cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNV
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCS
Yes
LR
ENV1
KR
Yes
ABS
Yes
BV
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
KC
Yes
B&R ID code
0x267E
Status indicators
Operating state, module status
Additional power dissipation caused by actuators (resistive) [W]
-
Output I/O power supply
Nominal output voltage
24 VDC from the internal I/O power supply
Fuse
Integrated 6.3 A, slow-blow, can be replaced
Behavior on short circuit
Integrated fuse
Permissible contact load
10 A
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation elevation above sea level
0 to 2000 m
No limitation
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529
IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation
-25 to 60°C
Vertical mounting orientation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical properties
Note
Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch
12.5+0.2 mm
Materialnummer:
X20PD0012
Beskrivning:
Integrated exchangeable microfuse
Monitoring of the fuse
Potential for routing as needed
The potential distributor module provides 12x 24 VDC (from the internal I/O supply) on the terminal connections and opens up additional wiring possibilities for actuators and sensors. The module is equipped with a replaceable microfuse between the 24 VDC potential on the terminal block and the X20 system I/O supply. The function of the fuse is monitored.