Short description
I/O module 2 analog inputs, 2 analog outputs, each ±10 V
General information
B&R ID code 0x1465
Status indicators I/O function per channel, supply voltage, bus function
Diagnostics
Inputs Yes, using LED status indicator and software
I/O power supply Yes, using LED status indicator and software
Connection type
X2X Link M12, B-coded
Inputs/Outputs 4x M12, A-coded
I/O power supply M8, 4-pin
Power consumption
Internal I/O 3 W
X2X Link power supply 0.75 W
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Power consumption
Sensor/Actuator power supply Max. 12 W
Sensor/Actuator power supply
Voltage I/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.5 A Max. 2 VDC
Summation current Max. 0.5 A
Short-circuit proof Yes
Analog inputs
Input ±10 V
Input type Differential input
Digital converter resolution 12-bit
Conversion time 400 µs for both inputs
Output format INT
Output format
Voltage INT 0x8001 - 0x7FFF / 1 LSB = 0x0010 = 4.882 mV
Input impedance in signal range 20 MΩ
Input protection Protection against wiring with supply voltage
Permissible input signal Max. ±30 V
Output of digital value during overload
Undershoot 0x8001
Overshoot 0x7FFF
Conversion procedure Successive approximation
Max. error
Gain 0.1%
Offset 0.05%
Max. gain drift 0.011%/°C
Max. offset drift 0.009%/°C
Common-mode rejection
DC >50 dB
50 Hz >50 dB
Common-mode range ±11 V
Crosstalk between channels <-70 dB
Nonlinearity <0.1%
Insulation voltage between channel and bus 500 Veff
Input filter
Cutoff frequency 300 Hz
Slope 40 dB
Analog outputs
Output ±10 V
Digital converter resolution 12-bit
Conversion time 400 µs for both outputs
Settling time on output change over entire range Approx. 1 ms
Switch on/off behavior Internal enable relay for startup and errors
Output protection Protection against wiring with supply voltage, short-circuit proof
Output format INT 0x8001 - 0x7FFF / 1 LSB = 0x0010 = 4.882 mV
Load per channel Max. ±10 mA, load ≥ 1 kΩ
Output filter First-order low-pass filter / cutoff frequency 2.5 kHz
Max. gain drift 0.012%/°C
Max. offset drift 0.015%/°C
Error caused by load change Max. 0.01%, from 10 MΩ → 1 kΩ, resistive
Nonlinearity <0.15%
Insulation voltage between channel and bus 500 Veff
Output response when the power supply is switched on/off An enable relay is switched on at a defined value ≠ 0, default setting = 10 kΩ to GND
Short-circuit proof
Current limiting ±40 mA
To GND Yes
To sensor or I/O power supply Yes
Max. error at 25°C and 10 kΩ load
Gain 0.15%
Offset 0.05%
Electrical properties
Electrical isolation
Channel isolated from bus

Channel not isolated from channel
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 195 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Référence produit:
X67AM1223
Description:
  • 2 analog inputs, 2 analog outputs, ±10 V each
  • Open circuit detection on the inputs
  • Configurable digital input filters
  • Very short cycle times
  • Optimal shield grounding on all channels

The module is equipped with 2 inputs and 2 outputs with 12-bit digital converter resolution. The range of the input/output signal is ±10 V.

Automation Studio HW Upgrades Version (date) Téléchargement
V2.6 HW Upgrade (X67AM1223F) EXE / 485 Ko
V3.0 HW Upgrade (X67AM1223F) EXE / 485 Ko
V4.0 HW Upgrade (X67AM1223) EXE / 555 Ko
Certifications Version (date) Téléchargement
244665 CSA HazLoc CoC X20, X67 PDF / 158 Ko
E115267 UL CoC X67 PDF / 155 Ko
EU Declaration ATEX X67 PDF / 191 Ko
EU Declaration PLC X67 PDF / 674 Ko
Safe cutoff of potential groups PDF / 211 Ko
TÜV 05 ATEX 7201 X PDF / 5 Mo
UK Declaration PLC X67 PDF / 469 Ko
X20, X67 KC certificates PDF / 6 Mo
Documentation Version (date) Téléchargement
Datasheet X67AM1223 PDF / 512 Ko
Installation- / EMC-Guide PDF / 20 Mo
X67 System User´s Manual PDF / 6 Mo
E-CAD (modèles Electro ou EPLAN) Version (date) Téléchargement
X67 EPLAN P8 from V2.4 EXE / 105 Mo
M-CAD (modèles mécaniques) Version (date) Téléchargement
3D File DXF/STEP X67 ZIP / 4 Mo

Veuillez sélectionner un pays et une langue