Short description
Communication module PROFIBUS DP V0/V1 master
General information
B&R ID code 0x1F22
Status indicators Module status, bus status
Diagnostics
Module status Yes, using LED status indicator and software
Bus status Yes, using LED status indicator and software
Power consumption 1.4 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
KC Yes
Interfaces
Interface IF1
Fieldbus PROFIBUS DP V0/V1 master
Variant 9-pin female DSUB connector
Max. distance 1200 m
Transfer rate Max. 12 Mbit/s
Terminating resistor External using T-connector (0G1000.00-090)
Controller EC1
Memory 8 MB SDRAM
Cyclic data
Input data 3.5 kB
Output data 3.5 kB
Electrical properties
Electrical isolation PLC isolated from PROFIBUS (IF1)
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Slot In the X20 PLC
Material number:
X20IF1061
Description:
  • PROFIBUS DP V1 master

The interface module can be used to expand the X20 CPU for specific applications. It is equipped with a PROFIBUS DP V1 master interface.

Optional Accessories
Infrastructure components
0G1000.00-090 Bus connector, RS485, for PROFIBUS networks

Wybierz kraj i język