Short description
General information
CPU / X2X Link power supply input
Input voltage | 24 VDC -15% / +20% |
Input current | Max. 0.7 A |
Fuse | Integrated, cannot be replaced |
Reverse polarity protection | Yes |
CPU / X2X Link power supply output
Input I/O power supply
Input voltage | 24 VDC -15% / +20% |
Fuse | Required line fuse: Max. 10 A, slow-blow |
Reverse polarity protection | No |
Output I/O power supply
Nominal output voltage | 24 VDC |
Behavior on short circuit | Required line fuse |
Permissible contact load | 10 A |
Interfaces
Electrical properties
Electrical isolation |
CPU/X2X Link supply isolated from CPU/X2X Link power supply I/O supply not isolated from I/O power supply
|
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | Up to 100%, condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB12 separately. Order 1x Compact-S CPU base X20cBB5x separately. |
Pitch | 12.5+0.2 mm |
Référence produit:
X20cPS9600Description:
- Supply for Compact-S CPU, X2X Link and internal I/O power supply
- Galvanic isolation of supply and CPU / X2X Link power supply
- Redundancy of the CPU / X2X Link power supply possible through parallel operation of multiple power supply modules
- RS232 configurable as an online interface
- CAN bus
The power supply module is used together with an X20 Compact-S CPU. It has a feed for the Compact-S CPU, X2X Link and the internal I/O power supply.
Accessoires obligatoires
System modules for Compact-S PLCs
X20cBB52 | X20c Compact-S bus base, coated, for Compact-S PLC and Compact-S PLC power supply module, base for integrated RS232 interface, X20 connection, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included |
X20cBB57 | X20c Compact-S bus base, coated, for Compact-S PLC and Compact-S PLC power supply module, base for integrated RS232 and CAN bus interface, X20 connection, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included |
Terminal blocks
X20TB12 | X20 terminal block, 12-pin, 24 VDC keyed |
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V4.8 HW Upgrade (X20cPS9600) | EXE / 882 Ko |
Certifications | Version (date) | Téléchargement |
---|---|---|
ABS Certificate of Product Design Assessment - X20 IO Series | PDF / 2 Mo | |
EU Declaration ATEX X20 | PDF / 218 Ko | |
EU Declaration of conformity PLC X20 | PDF / 169 Ko | |
Lloyds Register | PDF / 502 Ko | |
UK Declaration PLC X20 | PDF / 151 Ko |
Documentation | Version (date) | Téléchargement |
---|---|---|
Data sheet X20(c)PS9600 | PDF / 425 Ko | |
Installation- / EMC-Guide | PDF / 20 Mo | |
X20 System User´s Manual | PDF / 7 Mo |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
Makro-/Artikeldaten 4.0.0 (X20cPS9600) | EXE / 670 Ko | |
Makro-/Artikeldaten 4.0.0 (X20cPS9600) | EXE / 673 Ko | |
X20 EPLAN P8 from V2.4 | EXE / 160 Mo |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 Ko | |
3D File STEP X20 I/O-Slice | ZIP / 872 Ko | |
Dimensions PDF X20 Electronic module | PDF / 3 Ko |