3AT450.6

Short description
I/O module 4 inputs for Pt100 resistance measurement
General information
Status indicators Converter function, measuring time
Diagnostics
Converter Yes, using LED status indicator
Power consumption
24 VDC 3.0 W
5 VDC 1.0 W
Total 4.0 W
Electrical isolation
Channel - Channel No
Channel - PLC Yes
Certifications
CE Yes
UKCA Yes
UL cULus E115267
Industrial control equipment
EAC Yes
Resistance measurement temperature inputs
Input Resistance measurement for 4-wire connections
Digital converter resolution 13500 steps internally
Conversion time 100 ms at 20 ms measurement time / 85 ms at 16.67 ms measurement time
Output format INT
Sensor Pt100: -50 to 450°C
Basic accuracy ±0.1% at 20°C
Operating conditions
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation 0 to 60°C
Storage -25 to 70°C
Relative humidity
Operation 5 to 95%
Mechanical properties
Note Order 1x terminal block TB170 separately.
Dimensions
Width System 2005 single-width
Can be installed on
Base unit Yes
Expansion unit Yes
Numero materiale:
3AT450.6
Descrizione:
2005 analog input module, 4 inputs, Pt100 (4-wire connections), -50 to +450°C, order 1x terminal block TB170 separately!
Accessori obbligatori
Terminal blocks
3TB170.9 2005 terminal block, 20-pin, screw clamp terminal block
3TB170.91 2005 terminal block, 20-pin, push-in terminal block
Aggiornamenti HW di Automation Studio Versione (data) Download
V2.6 HW Upgrade (3AT450.6) EXE / 398 KB
V3.0 HW Upgrade (3AT450.6) EXE / 397 KB
Documentazione Versione (data) Download
Datasheet 3AT450.6 PDF / 553 KB

Si prega di scegliere il Paese e la lingua

B&R Logo