
0xA717
Status indicators
Module status, data transfer
Power consumption
1.8 W
Additional power dissipation caused by actuators (resistive) [W]
-
Interfaces
Interface IF1
Cyclic data
Input data
Max. 244 bytes
Output data
Max. 244 bytes
Fieldbus
PROFIBUS DP V0/V1 slave
Variant
9-pin female DSUB connector
Max. distance
1200 m
Transfer rate
Max. 12 Mbit/s
Controller
netX100
Electrical properties
Electrical isolation
PLC isolated from PROFIBUS (IF1)
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation elevation above sea level
0 to 2000 m
No limitation
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529
IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation
-25 to 60°C
Vertical mounting orientation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical properties
Slot
In the X20 PLC and expandable bus controller X20BC1083
Materialenummer:
X20IF1063-1
Beskrivelse:
PROFIBUS DP V1 slave
The interface module is equipped with a PROFIBUS DP V1 interface. This allows the B&R system (I/O modules, POWERLINK, etc.) to be connected to systems from other manufacturers and makes it possible to quickly and easily transfer data in both directions.
The interface module can be operated in the X20 controllers or in the expandable X20BC1083 POWERLINK bus controller.