DWL@DWL10000604628

仕様版 言語
オペレーティングシステム
日付
サイズ
タイプ ダウンロード
2.6.1.0 * 2025/03/04 2 MB EXE AS4_HW_X67SC4122.L12.exe
説明 V4.6 HW Upgrade (X67SC4122.L12)

Revision information X67SC4122.L12

Version 2.6.1.0:

ID: FUVI-10596
New data sheet V2.21
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: FUVI-10595
Sensor supply for X67 modules
The pulse outputs can be configured to supply voltage for field mounted sensors.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: QCAS-240
Test pulse generation and evaluation process corrected
The time sequence for test pulse generation and evaluation has been revised. Channels are acknowledged simultaneously after a short circuit, there is no discrepancy error.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\42918_1.fw(581)

Version 2.6.0.0:

ID: 780165
Correction of the input filter with set "Filter off".
Correction of the input filter, if a "Filter off" is set and a channel error is detected.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 780270
New data sheet V2.18
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\42918_1.fw(580)

Version 2.2.0.0:

ID: 668620
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 688770
Loss of safety connection
Loss of safety connection, even though the parametrized "safe data duration" is longer than the network failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689720
Propagation delay statistics
The Propagation delay statistics can now be read out.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689905
Increased delay of external feedback error detection
Increased delay of external feedback error detection
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689955
Improvement of the internal voltage monitoring.
Improvement of the internal voltagemonitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 690010
Improvementof the feedback diagnosis.
Improvement of the feedback diagnosis of the output.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 690100
New data sheet V2.06
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\42918_1.fw(571)

Version 2.1.0.0:

ID: 644285
major (even incompatible) changes for mapp Safety
First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\42918_1.fw(570)

Version 1.10.9.1:

ID: 643220
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(330)

Version 1.10.9.0:

ID: 618290
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(330)

Version 1.10.1.1:

ID:516730
fixed internal communication problems
fixed internal communication problems
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552645
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552650
Loggerentry on negativ edge of SafeModuleOK
Ifa negativ edge on SafeModuleOK is detected, a logger entry will be generated
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 553760
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(325)

Version 1.10.1.0:

ID: 474970
Correction for FBK_Status_1
Correction for FBK_Status_1
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 516730
fixed internal communication problems
fixed internal communication problems
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552645
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552650
Loggerentry on negativ edge of SafeModuleOK
If a negativ edge on SafeModuleOK is detected, a logger entry will be generated
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 553760
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(325)

Version 1.10.0.6:

ID: 533065
Add blackout mode
Add blackout mode
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 533155
New channel for ConnectionValid
New channel for ConnectionValid
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 533175
Update ECAD data
Update ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(320)

Version 1.10.0.0:

ID: 402885
Step File
The step file is available since 14th November 2014.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 441620
EPLAN Data for pinout - file corrected
EPLAN Data for pinout - file corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 470660
Support of release 1.10 including openSAFETY 1.5
Support of release 1.10 including openSAFETY 1.5 with easier parametrization of timing parameters
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 470665
changed manual verion to 1.100
changed manual verion to 1.100
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(320)

Version 1.9.1.1:

ID: 425470
change of input filter
The behaviour of the input filter has changed.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 425475
Update Online Help
Update Online Help V1.91
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 425480
fw valid from SafetyRelease 1.4 on
The firmware is used for all SafetyReleases from 1.4 on.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272),6\42918_1.fw(301)

Version 1.9.0.0:

ID: 286520
Diagnosticcoverage not relevant for users
Since the parameter "Diagnostic coverage" isn't relevant for users, it was generally removed from the datasheet of allsafety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 413875
SafeModuleID >300
Now it is possible to set SafeModuleID greater than 300, like described in the AS-Help.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414030
Channel-Status-Info ON
The default value of the Channel-Status information is now ON.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414190
added parameter "Disable OSSD"
added parameter "Disable OSSD"
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414250
parameter max. Switching Frequency removed
Parameter max. Switching Frequency has no meaning any more.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes

ID: 414295
2-channel evaluation: additional information at warning
If warning "discrepancy time elapsed" appears for 2-channel evaluation, info0 will now display the chosen PLCopen FBK (equivalent or antivalent).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 414370
Update Online Help
Update Online Help V1.90
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290), 5\42918_1.fw(300)

