2.0.1.0 * 11.12.2019 3 MB EXE AS3.0_HW_X20cDS438A.exe
Popis V3.0 HW Upgrade (X20cDS438A)

Revision information X20cDS438A

Version 2.0.1.0:

ID: 672745 / Support ID: 400302845
Correction forAutomation Studio 3
The parameter CfO_BaudratePrescaler can be written with Library AsIoAcc.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(133), 1\60247_2.fw(133)

Version 2.0.0.0:

ID:
Adaptationsfor Automation Studio 4.8
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.9.1.0:

ID: 637120
Confusing warning message eliminated
In several versions of AutomationStudio, a confusing warning message could occur. The message was eliminated because it was without any significance for using the module.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 639445
Module documentation revised
Data sheet V1.50
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(133), 1\60247_2.fw(133)

Version 1.9.0.0:

ID: 632210
Two-wire interface revised
The TWI driver was revised to improve e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(133), 1\60247_2.fw(133)

Version 1.8.0.0:

ID:614495
Module documentation revised
Data sheet V1.40
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614500
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identification procedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures inAutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614515
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(132), 1\60247_2.fw(132)

Version 1.7.0.0:

ID: 596575
Up-/Download behavior of paramerter server revised.
Channel description changed:No
Configuration description changed: No
Firmware changed: Yes

ID: 596580
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(126)

Version 1.6.1.1:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.1.0:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.0.2:

ID: 534175
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(125)

Version 1.5.1.0:

ID: 515960
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than canbetransfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)

Version 1.5.0.1:

ID: 484190
Support X20cDS438A
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.9.1.0 * 02.04.2019 6 MB EXE AS3.0_HW_X20cDS438A.exe
Popis V3.0 HW Upgrade (X20cDS438A)

Revision information X20cDS438A

Version 1.9.1.0:

ID: 637120
Confusing warning message eliminated
In several versions of AutomationStudio, a confusing warning message couldoccur. The message was eliminated because it was without any significance forusing the module.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 639445
Module documentation revised
Data sheet V1.50
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(133), 1\60247_2.fw(133)

Version 1.9.0.0:

ID: 632210
Two-wire interface revised
The TWI driver was revised to improve e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(133), 1\60247_2.fw(133)

Version 1.8.0.0:

ID: 614495
Module documentation revised
Data sheet V1.40
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614500
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identification procedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures inAutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614515
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(132), 1\60247_2.fw(132)

Version 1.7.0.0:

ID: 596575
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596580
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(126)

Version 1.6.1.1:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.1.0:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.0.2:

ID: 534175
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(125)

Version 1.5.1.0:

ID: 515960
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)

Version 1.5.0.1:

ID: 484190
Support X20cDS438A
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.9.0.0 * 21.02.2019 3 MB EXE AS3.0_HW_X20cDS438A.exe
Popis V3.0 HW Upgrade (X20cDS438A)

Revision information X20cDS438A

Version 1.9.0.0:

ID: 632210
Two-wire interface revised
The TWI driver was revised to improve e.g. the restart behavior of the module.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(133), 1\60247_2.fw(133)

Version 1.8.0.0:

ID: 614495
Module documentation revised
Data sheet V1.40
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614500
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identification procedurewas defined automatically (given by the IO-Link device). The extension offersto force one of the identification procedures in AutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 614515
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(132), 1\60247_2.fw(132)

Version 1.7.0.0:

ID: 596575
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596580
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(126)

Version 1.6.1.1:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.1.0:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.0.2:

ID: 534175
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(125)

Version 1.5.1.0:

ID: 515960
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)

Version 1.5.0.1:

ID: 484190
Support X20cDS438A
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.8.0.0 * 13.11.2018 3 MB EXE AS3.0_HW_X20cDS438A.exe
Popis V3.0 HW Upgrade (X20cDS438A)

Revision information X20cDS438A

Version 1.8.0.0:

ID: 614495
Module documentation revised
Datasheet V1.40
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 614500
Identification procedure of IO-Link device extended
The optional verification of device ID and serial number of the connected IO-Link device can be done according to IO-Link revision 1.0 or 1.1. Up to now,the identification procedure was defined automatically (given by the IO-Link device). The extension offers to force one of the identification procedures inAutomationStudio.
Channel description changed: Yes
Configuration description changed: Yes
Firmwarechanged: Yes

ID: 614515
Communication behavior of IO-Link master revised
The communication behavior was optimized if there is no device is connectedto an activated IO-Link channel.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(132), 1\60247_2.fw(132)

Version 1.7.0.0:

ID: 596575
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596580
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(126)

Version 1.6.1.1:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.1.0:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.0.2:

ID: 534175
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(125)

Version 1.5.1.0:

ID: 515960
Max. data transfer revised
Warning/Error message will be shown, when moreBytes are defined than can betransfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)

Version 1.5.0.1:

ID: 484190
Support X20cDS438A
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.7.0.0 * 30.05.2018 3 MB EXE AS3.0_HW_X20cDS438A.exe
Popis V3.0 HW Upgrade (X20cDS438A)

Revision information X20cDS438A

Version 1.7.0.0:

ID: 596575
Up-/Download behavior of paramerter server revised.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 596580
Behavior on connection loss revised
In case of connection loss, the "InputData" data points are reset.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(126)

Version 1.6.1.1:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.1.0:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.0.2:

ID: 534175
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(125)

Version 1.5.1.0:

ID: 515960
Max. data transfer revised
Warning/Error message willbe shown, when more Bytes are defined than can betransfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)

Version 1.5.0.1:

ID: 484190
Support X20cDS438A
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.6.1.1 * 05.09.2017 3 MB EXE AS3.0_HW_X20cDS438A.exe
Popis V3.0 HW Upgrade (X20cDS438A)

Revision information X20cDS438A

Version 1.6.1.1:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.1.0:

ID: 540035
SDM view revised.
Connected IO-Link devices are shown as connected in SDM view.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(125)

Version 1.6.0.2:

ID: 534175
Adaption of IO-Link baud rate
Baud rate optimized for fast answering IO-Link slaves
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\60247_1.fw(125)

Version 1.5.1.0:

ID: 515960
Max. data transfer revised
Warning/Error message will be shown, when more Bytes are defined than can be transfered.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)

Version 1.5.0.1:

ID: 484190
Support X20cDS438A
Support for Automation Studio
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\60247_1.fw(122)