Short description
I/O module 4 digital inputs 100 to 240 VAC for 2-wire connections
General information
B&R ID code 0x2545
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
External I/O power supply Yes, using software (typ. threshold 85 VAC)
Power consumption
Bus 0.17 W
Internal I/O -
External I/O 0.91 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
CRA (Cyber Resilience Act) In preparation
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
CCS Yes
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
KC Yes
Digital inputs
Nominal voltage 100 to 240 VAC
Input filter
Software Default 1 ms, configurable between 0 and 25 ms in 0.2 ms increments
Hardware
1 → 0 ≤30 ms
0 → 1 ≤40 ms
Connection type 2-wire connections
Rated frequency 47 to 63 Hz
Switching threshold
Low <40 VAC
High >79 VAC
Insulation voltage between channel and bus 1 minute 2500 VAC
Input voltage
Maximum 264 VAC
Input current
100 VAC / 60 Hz 4 mA (Rev. ≥ E0), 5 mA (Rev. < E0)
240 VAC / 50 Hz 8.5 mA (Rev. ≥ E0), 11 mA (Rev. < E0)
Sensor power supply
Voltage Corresponds to the module power supply
Summation current 4 Aeff
Short-circuit proof No
Electrical properties
Electrical isolation Channel isolated from bus
Channel not isolated from channel
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Not permitted
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB32 separately.
Order 1x bus module X20BM12 separately.
Pitch 12.5+0.2 mm
型番:
X20DI4653
説明:
  • 4 digital inputs
  • 100 to 240 VAC inputs
  • 50 Hz or 60 Hz
  • 2-wire connections
  • 240 V coded

The module is equipped with 4 inputs for 2-wire connections. It is designed for an input voltage of 100 to 240 VAC.

必須アクセサリ
Bus modules
X20BM12 X20 bus module, 240 VAC keyed, internal I/O power supply connected through
Terminal blocks
X20TB32 X20 terminal block, 12-pin, 240 VAC keyed
Automation Studio HW アップグレード バージョン (日付) ダウンロード
V2.7 HW Upgrade (X20DI4653) EXE / 804 KB
V2.7 HW Upgrade (X20DI4653) EXE / 908 KB
V3.0 HW Upgrade (X20DI4653) EXE / 1 MB
V3.0 HW Upgrade (X20DI4653) EXE / 1 MB
V4.0 HW Upgrade (X20DI4653) EXE / 1,022 KB
E-CAD(ElectroまたはEPLANテンプレート) バージョン (日付) ダウンロード
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan.Templates) バージョン (日付) ダウンロード
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB
ドキュメンテーション バージョン (日付) ダウンロード
Data sheet X20DI4653 PDF / 2 MB
X20 Package leaflet ATEX/CSA PDF / 2 MB
X20 System User´s Manual PDF / 49 MB
証明書 バージョン (日付) ダウンロード
2226379 CSA Certificate of Compliance X20 X67 PDF / 366 KB
BV Type Approval Certificate - X20 PDF / 556 KB
CCS Type Approval Certificate - X20 PDF / 285 KB
E115267 UL Certificate of Compliance X20 PDF / 2 MB
EU Data Act - X20 IO - Connected Product Information Notice PDF / 92 KB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 320 KB
Lloyds Register (X20 only) PDF / 884 KB
TAA00000BJ DNV Type Approval Certificate X20 PDF / 191 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB

国と言語を選ぶ

B&R Logo