X67DC2322

Short description
I/O module 2 resolver inputs, 2 digital inputs, 2 digital outputs
General information
Diagnostics
Outputs Yes, using LED status indicator and software
I/O power supply Yes, using LED status indicator and software
Connection type
X2X Link M12, B-coded
Inputs/Outputs M12, A-coded
Encoder M12, 12-pin, A-coded
I/O power supply M8, 4-pin
Power consumption
Internal I/O 1 W
X2X Link power supply 0.75 W
Certifications
CE Yes
UKCA Yes
CRA (Cyber Resilience Act) In preparation
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
KC Yes
B&R ID code 0xA5C7
Status indicators I/O function per channel, supply voltage, bus function
Additional power dissipation caused by actuators (resistive) [W] 12.5 W
Resolver inputs
Reference output
Output voltage Typ. 4.4 Veff
Output current Max. 50 mAeff
Frequency 10 kHz
Resolver transformation ratio
BRX 0.5 (±10%)
BRT 1 (±10%)
Quantity 2
Type Differential
Angular position resolution 14-bit
Short-circuit protection (reference output) Yes
Input impedance 10.4 kΩ - j*11.1 kΩ
Resolver type BRX / BRT
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Digital inputs
Input filter
Hardware ≤20 µs
Software -
Switching threshold
Low <5 V
High >15 V
Quantity 2
Nominal voltage 24 VDC
Input current at 24 VDC Typ. 5 mA
Input circuit Sink
Sensor power supply 0.5 A summation current
Input delay <1 ms
Digital outputs
Switching delay
0 → 1 Max. 500 µs
1 → 0 Max. 500 µs
Switching frequency
Resistive load Max. 100 Hz
Quantity 2
Nominal voltage 24 VDC
Nominal output current 0.5 A
Total nominal current 1 A
Output circuit Source
Output protection Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply
Electrical properties
Electrical isolation
Channel isolated from bus

Channel not isolated from channel
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Weight 200 g
Número do material:
X67DC2322
Descrição:
  • 2 resolvers
  • BRX/BRT evaluation
  • 2 digital inputs and outputs for each

The module is equipped with 2 resolver connections as well as 2 digital inputs and outputs for each. It is possible to evaluate BRX and BRT resolvers using a configurable sine gain of 1 or 0.25.

Atualizações de HW Automation Studio Version (Data) Download
AS 2.6 HW Upgrade (X67DC2322) EXE / 563 KB
V3.0 HW Upgrade (X67DC2322) EXE / 3 MB
V4.0 HW Upgrade (X67DC2322) EXE / 2 MB
Certificados Version (Data) Download
2226379 CSA Certificate of Compliance X20 X67 PDF / 385 KB
E115267 UL CoC X67 PDF / 345 KB
EU Declaration ATEX X67 PDF / 191 KB
EU Declaration PLC X67 PDF / 674 KB
Safe cutoff of potential groups PDF / 211 KB
TÜV 05 ATEX 7201 X PDF / 5 MB
UK Declaration PLC X67 PDF / 469 KB
X20, X67 KC certificates PDF / 6 MB
Documentação Version (Data) Download
Data sheet X67DC2322 PDF / 1 MB
X67 System User´s Manual PDF / 19 MB
E-CAD (Modelos Electro ou EPLAN) Version (Data) Download
X67 EPLAN P8 from V2.4 EXE / 105 MB
M-CAD (Mechan. Modelos) Version (Data) Download
3D File DXF/STEP X67 ZIP / 2 MB

Por favor escolha o país e o idioma

B&R Logo