General information
Status display Green LED (DC OK), threshold value Uout = 21.5 V
Insulation voltages
Input - Output 4 kV AC (type test)
2 kV AC (routine test)
Connection type Screw terminal
Connection cross section
Wire end sleeves Flexible cables require wire end sleeves in order to fulfill EN 62368 / UL 60950
Flexible 0.2 to 2.5 mm² / 24 to 12 AWG
Inflexible 0.2 to 2.5 mm² / 24 to 12 AWG
Wire stripping length 6.5 mm (input/output)
Certifications
CE Yes
UKCA Yes
UL cULus E123528
Industrial control equipment
Input
Nominal input voltage 100 to 240 VAC
Input voltage AC 85 to 264 V (wide range), 45 to 65 Hz
DC 95 to 250 V
Input current Approx. 1.3 A (120 VAC)
Approx. 0.8 A (230 VAC)
Inrush current limiting <15 A (typical)
I2t <1 A2s
Power failure bypass >20 ms (120 VAC)
>100 ms (230 VAC)
Switch-on time <0.5 s (typical)
Protective circuit Transient surge protection with varistor
Internal fuse 4 A slow-blow
Required line fuse for line protection 6 A (characteristic B)
10 A (characteristic B)
16 A (characteristic B)
Output
Nominal voltage 24 VDC ±1%
Output power 100 W
Setting range for output voltage 22.5 to 29.5 VDC (>24 VDC power constant)
Output current
-25 to 40°C 4.4 A
40 to 55°C 4.2 A
>55°C Derating: 2.5% per °C
Current limiting Max. 6.5 A
Control deviation <1% (static load change 10 to 90%)
<2% (dynamic load change 10 to 90%)
<0.1% (input voltage change ±10%)
Rise time <0.5 s (UOUT (10 to 90%))
Residual ripple <25 mVSS (at nominal values)
Switching peaks <25 mVSS (at nominal values)
Can be connected in parallel Yes, to establish redundancy and increase capacity
Can be connected in series Yes
Protection against internal overvoltages Yes, limited to approximately 35 VDC
Protection functions Output protected against continuous short circuit, open circuit and overload
Power back immunity Max. 35 VDC
Output noise suppression Device complies with EN 55011 (class B)
Efficiency, reliability
Efficiency >88% (at 230 VAC and nominal values)
MTBF >500,000 h, per IEC 61709 (SN 29500)
Power dissipation
Rated load Max. 13.2 W
No-load operation Max. 0.7 W
Operating conditions
Installation elevation above sea level
Maximum 6000 m
Ventilation/Cooling Normal convection, no fan required
Degree of protection per EN 60529 IP20
Protection class II
Ambient conditions
Temperature
Operation -25 to 70°C (>55°C derating)
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation Max. 95%, non-condensing
Vibration
Operation <15 Hz, amplitude ±2.5 mm, per IEC 60068-2-6
15 to 150 Hz, 2.3 g, 90 min
Shock
Operation 30 g in each direction, per IEC 60068-2-27
Pollution degree 2, per EN 50178
Climate category 3K3, per EN 60721
Mechanical properties
Installation Easy top-hat rail installation (DIN rail NS 35, EN 60715) or wall mounting
Dimensions
Width 90 mm
Height 90 mm
Depth 61 mm
Weight 400 g
Malzeme numarası:
0PS1042.2
Açıklama:
  • 100 to 240 VAC wide-range input
  • Can be connected in parallel for increased capacity and redundancy
  • Reliable operation due to long power failure bypass function under full load and high MTBF (>500,000 h)
  • International certification package
  • Wide temperature range from -25 to 70°C
  • Extra flat design
  • Easy DIN rail or wall mounting
24 VDC power supply, 1-phase, 4.2 A, input 100 to 240 VAC, wide range, top-hat rail installation
Dökümantasyon Sürüm (Tarih) İndirme
Datasheet 0PS1042.2 PDF / 501 KB
Installation- / EMC-Guide PDF / 20 MB
Genel Sürüm (Tarih) İndirme
Power Supply Statement-Directive 2009/125/EC PDF / 20 KB
M-CAD (Mechan. Şablonlar) Sürüm (Tarih) İndirme
3D file DXF/STEP 0PS1042.2 ZIP / 1 MB
Sertifikalar Sürüm (Tarih) İndirme
EU Declaration Power supplies PDF / 129 KB

Lütfen ülke ve dil seçin

B&R Logo