I/O module | 2 digital inputs 100 to 240 VAC for 3-wire connections |
General information
B&R ID code | 0x2544 |
Status indicators | I/O function per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
External I/O power supply | Yes, using software (typ. threshold 85 VAC) |
Power consumption | |
Bus | 0.14 W |
Internal I/O | - |
External I/O | 0.55 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
LR | ENV1 |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
EAC | Yes |
KC | Yes |
Digital inputs
Nominal voltage | 100 to 240 VAC |
Input filter | |
Software | Default 1 ms, configurable between 0 and 25 ms in 0.2 ms increments |
Hardware | |
1 → 0 | ≤30 ms |
0 → 1 | ≤40 ms |
Connection type | 3-wire connections |
Rated frequency | 47 to 63 Hz |
Switching threshold | |
Low | <40 VAC |
High | >79 VAC |
Insulation voltage between channel and bus | 1 minute 2500 VAC |
Input voltage | |
Maximum | 264 VAC |
Input current | |
100 VAC / 60 Hz | 4 mA (Rev. ≥ E0), 5 mA (Rev. < E0) |
240 VAC / 50 Hz | 8.5 mA (Rev. ≥ E0), 11 mA (Rev. < E0) |
Sensor power supply
Voltage | Corresponds to the module power supply |
Summation current | 2 Aeff |
Short-circuit proof | No |
Electrical properties
Electrical isolation |
Channel isolated from bus Channel not isolated from channel |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Not permitted |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB32 separately. Order 1x bus module X20BM12 separately. |
Pitch | 12.5+0.2 mm |
Référence produit:
X20DI2653Description:
- 2 digital inputs
- 100 to 240 VAC inputs
- 50 Hz or 60 Hz
- 3-wire connections
- 240 V coded
The module is equipped with 2 inputs for 3-wire connections. It is designed for an input voltage of 100 to 240 VAC.
Accessoires obligatoires
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V2.7 HW Upgrade (X20DI2653) | EXE / 785 Ko | |
V2.7 HW Upgrade (X20DI2653) | EXE / 894 Ko | |
V3.0 HW Upgrade (X20DI2653) | EXE / 1 Mo | |
V3.0 HW Upgrade (X20DI2653) | EXE / 1 Mo | |
V4.0 HW Upgrade (X20DI2653) | EXE / 983 Ko |
Documentation | Version (date) | Téléchargement |
---|---|---|
Data sheet X20DI2653 | PDF / 195 Ko | |
Installation- / EMC-Guide | PDF / 20 Mo | |
X20 System User´s Manual | PDF / 7 Mo |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 Mo |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 Ko | |
3D File STEP X20 I/O-Slice | ZIP / 872 Ko | |
Dimensions PDF X20 Electronic module | PDF / 3 Ko |