Short description
I/O module 4 analog outputs 0 to 20 mA
General information
B&R ID code 0x16F4
Status indicators I/O function per channel, supply voltage, bus function
Diagnostics
I/O power supply Yes, using LED status indicator and software
Connection type
X2X Link M12, B-coded
Outputs 4x M12, A-coded
I/O power supply M8, 4-pin
Power consumption
Internal I/O 4.5 W
X2X Link power supply 0.75 W
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
KC Yes
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Power consumption
Actuator power supply Max. 12 W
Analog outputs
Output 0 to 20 mA
Digital converter resolution 12-bit
Conversion time 400 µs for all outputs
Settling time on output change over entire range Approx. 1 ms
Switch on/off behavior Internal enable relay for startup and errors
Output protection Protection against wiring with supply voltage, short-circuit proof
Output format Example: INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Load per channel Max. load is 400 Ω
Output filter Example: First-order low-pass filter / cutoff frequency 1.5 kHz
Max. gain drift 0.015%/°C
Max. offset drift 0.032%/°C
Error caused by load change Max. 0.5%, from 1 Ω → 400 Ω, resistive
Nonlinearity <0.1%
Insulation voltage between channel and bus 500 Veff
Output response when the power supply is switched on/off An enable relay is switched on at a defined value ≠ 0, default setting = 10 kΩ to GND
Short-circuit proof
Current limiting ±40 mA
To GND Yes
To sensor or I/O power supply Yes
Max. error at 25°C and 50 Ω load
Gain 0.2%
Offset 0.05%
Actuator power supply
Voltage I/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 500 mA Max. 2 VDC
Summation current Max. 0.5 A
Short-circuit proof Yes
Electrical properties
Electrical isolation
Channel isolated from bus

Channel not isolated from channel
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 190 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Número de material:
X67AO1323
Descripción:
  • 4 analog outputs 0 to 20 mA
  • Integrated enable relay for initial phase
  • Very short cycle times
  • Optimal shield grounding on all channels

The module is equipped with 4 outputs with 12-bit digital converter resolution. The range of the output signal is 0 to 20 mA.

Actualizaciones de hardware de Automation Studio Versión (fecha) Descargar
V2.6 HW Upgrade (X67AO1323F) EXE / 439 KB
V3.0 HW Upgrade (X67AO1323F) EXE / 438 KB
V4.0 HW Upgrade (X67AO1323) EXE / 519 KB
Certificados Versión (fecha) Descargar
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
E115267 UL CoC X67 PDF / 155 KB
EU Declaration ATEX X67 PDF / 191 KB
EU Declaration PLC X67 PDF / 674 KB
Safe cutoff of potential groups PDF / 211 KB
TÜV 05 ATEX 7201 X PDF / 5 MB
UK Declaration PLC X67 PDF / 469 KB
X20, X67 KC certificates PDF / 6 MB
Documentación Versión (fecha) Descargar
Datasheet X67AO1323 PDF / 351 KB
Installation- / EMC-Guide PDF / 20 MB
X67 System User´s Manual PDF / 6 MB
E-CAD (plantillas Electro o EPLAN) Versión (fecha) Descargar
X67 EPLAN P8 from V2.4 EXE / 105 MB
M-CAD (plantillas mecánicas) Versión (fecha) Descargar
3D File DXF/STEP X67 ZIP / 4 MB

Seleccione país e idioma