General information
B&R ID code | 0x30E2 |
Configuration software | Automation Studio (version 4.12.x or later) / SYCONnet |
Status indicators | Module status, network status, data transfer |
Diagnostics | |
Module status | Yes, using LED status indicator and software |
Network status | Yes, using LED status indicator and software |
Data transfer | Yes, using LED status indicator |
Certifications | |
CE | Yes |
UL | In preparation |
Controller
Processor | netX 500 |
Memory | |
Memory size | 8 MB SDRAM |
Dual-port memory | 64 kB |
Fieldbus
Type | EtherCAT (master) |
Variant | 2x RJ45, shielded |
Line length | Max. 100 m between 2 stations (segment length) |
Transfer rate | 100 Mbit/s |
Transfer | |
Physical layer | 100BASE-TX |
Half-duplex | Yes |
Full-duplex | Yes |
Autonegotiation | Yes |
Auto-MDI/MDIX | Yes |
Cyclic data | Max. 4600 bytes (without LRW) |
Functions |
Topology: Line or ring Data transport layer: ETH II, IEEE 802.3 100 Mbit, full-duplex Max. 388 slave modules Size of the file configuration. NXD max. 1 MB Mailbox protocols: CoE, EoE, FoE, SoE Interface check: Supported Slave station addresses: 1-14335 |
Electrical properties
Nominal voltage | +3.3 V ±5% |
Nominal current | Max. 800 mA |
Operating conditions
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction (derating) of the ambient temperature by 0.5°C per 100 m. |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | 0 to 55°C |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 10 to 95%, non-condensing |
Storage | 10 to 95%, non-condensing |
Transport | 10 to 95%, non-condensing |
Shock | |
Operation | 15 g, 11 ms |
Storage | 30 g, 15 ms |
Transport | 30 g, 15 ms |
Mechanical properties
Dimensions | |
Width | 120 mm |
Height | 86 mm |
Depth | 18.5 mm |
Weight | Max. 150 g |
Slot | Standard PCIe x1 half-size module |
Installation in | |
B&R Automation PC | Yes (APC910, APC4100) |
Material number:
5ACPCE.XECM-00Description:
PCIe EtherCAT master
Optional Accessories
Interface options
5AC901.IPLK-00 | Interface card - 1x POWERLINK interface - 2 MB SRAM - For APC910/PPC900/APC3100/PPC3100/APC4100 Important: The minimum requirement for operating an APC4100 with Automation Runtime is AR 6. |
5ACCIF04.FPLK-000 | Interface card - 1x POWERLINK interface - For APC3100/PPC3100/APC4100 |
PCI communication modules
5LS182.6-2 | Logic scanner, PCI half-size module, 1 POWERLINK (V1/V2) interface, managing or controlled node, integrated 2-port hub, ring redundancy function, PRC function, 1 MB SRAM (Automation Runtime), order 1x terminal block TB704 separately! |
5LS182.8 | Logic scanner, PCIe half-size module, 1 POWERLINK interface, managing or controlled node, integrated 2-port hub, ring redundancy function, PRC function, 1 MB SRAM (Automation Runtime) |
5LS187.6-1 | Logic Scanner, PCI half size module, 1 POWERLINK (V1/V2) interface, Managing or controlled node, 1 CAN bus interface, Electrically isolated, Max. 1 Mbit/s, Object buffer in send and receive direction, 1 MB SRAM (Automation Runtime), Order terminal blocks 2x TB704 separately! |
5LS189.6-1 | Logic scanner, PCI half-size module, 1 POWERLINK (V1/V2) interface, managing or controlled node, 1 X2X Link master interface, electrically isolated, 1 MB SRAM (Automation Runtime), order 2x terminal blocks TB704 separately! |
Aktualizacja Automation Studio HW | Version (Date) | Download |
---|---|---|
V4.12 HW Upgrade (5ACPCE.XECM-00) | EXE / 5 MB |
Aktualizacje Firmware | Version (Date) | Download |
---|---|---|
Hilscher firmware (5ACPCE.XECM-00) | ZIP / 448 KB |
Dokumentacja | Version (Date) | Download |
---|---|---|
Data sheet 5ACPCE.XECM-00 | PDF / 2 MB |