Short description
I/O module 8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B2 digital outputs, 24 VDC, 50 mA, OSSD <500 µs, SafeLOGIC-X technology
General information
B&R ID code 0x2F20
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Outputs Yes, using LED status indicator and software
Inputs Yes, using LED status indicator and software
Power consumption
Bus 0.4 W
Internal I/O 2.5 W
Electrical isolation
Channel - Bus Yes
Channel - Channel No
Certification
CE Yes
cULus
ATEX Zone 2 In preparation
EN IEC 61508:2010, EN IEC 62061:2010, EN ISO 13849-1:2008, EN IEC 61511:2004 Yes
EN 50156-1:2004 Yes
Safety characteristics
Note See section "Safety characteristics".
Safe digital inputs
Nominal voltage 24 VDC
Input filter
Hardware ≤150 µs
Software Configurable between 0 and 500 ms
Input circuit Sink
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Min. 2 mA to max. 3.28 mA
Input resistance Min. 7.33 kΩ
Error detection time 100 ms
Isolation voltage between channel and bus 500 Veff
Switching threshold
Low <5 VDC
High >15 VDC
Current on loss of ground
IOUT <100 µA
IGND <50 mA
Pulse outputs
Design Push-Pull
Nominal output current 50 mA
Output protection Shutdown of individual channels in the event of overload or short circuit
Peak short circuit current 0.5 A for 120 µs
Short circuit current 15 mAeff
Leakage current when switched off 0.1 mA
Switching voltage I/O power supply minus voltage drop due to RDS(on)
Total nominal current 200 mA
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation at elevations above sea level 0 to 2000 m, no limitation
EN 60529 protection IP20
Environmental conditions
Temperature
Operation
Horizontal installation 0 to 60°C
Vertical installation 0 to 50°C
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical characteristics
Note Order 2x safety-keyed terminal block separately.
Order 1x safety-keyed bus module separately.
Spacing 25+0.2 mm
Material number:
X20SLX842-1
Description:
X20 SafeLOGIC-X controller (Safety+) 8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B digital outputs, 24 VDC, 50 mA, OSSD <500 µs
Mandatory Accessories
Bus modules
X20BM33 X20 bus module, for X20 SafeIO modules, internal I/O power supply connected through
X20BM36 X20 bus module, for X20 SafeIO modules, with node number switch, internal I/O power supply connected through
Terminal blocks
X20TB52 X20 terminal block, 12-pin, safety-keyed
Aktualizacja Automation Studio HW Version (Date) Download
V6.0 HW Upgrade (X20SLX842-1) EXE / 620 KB
V6.0 HW Upgrade (X20SLX842-1) EXE / 620 KB
V6.0 HW Upgrade (X20SLX842-1) EXE / 620 KB
V6.0 HW Upgrade (X20SLX842-1) EXE / 620 KB
Certyfikaty Version (Date) Download
E115267 UL Certificate of Compliance X20 PDF / 2 MB
E537419 UL Certificate of Compliance X20 PDF / 617 KB
EU Data Act - X20 SafePLC - Connected Product Information Notice PDF / 92 KB
EU Declaration of Conformity CE_Declaration_FS_X20 PDF / 420 KB
M6A 041745 0023 TÜV Süd FS Certificate Safety+ PDF / 1,008 KB
UK Declaration FS PLC X20 PDF / 112 KB
Dokumentacja Version (Date) Download
Data sheets SafeIO and SafeLogic PDF / 29 MB
Integrated safety technology user's manual PDF / 59 MB
E-CAD (szablony Electro lub EPLAN) Version (Date) Download
Makro-/Artikeldaten (X20SLX842-1) EXE / 966 KB
Narzędzia / Przykłady Version (Date) Download
Sistema (VDMA) library ZIP / 5 KB

Wybierz kraj i język