Short description
I/O module 2 digital outputs 48 to 240 VAC for 3-wire connections
General information
B&R ID code 0xAC39
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Outputs Yes, using LED status indicator and software
Power consumption
Bus 0.6 W
Internal I/O -
External I/O -
Additional power dissipation caused by actuators (resistive) [W] +6
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
Digital outputs
Variant Triac
Circuit L-switching
Nominal voltage 48 to 240 VAC
Max. voltage 264 VAC
Rated frequency 47 to 63 Hz
Nominal output current 2 A
Total nominal current 4 A
Maximum current
Output current 2.5 A
Summation current 5 A
Connection type 3-wire connections
Zero-crossing detection Yes
Minimum holding current IH 15 mA
Leakage current Max. 2 mA at 240 V at 50 Hz
Max. 2.4 mA at 240 V at 60 Hz
Residual voltage (on-state voltage) 1.5 V
Phase-angle control
Area 5 to 95%
Resolution 1%
Accuracy (60 to 240 VAC) <100 μs
Voltage monitoring L - N Yes
Additional functions Open-circuit detection
Overvoltage protection between L and N Yes, varistor
Insulation voltages
Channel - Bus Tested with 2300 VAC (Rev. <E0 1500 VAC)
Channel - Internal I/O Tested with 2300 VAC (Rev. <E0 2000 VAC)
Channel - Ground Tested with 2300 VAC (Rev. <E0 1500 VAC)
Protective circuit
External See section "External fuses".
Internal Snubber circuit (RC element) and varistor
Electrical properties
Electrical isolation Channel isolated from bus and I/O power supply
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Not permitted
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB32 separately.
Order 1x bus module X20BM32 separately.
Pitch 25+0.2 mm
Material number:
X20DO2633
Description:
  • 2 digital outputs
  • Outputs with integrated snubber circuit
  • Outputs with 48 to 240 VAC
  • L switching
  • Zero-crossing detection
  • Phase-angle control
  • Open-circuit detection for each channel
  • Negative half-waves can be switched off
  • 50 Hz or 60 Hz
  • 3-wire connections
  • 240 V coding
  • OSP mode
  • Frequency mode

The module is a digital output module with phase-angle control that is equipped with 2 Triac outputs using 3-line connections. The supply (L and N) is fed directly to the module.

Mandatory Accessories
Bus modules
X20BM32 X20 bus module, for double-width modules, 240 VAC keyed, internal I/O power supply connected through
Terminal blocks
X20TB32 X20 terminal block, 12-pin, 240 VAC keyed
Aktualizacja Automation Studio HW Version (Date) Download
V2.7 HW Upgrade (X20DO2633) EXE / 1 MB
V3.0 HW Upgrade (X20DO2633) EXE / 2 MB
V4.0 HW Upgrade (X20DO2633) EXE / 1 MB
Certyfikaty Version (Date) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB
Dokumentacja Version (Date) Download
Data sheet X20(c)DO2633 PDF / 431 KB
Installation- / EMC-Guide PDF / 20 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (szablony Electro lub EPLAN) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. szablony) Version (Date) Download
3D File X20 Double IO Slice ZIP / 1,002 KB

Wybierz kraj i język