2.2.1.0 * 01.08.2023 5 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 2.2.1.0:

ID: 771355
Faulty FlatStream initialization corrected
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\51886_1.fw(261), 1\51886_2.fw(261), 1\51886_3.fw(261)

Version 2.2.0.0:

ID: 744100
Adaptations for fieldbus support.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 747010
Corrected stability problem that could occur with certain devices
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 747030
Additional Registers available
Channel description changed: Yes
Configuration description changed:No
Firmware changed: No

ID: 747040
New documentation 1.45 is available
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 749935 / Support ID: 400372679
Corrected problem with Synchonized0x channels
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(261), 1\51886_2.fw(261), 1\51886_3.fw(261)

Version 2.1.0.0:

ID: 729385
Support HW variant 3
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 739260
New documentation 1.43 is available
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 741205
revision of the comboboxes
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 742900 / Support ID: 400367910
Support for IO-Link timestamp version 1.1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(256), 1\51886_2.fw(256), 1\51886_3.fw(256)

Version 2.0.2.0:

ID: 672750 / Support ID: 400302845
Correction for Automation Studio 3
The parameter CfO_BaudratePrescaler can be written with Library AsIoAcc.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.10.0.0:

ID:
Adaptations for Automation Studio 4.8
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.9.0.0:

ID: 628895 / Support ID: 400274753
Two-wire interface revised
The TWI driver was revised to improve e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.8.0.0:

ID: 614455
Module documentation revised
Data sheet V1.30
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614505
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identification procedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures inAutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614510
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(132), 1\51886_2.fw(132)

Version 1.7.0.0:

ID: 596585
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596590
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(126)

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configurationdescription changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channeldescription changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / Support ID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used as well.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of module is handled by "ioLinkSetMode" function, the module will report correctly the new channel status.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be providedto live list
Requirement AR > B4.25
Channel description changed:No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for module DTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1) without ISDU support can be used.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(118)

Version 1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes of parameter server enables user to implement this functionality ona wider range of OI-Link devics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(111)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.2.0.0 * 07.04.2022 5 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 2.2.0.0:

ID: 744100
Adaptations for fieldbus support.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 747010
Corrected stability problem that could occur with certain devices
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 747030
Additional Registers available
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 747040
New documentation 1.45 is available
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 749935 / Support ID: 400372679
Corrected problem with Synchonized0x channels
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(261), 1\51886_2.fw(261), 1\51886_3.fw(261)

Version 2.1.0.0:

ID: 729385
Support HW variant 3
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 739260
New documentation 1.43 is available
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 741205
revision of the comboboxes
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 742900 / Support ID: 400367910
Support for IO-Link timestamp version 1.1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(256), 1\51886_2.fw(256), 1\51886_3.fw(256)

Version 2.0.2.0:

ID: 672750 / Support ID: 400302845
Correction for Automation Studio 3
The parameter CfO_BaudratePrescaler can be written with Library AsIoAcc.
Channeldescription changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.10.0.0:

ID:
Adaptations for Automation Studio 4.8
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.9.0.0:

ID: 628895 / Support ID: 400274753
Two-wire interface revised
The TWI driver was revised to improve e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.8.0.0:

ID: 614455
Module documentation revised
Data sheet V1.30
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614505
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identification procedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures inAutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614510
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(132), 1\51886_2.fw(132)

Version 1.7.0.0:

ID: 596585
Behavior on connection loss revised
In case of connection loss, the"InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596590
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(126)

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / Support ID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used as well.
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of module is handled by "ioLinkSetMode" function, the module will report correctly the new channel status.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be provided to live list
Requirement AR > B4.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for module DTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID:486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1) without ISDU support can be used.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(118)

Version 1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes of parameter server enables user to implement this functionality ona wider range of OI-Linkdevics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(111)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.1.0.0 * 30.11.2021 4 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 2.1.0.0:

ID: 729385
Support HW variant 3
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 739260
New documentation 1.43 is available
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 741205
revision of the comboboxes
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 742900 / Support ID: 400367910
Support for IO-Link timestamp version 1.1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(256), 1\51886_2.fw(256), 1\51886_3.fw(256)

Version 2.0.2.0:

ID: 672750 / Support ID: 400302845
Correction for Automation Studio 3
The parameter CfO_BaudratePrescaler can be written with Library AsIoAcc.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.10.0.0:

ID:
Adaptations for Automation Studio 4.8
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.9.0.0:

ID: 628895 / Support ID: 400274753
Two-wire interface revised
The TWI driver was revised to improve e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.8.0.0:

ID: 614455
Module documentation revised
Data sheet V1.30
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614505
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identification procedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures inAutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614510
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(132), 1\51886_2.fw(132)

Version 1.7.0.0:

ID: 596585
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596590
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(126)

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed:Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / Support ID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used as well.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of module is handled by "ioLinkSetMode" function, the module will report correctly the new channel status.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be provided to live list
Requirement AR > B4.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for module DTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1) without ISDU support can be used.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(118)

Version 1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes of parameter server enables user to implement this functionality onawider range of OI-Link devics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(111)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
2.0.2.0 * 12.12.2019 4 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 2.0.2.0:

ID: 672750 / Support ID: 400302845
Correction for Automation Studio 3
The parameter CfO_BaudratePrescaler can be written with Library AsIoAcc.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.10.0.0:

ID:
Adaptations for Automation Studio 4.8
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.9.0.0:

ID: 628895 / Support ID: 400274753
Two-wire interface revised
The TWI driver was revised to improve e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.8.0.0:

ID: 614455
Module documentation revised
Data sheet V1.30
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614505
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identificationprocedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures in AutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614510
Communication behaviorof IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes
Firmware: 1\51886_1.fw(132), 1\51886_2.fw(132)

