1.14.0.0 * 17.02.2022 1 MB EXE AS4_HW_X20cIF1082-2.exe
Popis V4.0 HW Upgrade (X20cIF1082-2)

Revision information X20cIF1082-2

Version 1.14.0.0:

ID: 735710
Update problem
If the firmware update of the interface card was interrupted (e.g. by a power failure), it was possible that the interface was no longer booted by Automation Runtime.
This problem can only occur with interfaces with revisions # E0 and when the hardware upgrade is changed.
To correct this problem, it is necessary to switch to another hardware upgrade. This will force an update or use this current hardware upgrade.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36364), 1\57910_1.pci(36359), 1\57910a0.epl(142), 1\57910a1.epl(142)

Version 1.13.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.12.0.0:

ID: 705090
POWERLINK: Operating mode "Ethernet"
If a POWERLINK interface was operatedin operating mode "Ethernet" and connected to a POWERLINK network in this mode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36364), 1\57910_1.pci(36357), 1\57910a0.epl(142), 1\57910a1.epl(142)

Version 1.11.1.0:

ID: 692870
Support HW variant 1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 694020
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configurationdescription changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(36108), 1\57910_1.pci(36101), 1\57910a0.epl(141), 1\57910a1.epl(141)

Version 1.10.0.0:

ID: 652270
POWERLINK: Possible failure of already configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652495
Error correction: DNA tree topologies not always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36108), 1\57910a0.epl(141)

Version 1.9.0.0:

ID: 636515
POWERLINK-Manager: With frequent failure of CN's, which are operated with the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(35340), 1\57910a0.epl(138)

Version 1.8.0.0:

ID: 591130
Documentation updated
Version 1.23
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603475 / Support ID: 400250890
POWERLINK CNs withconfiguration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 608220
Cannot connect hardware module to PLK2 interface of X20IF1082-2 in Ethernetmode in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(34825), 1\57910a0.epl(136)

Version 1.7.0.0:

ID: 568875
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(34313), 1\57910a0.epl(134)

Version 1.6.0.0:

ID: 539755 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(33545), 1\57910a0.epl(131)

Version 1.5.0.0:

ID: 504060
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 504205
Documentation updated
version 1.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.2.0.0:

ID: 443865 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.1.0.0:

ID: 417940
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417945 / Support ID: 400135055
Support of Poll Response Chaining on iCN
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424020 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing ofthe input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424060 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registeredwith an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32521), 1\57910a0.epl(127)

Version 1.0.0.0:

ID: 334965
Support X20cIF1082-2
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(31496), 1\57910a0.epl(123)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.13.0.0 * 23.07.2021 1 MB EXE AS4_HW_X20cIF1082-2.exe
Popis V4.0 HW Upgrade (X20cIF1082-2)

Revision information X20cIF1082-2

Version 1.13.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed:yes
Firmware changed: no

Version 1.12.0.0:

ID: 705090
POWERLINK: Operating mode "Ethernet"
If a POWERLINK interface was operated in operating mode "Ethernet" and connected to a POWERLINK network in thismode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36364), 1\57910_1.pci(36357), 1\57910a0.epl(142), 1\57910a1.epl(142)

Version 1.11.1.0:

ID: 692870
Support HW variant 1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 694020
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(36108), 1\57910_1.pci(36101), 1\57910a0.epl(141), 1\57910a1.epl(141)

Version 1.10.0.0:

ID: 652270
POWERLINK: Possible failure ofalready configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652495
Error correction: DNA tree topologies not always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36108), 1\57910a0.epl(141)

Version 1.9.0.0:

ID: 636515
POWERLINK-Manager: With frequent failure of CN's, which areoperated with the optimization "Chained station" it can be happen that failedCN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(35340), 1\57910a0.epl(138)

Version 1.8.0.0:

ID: 591130
Documentation updated
Version 1.23
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603475 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 608220
Cannot connect hardware module to PLK2 interface of X20IF1082-2 in Ethernetmode in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(34825), 1\57910a0.epl(136)

Version 1.7.0.0:

ID: 568875
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(34313), 1\57910a0.epl(134)

Version 1.6.0.0:

ID: 539755 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(33545), 1\57910a0.epl(131)

Version 1.5.0.0:

ID: 504060
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 504205
Documentation updated
version 1.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.2.0.0:

ID: 443865 / Support ID: 400154848
IP packets with multicastaddresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.1.0.0:

ID: 417940
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417945 / Support ID: 400135055
Support of Poll Response Chaining on iCN
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424020 / Support ID:400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424060 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32521), 1\57910a0.epl(127)

Version1.0.0.0:

