Please choose country and language

Short description
I/O module 6 safe type A digital inputs, 6 pulse outputs, 24 VDC, 2 safe type B1 digital outputs, 24 VDC, 0.5 A, OSSD <500 µs
General information
B&R ID code 0xBDA5
System requirements
Automation Studio 3.0.81.15 or later
Automation Runtime 3.00 or later
SafeDESIGNER 2.70 or later
Safety Release 1.2 or later
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using status LED and software
Outputs Yes, using status LED and software
Inputs Yes, using status LED and software
Blackout mode
Scope Module
Function Module function
Standalone mode No
Max. I/O cycle time 1 ms
Power consumption
Bus 0.25 W
Internal I/O 1.4 W
Electrical isolation
Channel - Bus Yes
Channel - Channel No
Certifications
CE Yes
KC Yes
EAC Yes
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
DNV GL Temperature: A (0 - 45°C)
Humidity: B (up to 100%)
Vibration: A (0.7 g)
EMC: B (bridge and open deck)
KR Yes
Functional safety cULus FSPC E361559
Energy and industrial systems
Certified for functional safety
ANSI UL 1998:2013
Functional safety IEC 61508:2010, SIL 3
EN 62061:2013, SIL 3
EN ISO 13849-1:2015, Cat. 4 / PL e
IEC 61511:2004, SIL 3
Functional safety EN 50156-1:2004
Safety characteristics
EN ISO 13849-1:2015
MTTFD 2500 years
Mission time Max. 20 years
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
PFH / PFHd
Module <1*10-10
openSAFETY wired Negligible
openSAFETY wireless <1*10-14 * Number of openSAFETY packets per hour
PFD <2*10-5
Proof test interval (PT) 20 years
Safe digital inputs
EN ISO 13849-1:2015
Category Cat. 3 when using individual input channels,
Cat. 4 when using input channel pairs (e.g. SI1 and SI2) or more than 2 input channels
PL PL e
DC >94%
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
SIL CL SIL 3
SFF >90%
Safe digital outputs
EN ISO 13849-1:2015
Category Cat. 3 if parameter "Disable OSSD = Yes - Warning",
Cat. 4 if parameter "Disable OSSD = No"
PL PL d if parameter "Disable OSSD = Yes - Warning",
PL e if parameter "Disable OSSD = No"
DC >60% if parameter "Disable OSSD = Yes - Warning",
>94% if parameter "Disable OSSD = No"
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
SIL CL SIL 2 if parameter "Disable OSSD = Yes - Warning",
SIL 3 if parameter "Disable OSSD = No"
SFF >60% if parameter "Disable OSSD = Yes - Warning",
>90% if parameter "Disable OSSD = No"
I/O power supply
Nominal voltage 24 VDC
Voltage range 24 VDC -15% / +20%
Integrated protection Reverse polarity protection
Safe digital inputs
Variant Type A
Nominal voltage 24 VDC
Input characteristics per EN 61131-2 Type 1
Input filter
Hardware ≤150 μs
Software Configurable between 0 and 500 ms
Input circuit Sink
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Max. 3.28 mA
Input resistance Min. 7.33 kΩ
Error detection time 100 ms
Isolation voltage between channel and bus 500 Veff
Switching threshold
Low <5 VDC
High >15 VDC
Line length between pulse output and input Max. 60 m with unshielded line
Max. 400 m with shielded line
Safe digital outputs
Variant FET, 2x positive switching, type B1, output level readable
Nominal voltage 24 VDC
Nominal output current 0.5 A
Total nominal current 1 A
Output protection Thermal short-circuit shutdown, integrated protection for switching inductive loads
Braking voltage when switching off inductive loads Max. 45 VDC
Error detection time 1 s
Isolation voltage between channel and bus 500 Veff
Peak short-circuit current Max. 12 A
Leakage current when switched off <500 µA
Residual voltage ≤300 mVDC at nominal current
Switching voltage I/O power supply minus residual voltage
Max. switching frequency 1000 Hz
Test pulse length Max. 500 µs
Max. capacitive load 100 nF
Current on loss of ground
IOUT <1 mA
IGND <180 mA
Pulse outputs
Variant Push-Pull
Nominal output current 20 mA
Output protection Shutdown of individual channels in the event of overload or short circuit
Peak short-circuit current 25 A for 15 µs
Short-circuit current 100 mAeff
Leakage current when switched off 0.1 mA
Residual voltage 3 VDC
Switching voltage I/O power supply minus residual voltage
Total nominal current 120 mA
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level 0 to 2000 m, no limitation
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation 0 to 60°C
Vertical mounting orientation 0 to 50°C
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x safety-keyed terminal block separately.
Order 1x safety-keyed bus module separately.
Spacing 25+0.2 mm
Material number:
X20SC2212
Description:
  • 6 safe digital inputs, sink circuit
  • 6 pulse outputs
  • Software input filter configurable for each channel
  • 2 safe digital outputs, output type B with 0.5 A, source circuit
  • Integrated output protection

The module is equipped with 6 safe digital inputs and 2 safe digital outputs. It is designed for a nominal voltage of 24 VDC.

The module can be used to read in digital signals and to control actuators in safety-related applications up to PL e or SIL 3.

The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.

The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The "high-side high-side" variant (output type B) is required for actuators with reference potential (e.g. Enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. Safe digital output channels provide protection against automatic restart when network errors occur.

This module is designed for X20 12-pin terminal blocks.

Mandatory Accessories
Bus modules
X20BM33 X20 bus module, for X20 SafeIO modules, internal I/O power supply continuous
X20BM36 X20 bus module, for X20 SafeIO modules, with node number switch, internal I/O power supply continuous
Terminal blocks
X20TB5F X20 terminal block, 16-pin, safety-keyed
Automation Studio HW Upgrades Version (Date) Download
V3.0 HW Upgrade (X20SC2212) EXE / 3 MB
V4.0 HW Upgrade (X20SC2212) EXE / 3 MB
V4.6 HW Upgrade (X20SC2212) EXE / 919 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
DNV GL Type Approval Certificate - X20 / Power Panel T30 PDF / 171 KB
E115267 UL CoC X20 PDF / 825 KB
FS Certificate mapp Safety PDF / 5 MB
FS EN 50156 Zertifikat SafeLOGIC, SafeIO PDF / 314 KB
FS Zertifikat SafeDESIGNER, SafeLOGIC, SafeIO PDF / 420 KB
FTZU 09 ATEX 0083X PDF / 697 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Documentation Version (Date) Download
Data sheet X20(c)SC2212 - Legacy PDF / 2 MB
Data sheet X20(c)SC2212 - mapp Safety PDF / 825 KB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D file STEP X20(c)Sxxxxx - Terminal block right side ZIP / 21 KB
DFX File I/O Slice ZIP / 4 KB
Dimensions PDF X20 I/O Slice PDF / 45 KB
Tools / Utilities / Examples Version (Date) Download
Sistema library ZIP / 263 KB

Please choose country and language