Status display | Green LED (DC OK), threshold value Uout = 21.5 V |
Insulation voltages | |
Input - Output |
4 kV AC (type test) 2 kV AC (routine test) |
Input - Ground |
2 kV AC (type test) 2 kV AC (routine test) |
Output - Ground | 500 VDC (routine test) |
Connection type | Screw terminal |
Connection cross section | |
Input | |
Wire end sleeves | Flexible cables require wire end sleeves in order to fulfill EN 62368 / UL 60950 |
Flexible | 0.2 to 4 mm² / 22 to 10 AWG |
Inflexible | 0.2 to 6 mm² / 22 to 10 AWG |
Output | |
Wire end sleeves | Flexible cables require wire end sleeves in order to fulfill EN 62368 / UL 60950 |
Flexible | 0.5 to 10 mm² / 8 to 6 AWG |
Inflexible | 0.5 to 16 mm² / 8 to 6 AWG |
Wire stripping length |
8 mm (input) 10 mm (output) |
Certifications | |
CE | Yes |
UKCA | Yes |
UL |
cULus E123528 Industrial control equipment |
Input
Nominal input voltage | 2/3x 400 to 500 VAC |
Input voltage |
3x 320 to 575 VAC, 45 to 65 Hz 2x 360 to 575 VAC, 45 to 65 Hz |
Input current |
3x 2.0 A (400 VAC) 3x 1.6 A (480 VAC) |
Inrush current limiting | <20 A |
I2t | 1.3 A2s |
Power failure bypass |
>16 ms (400 VAC) >20 ms (480 VAC) |
Switch-on time | <1 s (typical) |
Power factor (cos φ) | 0.76 |
Leakage current to PE | <3.5 mA |
Protective circuit | Transient surge protection with varistor |
Required line fuse for device and line protection |
2/3x 10 A (characteristic B) 2/3x 16 A (characteristic B) |
Output
Nominal voltage | 24 VDC ±1% |
Output power | 960 W |
Setting range for output voltage | 22.5 to 29.5 VDC |
Output current | |
-25 to 55°C | 40.0 A |
>55°C | Derating: 2.5% per °C |
Current limiting | Approx. 48 A |
Control deviation |
<1% (static load change 10 to 90%) <2% (dynamic load change 10 to 90%) <0.1% (input voltage change ±10%) |
Rise time | <2 ms (UOUT (10 to 90%)) |
Residual ripple | <20 mVSS |
Switching peaks | <40 mVSS |
Can be connected in parallel | Yes, to establish redundancy and increase capacity |
Can be connected in series | No |
Max. capacitive load | Unlimited |
Protection against internal overvoltages | Yes, limited to <35 VDC |
Protection functions | Output protected against continuous short circuit, open circuit and overload |
Power back immunity | Max. 35 VDC |
Output noise suppression | Device complies with EN 55011 (class B) |
Efficiency, reliability
Efficiency | >91.5% |
MTBF | >500,000 h, per IEC 61709 (SN 29500) |
Power dissipation | |
Rated load | 87 W |
No-load operation | 11 W |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | No |
Installation elevation above sea level | |
Maximum | 4000 m |
Ventilation/Cooling | Normal convection, no fan required |
Degree of protection per EN 60529 | IP20 |
Protection class | I, with PE connection |
Ambient conditions
Temperature | |
Operation | -25 to 70°C (>55°C derating) |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | Max. 95%, non-condensing |
Vibration | |
Operation |
<15 Hz, amplitude ±2.5 mm, per IEC 60068-2-6 15 to 150 Hz, 2.3 g, 90 min |
Shock | |
Operation | 15 g in each direction, per IEC 60068-2-27 |
Pollution degree | 2, per EN 50178 |
Climate category | 3K3, per EN 60721 |
Mechanical properties
Housing | |
Material |
Steel sheet, galvanized Side panels: Aluminum |
Installation | Easy top-hat rail installation (NS 35 rails, EN 60715) |
Dimensions | |
Width | 139 mm |
Height | 130 mm |
Depth | 190 mm |
Weight | 3200 g |
Référence produit:
0PS3400.1Description:
- 400 to 500 VAC wide-range input
- Reliable supply even if one phase briefly fails in 3-phase operation
- High dielectric strength
- Can be connected in parallel for increased capacity and redundancy
- Reliable operation due to long power failure bypass function under full load and high MTBF (>500,000 h)
- International certification package
- Wide temperature range from -25 to 70°C
- Closed metal housing
Certifications | Version (date) | Téléchargement |
---|---|---|
EU Declaration Power supplies | PDF / 129 Ko |
Documentation | Version (date) | Téléchargement |
---|---|---|
Datasheet 0PS3400.1 | PDF / 479 Ko | |
Installation- / EMC-Guide | PDF / 20 Mo |
Généralités | Version (date) | Téléchargement |
---|---|---|
Power Supply Statement-Directive 2009/125/EC | PDF / 20 Ko |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D file DXF/STEP 0PS3400.1 | ZIP / 717 Ko |