ID: 334965
Support X20cIF1082-2
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(31496), 1\57910a0.epl(123)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.12.0.0 * 28.01.2021 1 MB EXE AS4_HW_X20cIF1082-2.exe
Popis V4.0 HW Upgrade (X20cIF1082-2)

Revision information X20cIF1082-2-2

Version 1.12.0.0:

ID: 705090
POWERLINK: Operating mode "Ethernet"
If a POWERLINK interface was operated in operating mode "Ethernet" and connected to a POWERLINK network in this mode, the interface could fail.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36364), 1\57910_1.pci(36357), 1\57910a0.epl(142), 1\57910a1.epl(142)

Version 1.11.1.0:

ID: 692870
Support HW variant 1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 694020
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(36108), 1\57910_1.pci(36101), 1\57910a0.epl(141), 1\57910a1.epl(141)

Version 1.10.0.0:

ID: 652270
POWERLINK: Possible failure of already configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652495
Error correction: DNA tree topologies not always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36108), 1\57910a0.epl(141)

Version 1.9.0.0:

ID: 636515
POWERLINK-Manager: With frequent failure of CN's, which are operated with the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(35340),1\57910a0.epl(138)

Version 1.8.0.0:

ID: 591130
Documentation updated
Version 1.23
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603475/ Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration"Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 608220
Cannot connect hardware module to PLK2 interface of X20IF1082-2 in Ethernetmode in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(34825), 1\57910a0.epl(136)

Version 1.7.0.0:

ID: 568875
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(34313), 1\57910a0.epl(134)

Version 1.6.0.0:

ID: 539755 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(33545), 1\57910a0.epl(131)

Version 1.5.0.0:

ID: 504060
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 504205
Documentation updated
version 1.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.2.0.0:

ID: 443865 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.1.0.0:

ID: 417940
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417945 / Support ID: 400135055
Support of Poll Response Chaining on iCN
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424020 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out ofan SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424060 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configurationdescription changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32521), 1\57910a0.epl(127)

Version 1.0.0.0:

ID: 334965
Support X20cIF1082-2
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(31496), 1\57910a0.epl(123)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.11.1.0 * 09.07.2020 1 MB EXE AS4_HW_X20cIF1082-2.exe
Popis V4.0 HW Upgrade (X20cIF1082-2)

Revision information X20cIF1082-2

Version 1.11.1.0:

ID: 692870
Support HW variant 1
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 694020
Support for automatic DNA configuration from AS 4.9.1
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(36108), 1\57910_1.pci(36101), 1\57910a0.epl(141), 1\57910a1.epl(141)

Version 1.10.0.0:

ID: 652270
POWERLINK: Possible failure of already configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652495
Error correction: DNA tree topologies not always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36108), 1\57910a0.epl(141)

Version 1.9.0.0:

ID: 636515
POWERLINK-Manager: With frequent failure of CN's, which are operatedwith the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(35340), 1\57910a0.epl(138)

Version 1.8.0.0:

ID: 591130
Documentation updated
Version 1.23
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603475 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 608220
Cannot connect hardware module to PLK2 interface of X20IF1082-2 in Ethernetmode in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(34825), 1\57910a0.epl(136)

Version 1.7.0.0:

ID: 568875
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(34313), 1\57910a0.epl(134)

Version 1.6.0.0:

ID: 539755 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent inthe mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(33545), 1\57910a0.epl(131)

Version 1.5.0.0:

ID: 504060
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 504205
Documentation updated
version 1.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.2.0.0:

ID: 443865 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.1.0.0:

ID: 417940
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417945 / Support ID: 400135055
Support of Poll Response Chaining on iCN
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424020 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424060 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered withan incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32521), 1\57910a0.epl(127)

Version 1.0.0.0:

ID: 334965
Support X20cIF1082-2
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(31496), 1\57910a0.epl(123)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.10.0.0 * 02.12.2019 979 KB EXE AS4_HW_X20cIF1082-2.exe
Popis V4.0 HW Upgrade (X20cIF1082-2)

Revision information X20cIF1082-2

Version 1.10.0.0:

ID: 652270
POWERLINK: Possible failure of already configured CNs if new "chained stations" added during operation
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 652495
Error correction: DNA tree topologies not always started up correctly
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(36108), 1\57910a0.epl(141)

Version 1.9.0.0:

ID: 636515
POWERLINK-Manager: With frequent failure of CN's, which are operated with the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(35340), 1\57910a0.epl(138)

Version 1.8.0.0:

ID: 591130
Documentation updated
Version 1.23
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603475 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 608220
Cannot connect hardwaremodule to PLK2 interface of X20IF1082-2 in Ethernet mode in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(34825), 1\57910a0.epl(136)

Version 1.7.0.0:

