6x 24 VDC on the terminals, 6x ground on the terminals
General information
Diagnostics
Module run/error
Yes, using LED status indicator and software
Fuse monitoring
Yes, using LED status indicator and software
Power consumption
Bus
0.12 W
Internal I/O
1.15 W
External I/O
1.15 W
Certifications
CE
Yes
UKCA
Yes
CRA (Cyber Resilience Act)
In preparation
ATEX
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
UL
cULus E115267 Industrial control equipment
HazLoc
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNV
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCS
Yes
LR
ENV1
KR
Yes
ABS
Yes
BV
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
KC
Yes
B&R ID code
0x267F
Status indicators
Operating state, module status
Additional power dissipation caused by actuators (resistive) [W]
-
Input power supply with feed
Nominal input voltage
24 VDC -15% / +20% external, ground external
Input current
Max. 6 A
Fuse
Integrated 6.3 A, slow-blow, can be replaced
Behavior on short circuit
No protection available Use an external fuse.
Reverse polarity protection
No
Output I/O power supply
Behavior on short circuit
On 24 VDC power supply
Integrated fuse
On GND power supply
No protection available
Nominal output voltage
24 VDC, ground
Permissible contact load
6 A
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation elevation above sea level
0 to 2000 m
No limitation
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529
IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation
-25 to 60°C
Vertical mounting orientation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical properties
Note
Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM01 or X20BM11 separately.
Pitch
12.5+0.2 mm
Materialnummer:
X20PD2113
Beskrivning:
Integrated exchangeable microfuse
Monitoring of the fuse
Potential for routing as needed
Can be used as feed module for the I/O supply
The potential distributor module with feed can provide 6x 24 VDC and 6x ground connections from the internal I/O supply on the terminals. This module can also be used instead of a special feed module for the internal I/O supply. The internal 24 VDC supply is connected to the terminal connections through a replaceable microfuse for protection. The 24 VDC feed and the functionality of the fuse are monitored.