Short description
Bus controller POWERLINK (V1/V2) controlled node with compact link selector
General information
B&R ID code 0xDF10
Status indicators Module status, bus function
Diagnostics
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator and software
Support
Dynamic node allocation (DNA) Yes
Power consumption
Bus 2 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
EAC Yes
Interfaces
Fieldbus POWERLINK (V1/V2) controlled node
Type Type 2
Variant 2x shielded RJ45
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex No
Autonegotiation Yes
Auto-MDI/MDIX Yes
Hub propagation delay 0.96 to 1 µs
Min. cycle time
Fieldbus 200 μs
X2X Link 200 μs
Synchronization between bus systems possible Yes
Electrical properties
Electrical isolation POWERLINK isolated from bus and I/O
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Starting temperature Yes, -40°C
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Up to 100%, condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20cPS9400 separately.
Order 1x bus base X20cBB80 or X20cBB82 separately
Pitch
X20BB80 37.5+0.2 mm
X20BB82 87.5+0.2 mm
型番:
X20cBC8084
説明:
  • POWERLINK
  • I/O configuration and firmware update via the fieldbus
  • Integrated compact link selector function
  • 2 active hub expansion modules can be connected to the bus controller
  • Redundant supply possible

The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler.

POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org.

Systems with redundant cabling can be implemented easily using POWERLINK. Unlike ring redundancy, cable redundancy does not require cable looping, which can sometimes be problematic. This allows the creation of all types of tree structures. When using a device with the link selector function, data is always transferred via the highest quality network lines. The link selector function is integrated in the bus controller.

詳しい情報:

Technology information: Redundancy

User's manual: Redundancy for control systems

必須アクセサリ
System modules for bus controllers
X20cBB80 X20 bus base, coated, for X20 base module (BC, HB, etc.) and X20 power supply module, X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20cPS9400 X20 power supply module, coated, for bus controller and internal I/O power supply X2X Link power supply
System modules for expandable bus controllers
X20cBB82 X20 bus base, coated, for X20 base module (BC, HB, etc.) and X20 power supply module, with 2 expansion slots for 2 X20 add-on modules (IF, HB, etc.), X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
オプションで付属可
System modules for X20 redundancy systems
X20cHB2885 X20 hub expansion module, coated, integrated active 2-port hub, 2x RJ45
Automation Studio HW アップグレード バージョン (日付) ダウンロード
V3.0 HW Upgrade (X20cBC8084) EXE / 2 MB
V4.0 HW Upgrade (X20cBC8084) EXE / 2 MB
E-CAD(ElectroまたはEPLANテンプレート) バージョン (日付) ダウンロード
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan.Templates) バージョン (日付) ダウンロード
3D File STEP/DXF X20BC and X20IF Module ZIP / 1 MB
ドキュメンテーション バージョン (日付) ダウンロード
Coated modules PDF / 62 KB
Data sheet X20(c)BC8084 PDF / 2 MB
Installation- / EMC-Guide PDF / 20 MB
POWERLINK Bus Controller User's Manual PDF / 2 MB
Redundancy for control systems PDF / 9 MB
X20 System User´s Manual PDF / 7 MB
証明書 バージョン (日付) ダウンロード
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
ABS Certificate of Product Design Assessment - X20 IO Series PDF / 2 MB
DNV Type Approval Certificate - X20 PDF / 194 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Lloyds Register PDF / 502 KB
RINA Type Approval Certificate - X20 / Power Panel T30 PDF / 1 MB
UK Declaration PLC X20 PDF / 151 KB

国と言語を選ぶ

B&R Logo