DWL@DWL10000303024

Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.4.2.0 * 08.06.2017 2 MB EXE AS3.0_HW_X20cCP1586.exe
Popis V3.0 HW Upgrade (X20cCP1586)

Revision information X20cCP1586

Version 1.4.2.0:

ID: 537885 / Support ID: 400204420
POWERLINK V2: no asynchronous frames in mode NMT PRE_OPERATIONAL_1
Because of a timingproblem in the firmware it could happen that no asynchronous frames were sentin the mode PRE_OPERATIONAL_1
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57884_0.pci(17), 1\57884a0.epl(131)

Version 1.4.0.0:

ID: 497865
Configurable negative temperature display range
Channel descriptionchanged: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 520790
Module documentation revised
Data sheet V 1.37
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 521655
Correct setting of ETH-parameters when replacing the CPU
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57884_0.pci(17), 1\57884a0.epl(129)

Version 1.3.2.0:

ID: 490210
Additional info data points FirmwareVersion and HardwareVariant
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No
Firmware: 1\57884_0.pci(17), 1\57884a0.epl(129)

Version 1.3.0.0:

ID: 462625
IP packets with multicast addresses not received by POWERLINK interface (problem only occurs with Automation Runtime versions <A4.23)
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462645
Update online help
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 462730 / Support ID: 400134699
Reduced X2X susceptibility to disturbances
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 462810 / Support ID: 400164226
Corrected DRAM sizes in documentation
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57884_0.pci(17), 1\57884a0.epl(129)

Version 1.2.0.0:

ID: 443660 / Support ID: 400154848
IP packets with multicast addresses not received by the POWERLINK interface
Channel description changed: No
Configurationdescription changed: No
Firmware changed: Yes

ID: 445145
Documentation changed
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57884_0.pci(15), 1\57884a0.epl(128)

Version 1.1.0.0:

ID: 417220
Enhancement ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 417300
SupportBonding feature
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 417360
Documentation: enhancements and corrections
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 417490
Optimized EMC characteristics for GL
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 423945 / Support ID: 400138730
POWERLINK V2: "Controlled node" mode
In networks with heavy SoC jitter, the dropping out of an SoC sometimes caused a permanent freezing of the input data on the controlled node.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 424040 / Support ID: 400150240
POWERLINK V2: "Controlled node" mode
After a POWERLINK manager failed, thecontrolled node sometimes registered with an incorrect NMT status in the ident response.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57884_0.pci(15), 1\57884a0.epl(127)

Version 1.0.1.1:

ID: 391695 / Support ID: 400137793
Correction terminal mode
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\57884_0.pci(13), 1\57884a0.epl(123)

Version 1.0.1.0:

ID: 391225 / Support ID: 0
Sporadic error when starting the onboard POWERLINK interface corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57884_0.pci(13), 1\57884a0.epl(123)

Version 1.0.0.1:

ID: 341960
Support X20cCP1586
Enhancement online-help
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\57884_0.pci(12), 1\57884a0.epl(123)

Version 1.0.0.0:

ID: 341960
Support X20cCP1586
First version
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\57884_0.pci(11), 1\57884a0.epl(121)