I/O module 4 inputs for potentiometer displacement gauge
General information
Diagnostics
Module run/error Yes, using LED status indicator and software
Input Yes, using LED status indicator and software
Connection type
X2X Link M12, B-coded
Inputs 4x M12, A-coded
I/O power supply M8, 4-pin
Power consumption
Bus 0.75 W
Internal I/O 2 W
Certifications
CE Yes
UKCA Yes
CRA (Cyber Resilience Act) In preparation
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
KC Yes
B&R ID code 0x9957
Status indicators Channel status, operating state, module status
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protective function Reverse polarity protection
Potentiometer power supply
Short-circuit proof Yes
Potentiometer supply voltage Upot 4.5 V / Max. 50 mA
Voltage drop for short-circuit protection at 50 mA Max. 0.13 VDC
Potentiometer, displacement gauge
Output of digital value
Open circuit on GND 0x7FFF
Open circuit on slider 0x7FFF
Open circuit on Upot 0x0000
Valid range of values 0x0000 - 0x7FFF
Input filter
Cutoff frequency 10 kHz
Slope 60 dB/Dec.
Input type Single-ended input in the range of 0 to Upot
Digital converter resolution 15-bit
Measurement sensor 0.5 to 10 kΩ, potentiometer
Conversion time <200 µs for all channels
Output format INT (16-bit 2s complement)
Short-circuit protection Upot Yes
Influence of cable length Twisted and shielded conductors, cable length as short as possible, cable routing separate from load circuits, without intermediate terminal to sensor
Common-mode range 0 to Upot
Insulation voltage between input and bus 500 Veff
Quantization; LSB value (14-bit) 275 µV
Conversion procedure Sample & Hold
Electrical properties
Electrical isolation Bus isolated from analog input
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Weight 195 g
Materiaalnummer:
X67AI4850
Omschrijving:
  • 4 inputs for potentiometer displacement gauge

The module is a 4-channel analog input module. It is used to evaluate potentiometer displacement gauges.

Automation Studio HW Upgrades Versie (Datum) Download
V2.6 HW Upgrade (X67AI4850) EXE / 1 MB
V3.0 HW Upgrade (X67AI4850) EXE / 458 KB
V3.0 HW Upgrade (X67AI4850) EXE / 2 MB
V4.0 HW Upgrade (X67AI4850) EXE / 2 MB
Certificaten Versie (Datum) Download
2226379 CSA Certificate of Compliance X20 X67 PDF / 385 KB
E115267 UL CoC X67 PDF / 345 KB
EU Declaration ATEX X67 PDF / 191 KB
EU Declaration PLC X67 PDF / 674 KB
TÜV 05 ATEX 7201 X PDF / 5 MB
UK Declaration PLC X67 PDF / 469 KB
X20, X67 KC certificates PDF / 6 MB
Documentatie Versie (Datum) Download
Data sheet X67AI4850 PDF / 893 KB
X67 System User´s Manual PDF / 19 MB
E-CAD (Electro of EPLAN Templates) Versie (Datum) Download
X67 EPLAN P8 from V2.4 EXE / 105 MB
M-CAD (Mechan. Templates) Versie (Datum) Download
3D File DXF/STEP X67 ZIP / 2 MB

Graag land en taal kiezen

B&R Logo