Short description
Bus controller POWERLINK (V1/V2) controlled node with up to 2 slots for interface modules
General information
B&R ID code 0xE217
Status indicators Module status, bus function
Diagnostics
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator and software
Support
Dynamic node allocation (DNA) Yes
Power consumption
Bus 2 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
EAC Yes
Interfaces
Fieldbus POWERLINK (V1/V2) controlled node
Type Type 2
Variant 2x shielded RJ45 (hub)
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex No
Autonegotiation Yes
Auto-MDI/MDIX Yes
Hub propagation delay 0.96 to 1 µs
Min. cycle time
Fieldbus 200 μs
X2X Link 200 μs
Synchronization between bus systems possible Yes
Cyclic data
Input data Max. 1488 bytes
Output data Max. 1488 bytes
Electrical properties
Electrical isolation POWERLINK isolated from bus and I/O
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Starting temperature Yes, -40°C
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Up to 100%, condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20cPS9400 separately.
Order 1x bus base X20cBB81 or X20cBB82 separately
Pitch
X20BB81 62.5+0.2 mm
X20BB82 87.5+0.2 mm
Materialenummer:
X20cBC1083
Beskrivelse:
  • POWERLINK
  • I/O configuration and firmware update via the fieldbus
  • Integrated hub for efficient cabling
  • Up to 2 slots for interface modules

The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler.

POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org.

The bus modules expanded to the left allow connection of up to 2 interface modules in addition to the bus controller.

Obligatorisk tilbehør
System modules for bus controllers
X20cPS9400 X20 power supply module, coated, for bus controller and internal I/O power supply X2X Link power supply
System modules for expandable bus controllers
X20cBB81 X20 bus base, coated, for X20 base module (BC, HB, etc.) and X20 power supply module, with one expansion slot for X20 add-on module (IF, HB, etc.), X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
X20cBB82 X20 bus base, coated, for X20 base module (BC, HB, etc.) and X20 power supply module, with 2 expansion slots for 2 X20 add-on modules (IF, HB, etc.), X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Valgfrit tilbehør
X20 interface module communication
X20cIF1041-1 X20 interface module, coated, for DTM configuration, 1 CANopen master interface, electrically isolated, order 1x terminal block TB2105 separately!
X20cIF1061-1 X20 interface module, coated, for DTM configuration, 1 PROFIBUS DP V0/V1 master interface, electrically isolated
X20cIF1063-1 X20 interface module, coated, for DTM configuration, 1 PROFIBUS DP V1 slave interface, electrically isolated
X20cIF10D3-1 X20 interface module, coated, for DTM configuration, 1 EtherNet/IP adapter (slave) interface, electrically isolated
X20cIF10E3-1 X20 interface module, coated, for DTM configuration, 1 PROFINET IO device (slave) interface module, electrically isolated
Automation Studio HW opgraderinger Version (dato) Download
V3.0 HW Upgrade (X20cBC1083) EXE / 2 MB
V4.0 HW Upgrade (X20cBC1083) EXE / 1 MB
Certifikater Version (dato) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
ABS Certificate of Product Design Assessment - X20 IO Series PDF / 2 MB
DNV Type Approval Certificate - X20 PDF / 194 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Lloyds Register PDF / 502 KB
RINA Type Approval Certificate - X20 / Power Panel T30 PDF / 1 MB
UK Declaration PLC X20 PDF / 151 KB
Dokumentation Version (dato) Download
Coated modules PDF / 62 KB
Data sheet X20(c)BC1083 PDF / 857 KB
Installation- / EMC-Guide PDF / 20 MB
POWERLINK Bus Controller User's Manual PDF / 2 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Elektro eller EPLAN skabeloner) Version (dato) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. skabeloner) Version (dato) Download
3D File STEP/DXF X20BC and X20IF Module ZIP / 1 MB

Vælg venligst land og sprog

B&R Logo