General information
| B&R ID code | 0xEF21 |
| Certifications | |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | Evaluation ongoing |
| Functional safety | Yes (openSAFETY) |
| UL |
cULus E115267 Industrial control equipment |
Safety characteristics
| EN ISO 13849-1:2015 | |
| Category | Cat. 4 |
| PL | PL e |
| DC | >94% |
| MTTFD per channel | 2500 years |
| Mission time | Max. 20 years |
|
IEC 61508:2010, IEC 61511:2004, EN 62061:2013 |
|
| SIL CL | SIL 3 |
| SFF | >90% |
| PFH / PFHd | |
| Module | <1*10-10 |
| openSAFETY wired | Negligible |
| openSAFETY wireless | <1*10-14 * Number of openSAFETY packets per hour |
| PFD per channel | <2*10-5 |
| Proof test interval (PT) | 20 years |
| Emergency stop | |
| EN ISO 13849-1:2015 | |
| B10d |
Emergency stop switching element (1.20.126.414/0000): 130,000 Emergency stop button (1.30.273.512/0300): 130,000 |
Interfaces
Features
| Pushbuttons | |
| Quantity | 2 (green, red) |
| Type |
Rafix 22 FS+ 1.30.270.021/2500 (green) Rafix 22 FS+ 1.30.270.021/2300 (red) |
| Selector switch | |
| Quantity | 1 |
| Type | Rafix 22 FS+ 1.30.272.102/2200 |
| Key switch | |
| Quantity | 1 |
| Type | Rafix 22 FS+ 1.30.255.222/0000 |
| Emergency stop | |
| Quantity | 1 |
| Type | RAFIX 22 FS+ Plus 1 1.30.273.512/0300 |
| Standard switching element | |
| Quantity | 4 |
| Type | 2x maintained / 2x momentary - RAFIX 22 FS universal, 1.20.126.005/0000 |
| Emergency stop switching element | |
| Quantity | 1 |
| Type | Maintained - RAFIX 22 FS+ PCB gold, 1.20.126.414/0000 |
Electrical properties
Operating conditions
| Degree of protection per EN 60529 | IP65 with panel with mounting unit 5ACCMA00.0000-000, 5ACCMA00.0001-000 or 5ACCMA00.0002-000 |
| Degree of protection per UL 50 | Type 4X indoor with mounting unit 5ACCMA00.0000-000, 5ACCMA00.0001-000 or 5ACCMA00.0002-000 |
Ambient conditions
Référence produit:
5ACCKPS0.215C-000Description:
AP5000 swing arm expansion option - Expansion unit POWERLINK SAFETY - 1x emergency stop (SAFETY) - 2x pushbutton (red and green) - 1x selector switch (SAFETY) - 1x key switch (SAFETY) - 1x front USB interface - For panel 5AP5230.215C-000
| Automation Studio HW Upgrades | Version (date) | Téléchargement |
|---|---|---|
| V4.2 HW Upgrade (5ACCKPS0.215C-000) | EXE / 4 Mo | |
| V4.6 HW Upgrade (5ACCKPS0.215C-000) | EXE / 4 Mo |
| Certifications | Version (date) | Téléchargement |
|---|---|---|
| M6A 041745 0010 TÜV Süd FS Certificate SafeDESIGNER, SafeLOGIC, SafeIO | PDF / 842 Ko |
| Documentation | Version (date) | Téléchargement |
|---|---|---|
| Data sheet 5ACCKPS0.215C-000 | PDF / 3 Mo | |
| Data sheet B050006543xx-yy and B050006677xx-yy - Legacy | PDF / 269 Ko | |
| Data sheet B050006543xx-yy and B050006677xx-yy - mapp Safety | PDF / 140 Ko |
| M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
|---|---|---|
| 3D files DXF/STP 5ACCKPS0.215C-000 and 5ACCKPS1.215C-000 | ZIP / 2 Mo |