Short description
Communication module 1x POWERLINK (V1/V2) managing or controlled node
General information
Diagnostics
Bus function Yes, using LED status indicator and software
Station status Yes, using LED status indicator and software
Electrical isolation
PC - IFx Yes
Certifications
CE Yes
CRA (Cyber Resilience Act) In preparation
UL cULus E115267
Industrial control equipment
B&R ID code 0xAAC0
Ready relay Normally open contact and normally closed contact, max. 30 VDC, max. 10 A
Status indicators Status of the POWERLINK station, network activity, link
Power consumption 2 W
Controller
SRAM 1 MB, battery-backed
Interfaces
Transfer
Physical layer ANSI/IEEE 802.3
Half-duplex Yes
Full-duplex POWERLINK mode: No / Ethernet mode: Yes
Autonegotiation Yes
Auto-MDI/MDIX Yes
Fieldbus POWERLINK (V1/V2) managing or controlled node
Type Type 4
Variant 2x shielded RJ45 (hub)
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Hub propagation delay 0.96 to 1 µs
Operating conditions
Degree of protection per EN 60529 IP20 in installed state
Ambient conditions
Temperature
Operation 0 to 55°C
Storage -25 to 70°C
Transport -25 to 70°C
Relative humidity
Operation 0 to 95%, non-condensing
Storage 0 to 95%, non-condensing
Transport 0 to 95%, non-condensing
Mechanical properties
Installation in
B&R Automation PC Yes
B&R Panel PC Yes
Desktop PC Yes
Note Order 1x terminal block TB704 separately.
Lithium battery included in content of delivery
Slot Standard PCI half-size module, Plug & Play
型番:
5LS182.6-2
説明:
  • POWERLINK (V1/V2) for real-time Ethernet communication
  • Integrated hub for efficient cabling
  • Configurable ring redundancy
  • Poll response chaining

Logic scanner module 5LS182.6-2 is a PCI half-size module. It supports plug and play and has 1 MB SRAM for remanent data (process variables and data objects). Memory available for remanent process variables depends on the CPU, Automation Runtime, etc.

5LS182.6-2 is a high-performance POWERLINK managing node solution in accordance with specification EPSG DS301. This integrated hub allows for easy implementation of either a simple tree structure or optional ring redundancy without extra effort.

With poll-response chaining, the module offers a solution for the highest demands on response time and the shortest cycle times. Especially for central control tasks, poll-response chaining in combination with the B&R control system provides ideal performance.

The module is also equipped with a ready relay.

配送品に含まれる
Batteries
4A0006.00-000 Logic scanner, PCI half-size module, 1 POWERLINK (V1/V2) interface, managing or controlled node, integrated 2-port hub, ring redundancy function, PRC function, 1 MB SRAM (Automation Runtime), order 1x terminal block TB704 separately!
必須アクセサリ
Terminal blocks
0TB704.9 Logic scanner, PCI half-size module, 1 POWERLINK (V1/V2) interface, managing or controlled node, integrated 2-port hub, ring redundancy function, PRC function, 1 MB SRAM (Automation Runtime), order 1x terminal block TB704 separately!
0TB704.91 Logic scanner, PCI half-size module, 1 POWERLINK (V1/V2) interface, managing or controlled node, integrated 2-port hub, ring redundancy function, PRC function, 1 MB SRAM (Automation Runtime), order 1x terminal block TB704 separately!
オプションで付属可
Batteries
0AC201.91 Logic scanner, PCI half-size module, 1 POWERLINK (V1/V2) interface, managing or controlled node, integrated 2-port hub, ring redundancy function, PRC function, 1 MB SRAM (Automation Runtime), order 1x terminal block TB704 separately!
Automation Studio HW アップグレード バージョン (日付) ダウンロード
V2.6 HW Upgrade (5LS182.6-2) EXE / 615 KB
V3.0 HW Upgrade (5LS182.6-2) EXE / 2 MB
V3.0 HW Upgrade (5LS182.6-2) EXE / 642 KB
V4.0 HW Upgrade (5LS182.6-2) EXE / 3 MB
V6.0 HW Upgrade (5LS182.6-2) EXE / 2 MB
E-CAD(ElectroまたはEPLANテンプレート) バージョン (日付) ダウンロード
APC EPLAN P8 from V2.4 EXE / 99 MB
ドキュメンテーション バージョン (日付) ダウンロード
Data sheet 5LS182.6-2 PDF / 4 MB

国と言語を選ぶ

B&R Logo