Short description
I/O module | 4 NAMUR inputs, special function |
General information
B&R ID code | 0x2105 |
Status indicators | I/O function per channel, open-circuit and short-circuit detection per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Short circuit | Yes, using LED status indicator and software |
Open circuit | Yes, using LED status indicator and software |
Power consumption | |
Bus | 0.01 W |
Internal I/O | 1.5 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
CCS | Yes |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
KC | Yes |
Event counters
NAMUR inputs
Open-circuit detection | <350 µA |
Input circuit | For NAMUR encoder per EN 60947-5-6 |
Insulation voltage between channel and bus | 500 Veff |
Short-circuit detection | >7 mA |
Open-circuit voltage | 8.05 V ±0.33% |
Switching amplifier internal resistance | 1 kΩ ±1% |
Max. short-circuit current | 8.2 mA |
Input delay | |
1 input active | ≤310 µs |
2 inputs active | ≤450 µs |
3 inputs active | ≤570 µs |
4 inputs active | ≤735 µs |
Switching threshold | |
Area | 1.2 mA to 2.1 mA |
Switching hysteresis | Typ. 300 µA |
Electrical properties
Electrical isolation |
Channel isolated from bus Channel not isolated from channel |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
Pitch | 12.5+0.2 mm |
Référence produit:
X20DI4760Description:
- 4 digital inputs
- Input module for NAMUR encoders
- Open line and short circuit detection
- Each input can be used as a counter input
The module is used to transfer digital signals from NAMUR encoders according to EN 60947-5-6. In addition to NAMUR encoders, normal switches can also be used.
Accessoires obligatoires
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V2.6 HW Upgrade (X20DI4760) | EXE / 419 Ko | |
V2.6 HW Upgrade (X20DI4760) | EXE / 990 Ko | |
V3.0 HW Upgrade (X20DI4760) | EXE / 419 Ko | |
V3.0 HW Upgrade (X20DI4760) | EXE / 1 Mo | |
V4.0 HW Upgrade (X20DI4760) | EXE / 704 Ko |
Documentation | Version (date) | Téléchargement |
---|---|---|
Data sheet X20(c)DI4760 | PDF / 646 Ko | |
Installation- / EMC-Guide | PDF / 20 Mo | |
X20 Package leaflet ATEX/CSA | PDF / 2 Mo | |
X20 System User´s Manual | PDF / 7 Mo |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 Mo |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 Ko | |
3D File STEP X20 I/O-Slice | ZIP / 872 Ko | |
Dimensions PDF X20 Electronic module | PDF / 3 Ko |