Version 1.6.0.8:

ID: 388470
The module also supports SafetyRelease 1.8
Starting with this version, the module also supports SafetyRelease 1.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.7:

ID: 339300
internal Adjustments
internal Adjustments
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.5:

ID: 335515
The module also supports SafetyRelease 1.7
Starting with this version, the module also supports SafetyRelease 1.7
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 335520
unlock of SafeModule IDs > 300
SafeModule IDs up to 1023 are now unlocked
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.0:

ID: 314285
Adaption of module configuration file release 1.6
Adaption of module configuration file release 1.6
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.5.0.4:

ID: 303415
Support of AutomationStudio 4.0
Support of AutomationStudio 4.0
Channel description changed: No
Configuration description changed: No
Firmwarechanged: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.5.0.3:

ID: 287445
New feature
Discrepancy time maximum from 500ms to 10s increased.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 290270
Datasheet Version 1.50
Datasheet version 1.50 added in Html format
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.4.1.3:

ID: 284655
Release für kompatibles Safety Release 1.5
ID 284600

Parameter for backwards compatibility in description file changed
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281)

Version 1.4.0.3:

ID: 261780
Increase of minimum load to 12mA
The minimum load was increased to 12mA in the documentationErhöhung der Mindestlast auf 12mA
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281)
仕様版 言語
オペレーティングシステム
日付
サイズ
タイプ ダウンロード
2.6.0.0 * 2024/03/05 2 MB EXE AS4_HW_X67SC4122.L12.exe
説明 V4.6 HW Upgrade (X67SC4122.L12)

Revision information X67SC4122.L12

Version 2.6.0.0:

ID: 780165
Correction of the input filter with set "Filter off".
Correction of the input filter, if a "Filter off" is set and a channel error is detected.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 780270
New data sheet V2.18
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\42918_1.fw(580)

Version 2.2.0.0:

ID: 668620
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 688770 / Support ID:400299371
Loss of safety connection
Loss of safety connection, eventhough the parametrized "safe data duration"is longer than the network failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689720
Propagation delay statistics
The Propagation delay statistics can now be read out.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689905
Increased delay of external feedback error detection
Increased delay of external feedback error detection
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689955
Improvement of the internal voltage monitoring.
Improvement of the internal voltage monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 690010
Improvement of the feedbackdiagnosis.
Improvement of the feedback diagnosis of the output.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 690100
New data sheet V2.06
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\42918_1.fw(571)

Version 2.1.0.0:

ID: 644285
major (even incompatible) changes for mapp Safety
First upgradefor mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\42918_1.fw(570)

Version 1.10.9.1:

ID: 643220
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(330)

Version 1.10.9.0:

ID: 618290
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(330)

Version 1.10.1.1:

ID: 516730
fixed internal communication problems
fixed internal communication problems
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552645
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552650
Loggerentry on negativ edge of SafeModuleOK
If a negativ edge on SafeModuleOK is detected, a logger entry will be generated
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 553760
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(325)

Version 1.10.1.0:

ID: 474970
Correction for FBK_Status_1
Correction for FBK_Status_1
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 516730
fixed internal communication problems
fixed internal communication problems
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552645
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552650
Loggerentry on negativ edge of SafeModuleOK
If a negativ edge on SafeModuleOK is detected, a logger entry will be generated
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 553760
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301),7\42918_1.fw(325)

Version 1.10.0.6:

ID: 533065
Add blackout mode
Add blackout mode
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 533155
New channel for ConnectionValid
New channel for ConnectionValid
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 533175
Update ECAD data
Update ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(320)

Version 1.10.0.0:

ID: 402885 / Support ID: 400142740
Step File
The step file is available since 14th November 2014.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 441620 / Support ID: 400159816
EPLAN Data for pinout - file corrected
EPLAN Data for pinout - file corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 470660
Support of release 1.10 including openSAFETY 1.5
Support of release 1.10including openSAFETY 1.5 with easier parametrizationof timing parameters
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 470665
changed manual verion to 1.100
changed manual verion to 1.100
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(320)

