DWL@DWL10000800516

Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.7.0.0 * 01.10.2024 1 MB EXE AS6_HW_X20DO8332.exe
Popis V6.0 HW Upgrade (X20DO8332)

Revision information X20DO8332

Version 1.7.0.0:

ID: TDYD-7027
Incorrectly configured modules were not identified on the X2X bus in certain circumstances.
A dynamic hardwareconfiguration is used for various customer applications. In this case, a default configuration is simply created in AS and the actual configuration is readout after the system has started up. Due to a hardware change of several I/O modules, only a cyclic size of 12 bytes (previously 31 bytes) is accepted in the bootloader. If a module with more cyclic data (e.g. a safety module) is nowconfigured, this module can no longer be identified on the bus. As a workaround, these "large" modules can be configured on other X2X slots. This problem can only be corrected with a new bootloader, which can only be delivered via production. Production will be switched to the new software accordingly.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\7069_1.fw(560), 1\7069_10.fw(150), 1\7069_11.fw(150), 1\7069_20.fw(200), 1\7069_21.fw(230), 1\7069_5.fw(801)

Version 1.6.0.0:

ID: 759680
Support new HW variant 21
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\7069_1.fw(560), 1\7069_10.fw(150), 1\7069_11.fw(150), 1\7069_20.fw(200), 1\7069_21.fw(210), 1\7069_5.fw(801)

Version 1.5.0.0:

ID: 738555
Support new HW variant 20
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes
Firmware: 1\7069_1.fw(560), 1\7069_10.fw(150), 1\7069_11.fw(150), 1\7069_20.fw(200), 1\7069_5.fw(801)

Version 1.4.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.3.0.0:

ID: 676535
Support hardware variant 11
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 679820
Module documentation revised
Data sheet V 3.26
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7069_1.fw(560), 1\7069_10.fw(150), 1\7069_11.fw(150), 1\7069_5.fw(801)

Version 1.2.0.0:

ID:
Adaptations for Automation Studio 4.8
Channeldescription changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.1.0.0:

ID: 630145
Support hardware variant 10
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 632225
Module documentation revised
Data sheet V 3.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7069_1.fw(560), 1\7069_10.fw(100), 1\7069_5.fw(801)

Version 1.0.2.0:

ID: 469185
Module documentation revised
Data sheetV3.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7069_1.fw(560), 1\7069_5.fw(801)

Version 1.0.1.4:

ID: 396405
Enhancement online-help files
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7069_1.fw(560), 1\7069_5.fw(801)

Version 1.0.1.3:

ID: 394490
Enhancements packed data point for outputs
Channel description changed: Yes
Configurationdescription changed: No
Firmware changed: No
Firmware: 1\7069_1.fw(560), 1\7069_5.fw(801)

Version 1.0.1.1:

ID: 216005
Support of asynchronous module status data points, UART Re-Init
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\7069_1.fw(560), 1\7069_5.fw(800)

Version 1.0.1.0:

ID: 184975
HWC correction, correct display of PS status
HWC correction, correct display of PS status if dig. status=off
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\7069_1.fw(530)
Loading
Zpět k seznamu

Vyberte prosím zemi a jazyk