ID: 568875
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(34313), 1\57910a0.epl(134)

Version 1.6.0.0:

ID: 539755 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(33545), 1\57910a0.epl(131)

Version 1.5.0.0:

ID: 504060
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 504205
Documentation updated
version 1.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.2.0.0:

ID: 443865 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.1.0.0:

ID: 417940
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417945 / Support ID: 400135055
Support of Poll Response Chaining on iCN
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424020 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424060 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes
Firmware: 1\57910_0.pci(32521), 1\57910a0.epl(127)

Version 1.0.0.0:

ID: 334965
Support X20cIF1082-2
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(31496), 1\57910a0.epl(123)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.9.0.0 * 09.04.2019 936 KB EXE AS4_HW_X20cIF1082-2.exe
Popis V4.0 HW Upgrade (X20cIF1082-2)

Revision information X20cIF1082-2

Version 1.9.0.0:

ID: 636515
POWERLINK-Manager: With frequent failure of CN's, which are operated with the optimization "Chained station" it can be happen that failed CN's were not longer adressed by the manager.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(35340), 1\57910a0.epl(138)

Version 1.8.0.0:

ID: 591130
Documentation updated
Version 1.23
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603475 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in thenetwork can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 608220
Cannot connect hardware module to PLK2 interface of X20IF1082-2 in Ethernetmode in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(34825), 1\57910a0.epl(136)

Version 1.7.0.0:

ID: 568875
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(34313), 1\57910a0.epl(134)

Version 1.6.0.0:

ID: 539755 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(33545), 1\57910a0.epl(131)

Version 1.5.0.0:

ID: 504060
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 504205
Documentation updated
version 1.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.2.0.0:

ID: 443865 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.1.0.0:

ID: 417940
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417945 / Support ID: 400135055
Support of Poll Response Chaining on iCN
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424020 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424060 / Support ID: 400150240
POWERLINKV2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32521), 1\57910a0.epl(127)

Version 1.0.0.0:

ID: 334965
Support X20cIF1082-2
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(31496), 1\57910a0.epl(123)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.8.0.0 * 24.08.2018 932 KB EXE AS4_HW_X20cIF1082-2.exe
Popis V4.0 HW Upgrade (X20cIF1082-2)

Revision information X20cIF1082-2

Version 1.8.0.0:

ID: 591130
Documentation updated
Version1.23
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 603475 / Support ID: 400250890
POWERLINK CNs with configuration "Optimization: Minimal latency": No input data received
POWERLINK CNs with configuration "Optimization: Minimal latency" and "Chained station: On" that are not physically present in the network can cause no input data to be received from all CNs with setting "Optimization: Minimal latency".
Channel description changed: No
Configurationdescription changed: No
Firmware changed: Yes

ID: 608220
Cannot connect hardware module to PLK2 interface of X20IF1082-2 in Ethernetmode in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57910_0.pci(34825), 1\57910a0.epl(136)

Version 1.7.0.0:

ID: 568875
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(34313), 1\57910a0.epl(134)

Version 1.6.0.0:

ID: 539755 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames were sent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(33545), 1\57910a0.epl(131)

Version 1.5.0.0:

ID: 504060
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 504205
Documentation updated
version 1.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.2.0.0:

ID: 443865 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.1.0.0:

ID: 417940
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417945 / Support ID: 400135055
Support of Poll Response Chaining on iCN
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424020 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes

ID: 424060 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32521), 1\57910a0.epl(127)

Version 1.0.0.0:

ID: 334965
Support X20cIF1082-2
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(31496), 1\57910a0.epl(123)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.7.0.0 * 02.02.2018 921 KB EXE AS4_HW_X20cIF1082-2.exe
Popis V4.0 HW Upgrade (X20cIF1082-2)

Revision information X20cIF1082-2

Version 1.7.0.0:

ID: 568875
Support HW-Revision DO
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(34313), 1\57910a0.epl(134)

Version 1.6.0.0:

ID: 539755 / Support ID: 400204420
POWERLINKV2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timing problem in the firmware it could happen that no asynchronous frames weresent in the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(33545), 1\57910a0.epl(131)

Version 1.5.0.0:

ID: 504060
X20-Compact-S support
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 504205
Documentation updated
version 1.22
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.2.0.0:

ID: 443865 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32777), 1\57910a0.epl(128)

Version 1.1.0.0:

ID: 417940
Support Bonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417945 / Support ID: 400135055
Support of Poll Response Chaining on iCN
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424020 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezingof the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424060 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, the controlled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57910_0.pci(32521), 1\57910a0.epl(127)

Version 1.0.0.0:

ID: 334965
Support X20cIF1082-2
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57910_0.pci(31496), 1\57910a0.epl(123)