Version 1.9.1.1:

ID: 425470
change of input filter
The behaviour of the input filter has changed.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 425475
Update Online Help
Update Online Help V1.91
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:No

ID: 425480
fw valid from SafetyRelease 1.4 on
The firmware is used for all SafetyReleases from 1.4 on.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301)

Version 1.9.0.0:

ID: 286520 / Support ID: 400082173
Diagnostic coverage not relevantfor users
Since the parameter "Diagnostic coverage" isn't relevant for users, it was generally removed from the datasheet of all safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 413875
SafeModuleID >300
Now it is possible to set SafeModuleID greater than 300, like described in the AS-Help.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414030
Channel-Status-Info ON
The default value of the Channel-Status information is now ON.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414190
added parameter "Disable OSSD"
added parameter "Disable OSSD"
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414250
parameter max. Switching Frequency removed
Parameter max. Switching Frequency has no meaning any more.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes

ID: 414295
2-channel evaluation: additional information at warning
If warning "discrepancy time elapsed" appears for 2-channel evaluation, info0will now display the chosen PLCopen FBK (equivalent or antivalent).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 414370
Update Online Help
Update Online Help V1.90
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290), 5\42918_1.fw(300)

Version 1.6.0.8:

ID: 388470
The module also supports SafetyRelease 1.8
Starting with this version, the module also supports SafetyRelease 1.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.7:

ID: 339300
internal Adjustments
internal Adjustments
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.5:

ID: 335515
The module also supports SafetyRelease 1.7
Starting with this version, the module also supports SafetyRelease 1.7
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 335520 / Support ID: 400083263
unlock of SafeModule IDs > 300
SafeModule IDs up to 1023 are now unlocked
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.0:

ID: 314285
Adaption of module configuration file release 1.6
Adaption of module configuration file release 1.6
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.5.0.4:

ID: 303415
Support of AutomationStudio 4.0
Support of AutomationStudio 4.0
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.5.0.3:

ID: 287445
New feature
Discrepancy time maximum from 500ms to 10s increased.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 290270
Datasheet Version 1.50
Datasheet version 1.50 added in Html format
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.4.1.3:

ID: 284655
Release für kompatibles Safety Release 1.5
ID 284600

Parameter for backwards compatibility in description file changed
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281)

Version 1.4.0.3:

ID: 261780
Increase of minimum load to 12mA
The minimum load was increased to 12mA in the documentationErhöhung der Mindestlast auf 12mA
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281)
仕様版 言語
オペレーティングシステム
日付
サイズ
タイプ ダウンロード
2.2.0.0 * 2020/07/21 2 MB EXE AS4_HW_X67SC4122.L12.exe
説明 V4.6 HW Upgrade (X67SC4122.L12)

Revision information X67SC4122.L12

Version 2.2.0.0:

ID: 668620
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 688770 / Support ID: 400299371
Loss of safety connection
Loss of safety connection, even though theparametrized "safe data duration"is longer than the network failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689720
Propagation delay statistics
The Propagation delay statistics can now be read out.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689905
Increased delay of external feedback error detection
Increased delay of external feedback error detection
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 689955
Improvement of the internal voltage monitoring.
Improvement of the internal voltage monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 690010
Improvement of the feedback diagnosis.
Improvement of the feedback diagnosis of the output.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 690100
New data sheet V2.06
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\42918_1.fw(571)

Version 2.1.0.0:

ID: 644285
major (even incompatible) changes for mapp Safety
First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\42918_1.fw(570)

Version 1.10.9.1:

ID: 643220
data sheetV1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(330)

Version 1.10.9.0:

ID: 618290
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(330)

Version 1.10.1.1:

ID: 516730
fixed internalcommunication problems
fixed internal communication problems
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552645
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552650
Loggerentry on negativ edge of SafeModuleOK
If a negativ edge on SafeModuleOK is detected, a logger entry will be generated
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 553760
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(325)

Version 1.10.1.0:

ID: 474970
Correction for FBK_Status_1
Correction for FBK_Status_1
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 516730
fixed internal communication problems
fixed internal communication problems
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552645
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552650
Loggerentry on negativ edge of SafeModuleOK
If a negativ edge on SafeModuleOK is detected, a logger entry will be generated
Channeldescription changed: No
Configuration description changed: No
Firmware changed: No