Version 1.7.0.0:

ID: 596585
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596590
Up-/Download behavior of paramerterserver revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(126)

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will beshown, when more Bytes are defined than can betransfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / Support ID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used aswell.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of module is handled by "ioLinkSetMode" function, the module will report correctly the new channel status.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be provided to live list
Requirement AR > B4.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for module DTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1) without ISDU support can be used.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(118)

Version 1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes of parameter server enables user to implement this functionality ona wider range of OI-Link devics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channeldescription changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(111)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.10.0.0 * 25.10.2019 4 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 1.10.0.0:

ID:
Adaptations for Automation Studio 4.8
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.9.0.0:

ID: 628895 / Support ID: 400274753
Two-wire interface revised
The TWI driver was revised toimprove e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.8.0.0:

ID: 614455
Module documentation revised
Data sheet V1.30
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614505
Identification procedure of IO-Link device extended
The optional verification of device ID and serialnumber of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now, the identification procedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures in AutomationStudio.
Channel description changed:Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614510
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(132), 1\51886_2.fw(132)

Version 1.7.0.0:

ID: 596585
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596590
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(126)

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown asconnected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmwarechanged: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / Support ID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used as well.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configuration description changed:No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of module is handled by "ioLinkSetMode" function, the module will report correctly the new channel status.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be provided to live list
Requirement AR >B4.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for moduleDTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1)without ISDU support can be used.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware:1\51886_1.fw(118)

Version 1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes of parameter server enables user to implement this functionality ona wider range of OI-Link devics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(111)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.9.0.0 * 21.02.2019 4 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 1.9.0.0:

ID: 628895 / Support ID: 400274753
Two-wire interface revised
The TWI driver was revised to improve e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(133), 1\51886_2.fw(133)

Version 1.8.0.0:

ID: 614455
Module documentation revised
Data sheet V1.30
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614505
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identification procedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures inAutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614510
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(132), 1\51886_2.fw(132)

Version 1.7.0.0:

ID: 596585
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596590
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(126)

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / Support ID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used as well.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of moduleis handled by "ioLinkSetMode" function, the modulewill report correctly the new channel status.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be provided to live list
Requirement AR > B4.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for module DTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1) without ISDU support can be used.
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes
Firmware: 1\51886_1.fw(118)

Version1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes of parameter server enables user to implement this functionality ona wider range of OI-Link devics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(111)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.8.0.0 * 13.11.2018 4 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 1.8.0.0:

ID: 614455
Module documentation revised
Data sheet V1.30
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: No

ID: 614505
Identificationprocedure of IO-Link device extended
The optional verification of deviceID and serial number of the connected IO-Link device can be done according toIO-Link revision 1.0 or 1.1. Up to now, the identification procedure was defined automatically (given by the IO-Link device). The extension offers to forceone of the identification procedures in AutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614510
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device isconnected to an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(132), 1\51886_2.fw(132)

Version 1.7.0.0:

ID: 596585
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596590
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(126)

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM viewrevised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / SupportID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used as well.
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of module is handled by "ioLinkSetMode" function, the module will report correctly the new channel status.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be provided to live list
Requirement AR > B4.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for module DTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1) without ISDU support can be used.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(118)

Version 1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes ofparameter server enables user to implement this functionality on a wider range of OI-Link devics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(111)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.7.0.0 * 30.05.2018 4 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 1.7.0.0:

ID: 596585
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596590
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(126)

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmwarechanged: Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / Support ID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used as well.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware:1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of module is handledby "ioLinkSetMode" function, the modulewill report correctly the new channelstatus.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be provided to live list
Requirement AR > B4.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for module DTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1) without ISDU support can be used.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(118)

Version 1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes of parameter server enables user to implement this functionality ona wider range of OI-Link devics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(111)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.6.1.1 * 05.09.2017 4 MB EXE AS4_HW_X67DS438A.exe
Popis V4.1 HW Upgrade (X67DS438A)

Revision information X67DS438A

Version 1.6.1.1:

ID: 540040
SDM view revised.
Connected IO-Linkdevices are shown as connected in SDM view.
Channel description changed:No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.1.0:

ID: 540040
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(125)

Version 1.6.0.2:

ID: 534170
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(125)

Version 1.5.1.0:

ID: 515970
Max. data transfer revised
Warning/Error message will be shown, whenmore Bytes are defined than can betransfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.5.0.1:

ID: 498430 / Support ID: 400194261
Continuous product improvement
Timeout behavior for DTM access revised; Very slow IO-Link devices can be used as well.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 503215
Module documentation revised
Data sheet V 1.10
Channel description changed: No
Configurationdescription changed: No
Firmware changed: No
Firmware: 1\51886_1.fw(122)

Version 1.4.0.0:

ID: 489645
Firmware revised for use with AsIoLink library
If channel mode of module is handled by "ioLinkSetMode" function, the module will report correctly the new channel status.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(119)

Version 1.3.0.1:

ID: 471250
Item designation can be provided to live list
Requirement AR > B4.25
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 485345
Support for module DTM revised
The user defined item designation is shown in livelist of module (required AR: B4.25 or higher)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 486555
Initializing of IO-Link slaves revised.
IO-Link devices (V1.1) without ISDU support can be used.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(118)

Version 1.2.0.0:

ID: 345640
Compatibility extended
Additional frame type implemented
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(116)

Version 1.1.0.1:

ID: 443900
Compatibility extended - parameter server
Changes of parameter server enables user to implement this functionality ona wider range of OI-Link devics
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\51886_1.fw(115)

Version 1.0.2.0:

ID: 399210
Support X67DS438A
Support for AutomationStudio incl. documentation
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:No
Firmware: 1\51886_1.fw(111)