DWL@DWL10000777845

Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.6.0.0 * 05.03.2024 2 MB EXE AS6_HW_X20SI8110.exe
Popis V6.0 HW Upgrade (X20SI8110)

Revision information X20SI8110

Version 2.6.0.0:

ID: 780340
New data sheet V2.20
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 780355
Correction of the input filter with set "Filter off".
Correction of the input filter, if a "Filter off" is set and a channel error is detected.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 780400 / Support ID: 400412437
Configuration for Power Calculation available
The Configuration for Power Calculation is now available in Automation Studio
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\59202_1.fw(580)

Version 2.4.0.0:

ID: 719745
Failsafe at every boot
It could happen under rare conditions that the module is stuck in failsafe state at every boot, generating logger messages:
-1073565951/-1073561855 "internal cross communication error EPS" or -1073565945/-1073561849 "Received crc data is not equal to sent crc data"
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 726610
The power calculation of the modules is supported
The data for the power calculation of the data sheet is included in the HWX.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID:727130
New data sheet V2.10
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\59202_1.fw(574)

Version 2.3.1.0:

ID: 706330
Limit values for the module cycle time adjusted
The limit values for the calculation and monitoring of module cycle time and slot time adjusted.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 706390
New data sheet V2.08
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\59202_1.fw(573)

Version 2.3.0.0:

ID: 692365
Support of the DYNlink interface
The DYNlink interface is supported by the safe inputs.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 692395 / Support ID: 400311305
The OSDD signal at the pulse output is corrected.
The OSDD signal atthe pulse output is output correctly even when not in use.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 696565
New data sheet V2.07
For changes see chapter "Version history" in the data sheet.
Channel description changed:No
Configuration description changed: No
Firmware changed: No
Firmware: 10\59202_1.fw(572)

Version 2.2.0.0:

ID: 668560
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID:689935
Improvement of the internal voltage monitoring.
Improvement of the internal voltage monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 690080
New data sheet V2.06
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 690165
Propagation delay statistics
The Propagation delay statistics can now be readout.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 690170 / Support ID: 400299371
Loss of safety connection
Loss of safety connection, even though the parametrized "safe data duration" is longer than the network failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\59202_1.fw(571)

Version 2.1.0.0:

ID: 644310
major (even incompatible) changes for mapp Safety
First upgrade for mapp Safety.
ATTENTION: existing applications must beadapted - see chapter "Switching to mapp Safety" in help!
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\59202_1.fw(570)

Version 1.10.9.1:

ID: 643470
data sheet V1.141
See chapture "Version history" in thedata sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\59202_1.fw(330)

Version 1.10.9.0:

ID: 618230
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\59202_1.fw(330)

Version 1.10.1.0:

ID: 575525
add PhysicalStateChannels on X20SLX842
add PhysicalStateChannels on X20SLX842.
Channel description changed: Yes
Configurationdescription changed: No
Firmware changed: Yes

ID: 575530
Adapt filter algorithm to eliminate dependencies between TON and TOF-filter
Filter algorithm was adapted to eliminate dependencies between TON and TOF-filter which existed since FW V301.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 575535
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 575540
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 577395 / Support ID: 400234330
Increasethe tolerance of the voltage monitor
The tolerance of the voltage monitor was increased to prevent sporadic false errors 99849
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\59202_1.fw(325)

Version 1.10.0.6:

ID: 533070
Add blackout mode
Add blackout mode
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 543080
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 543085
New channel for ConnectionValid
New channel forConnectionValid
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\59202_1.fw(322)

Version 1.10.0.3:

ID: 463885
first official release
first official release
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 1\59202_1.fw(322)