ID: 553760
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(325)

Version 1.10.0.6:

ID: 533065
Add blackout mode
Add blackout mode
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 533155
Newchannel for ConnectionValid
New channel for ConnectionValid
Channeldescription changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 533175
Update ECAD data
Update ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(320)

Version 1.10.0.0:

ID: 402885 / Support ID: 400142740
Step File
The step file is available since 14th November 2014.
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: No

ID: 441620 / Support ID: 400159816
EPLAN Data for pinout - file corrected
EPLAN Data for pinout - file corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 470660
Support ofrelease 1.10 including openSAFETY 1.5
Support of release 1.10 including openSAFETY 1.5 with easier parametrization of timing parameters
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 470665
changed manual verion to 1.100
changed manual verion to 1.100
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(320)

Version 1.9.1.1:

ID: 425470
change of input filter
The behaviour of the input filter has changed.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 425475
UpdateOnline Help
Update Online Help V1.91
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 425480
fw valid from SafetyRelease 1.4 on
The firmware is usedfor all SafetyReleases from 1.4 on.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301)

Version 1.9.0.0:

ID: 286520 / Support ID: 400082173
Diagnostic coverage not relevant for users
Since the parameter "Diagnostic coverage" isn't relevant for users, it was generally removed from the datasheet of all safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 413875
SafeModuleID >300
Now it is possibleto set SafeModuleID greater than 300, like described in the AS-Help.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414030
Channel-Status-Info ON
The default value of the Channel-Status information is now ON.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414190
added parameter "Disable OSSD"
added parameter "Disable OSSD"
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414250
parameter max. Switching Frequency removed
Parameter max. Switching Frequency has no meaning any more.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes

ID: 414295
2-channel evaluation: additional information at warning
If warning"discrepancy time elapsed" appears for 2-channel evaluation, info0 will now display the chosen PLCopen FBK (equivalent or antivalent).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 414370
Update Online Help
Update Online Help V1.90
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290), 5\42918_1.fw(300)

Version 1.6.0.8:

ID: 388470
The module also supports SafetyRelease 1.8
Starting with this version, the module also supports SafetyRelease 1.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.7:

ID: 339300
internal Adjustments
internal Adjustments
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.5:

ID: 335515
The module also supports SafetyRelease 1.7
Starting with this version, the module also supports SafetyRelease 1.7
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 335520 / Support ID: 400083263
unlock of SafeModule IDs > 300
SafeModule IDs up to 1023 are now unlocked
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.0:

ID: 314285
Adaption of module configuration file release 1.6
Adaption of module configuration file release 1.6
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.5.0.4:

ID: 303415
Support of AutomationStudio 4.0
Support of AutomationStudio 4.0
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.5.0.3:

ID: 287445
New feature
Discrepancy time maximum from 500ms to 10s increased.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 290270
Datasheet Version 1.50
Datasheet version 1.50 added in Html format
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.4.1.3:

ID: 284655
Release für kompatibles Safety Release 1.5
ID 284600

Parameter for backwards compatibility in description file changed
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281)

Version 1.4.0.3:

ID: 261780
Increase of minimum load to 12mA
The minimum load was increased to 12mA in the documentationErhöhung der Mindestlast auf 12mA
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281)
仕様版 言語
オペレーティングシステム
日付
サイズ
タイプ ダウンロード
2.1.0.0 * 2019/07/05 1 MB EXE AS4_HW_X67SC4122.L12.exe
説明 V4.6 HW Upgrade (X67SC4122.L12)

Revision information X67SC4122.L12

Version 2.1.0.0:

ID: 644285
major (even incompatible) changes for mapp Safety
First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes
Firmware: 10\42918_1.fw(570)

Version 1.10.9.1:

ID: 643220
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(330)

Version 1.10.9.0:

ID: 618290
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(330)

Version 1.10.1.1:

ID: 516730
fixed internal communication problems
fixed internal communication problems
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552645
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552650
Loggerentry on negativ edge of SafeModuleOK
If a negativ edge on SafeModuleOK is detected, a logger entry will be generated
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 553760
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(325)

Version 1.10.1.0:

ID: 474970
Correction for FBK_Status_1
Correction for FBK_Status_1
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 516730
fixed internal communication problems
fixed internal communication problems
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552645
Provide CRC of the Firmware
Provide CRC of the Firmware
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 552650
Loggerentry on negativ edge of SafeModuleOK
If a negativ edge on SafeModuleOK is detected, a logger entry will be generated
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 553760
New default values
The default values for "Filter On" and "Discrepancy Time" have been modified
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(325)

Version 1.10.0.6:

ID: 533065
Add blackout mode
Add blackout mode
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 533155
New channel for ConnectionValid
New channel for ConnectionValid
Channel description changed: Yes
Configuration description changed: No
Firmware changed: No

ID: 533175
Update ECAD data
Update ECAD data
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301), 7\42918_1.fw(320)

Version 1.10.0.0:

ID: 402885 / Support ID: 400142740
Step File
The step file is available since 14th November 2014.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 441620 / Support ID: 400159816
EPLAN Data for pinout- file corrected
EPLAN Data for pinout - file corrected
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 470660
Support of release 1.10 including openSAFETY 1.5
Support of release 1.10 including openSAFETY 1.5 with easier parametrization of timing parameters
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 470665
changed manual verion to 1.100
changed manual verion to 1.100
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301),7\42918_1.fw(320)

Version 1.9.1.1:

ID: 425470
change of input filter
The behaviour of the input filter has changed.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 425475
Update Online Help
Update OnlineHelp V1.91
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 425480
fw valid fromSafetyRelease 1.4 on
The firmware is used for all SafetyReleases from 1.4 on.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 6\42918_1.fw(301)

Version 1.9.0.0:

ID: 286520 / Support ID: 400082173
Diagnostic coverage not relevant for users
Since the parameter "Diagnostic coverage" isn't relevant for users, it was generally removed from the datasheet of all safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 413875
SafeModuleID >300
Now it is possible to set SafeModuleID greater than 300, like described in the AS-Help.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414030
Channel-Status-Info ON
The default value of the Channel-Status information is now ON.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414190
added parameter "Disable OSSD"
added parameter "Disable OSSD"
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 414250
parameter max. Switching Frequency removed
Parameter max. Switching Frequency has no meaning any more.
Channel description changed: Yes
Configuration description changed: No
Firmware changed: Yes

ID: 414295
2-channel evaluation: additional information at warning
If warning "discrepancy time elapsed" appears for 2-channel evaluation, info0 will now display the chosen PLCopen FBK (equivalent or antivalent).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 414370
Update Online Help
Update Online Help V1.90
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290), 5\42918_1.fw(300)

Version 1.6.0.8:

ID: 388470
The module alsosupports SafetyRelease 1.8
Starting with this version, the module also supports SafetyRelease 1.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.7:

ID: 339300
internal Adjustments
internal Adjustments
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.5:

ID: 335515
The module also supports SafetyRelease 1.7
Starting with this version, the module also supports SafetyRelease 1.7
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 335520 / Support ID: 400083263
unlock of SafeModule IDs > 300
SafeModule IDs up to 1023 are now unlocked
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.6.0.0:

ID: 314285
Adaption of module configuration file release 1.6
Adaption ofmodule configuration file release 1.6
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.5.0.4:

ID: 303415
Support of AutomationStudio 4.0
Support of AutomationStudio 4.0
Channel description changed: No
Configurationdescription changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.5.0.3:

ID: 287445
New feature
Discrepancy time maximum from 500ms to 10s increased.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 290270
Datasheet Version 1.50
Datasheet version 1.50 added in Html format
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281), 4\42918_1.fw(290)

Version 1.4.1.3:

ID: 284655
Release für kompatibles SafetyRelease 1.5
ID 284600

Parameter for backwards compatibility in description file changed
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281)

Version 1.4.0.3:

ID: 261780
Increase of minimum load to 12mA
The minimum load was increased to 12mA in the documentationErhöhung der Mindestlast auf 12mA
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:No
Firmware: 2\42918_1.fw(272), 3\42918_1.fw(281)