Derating of continuous output current depending on ambient temperature
|
|
Clock frequency 4 kHz
|
No derating (up to 50°C)
|
Other clock frequencies
|
The derating curves are included in the installation instructions, which can be downloaded from the homepage (www.br-automation.com).
|
Derating of continuous output current depending on installation elevation
|
|
Starting at 1000 m above sea level
|
1%, per 100 m
|
Max. continuous output current (In)
|
|
At 240 VAC
|
8 A
|
Max. transient current for 60 s
|
12 A
|
Output frequency range
|
0.5 to 500 Hz
|
Nominal clock frequency
|
4 kHz
|
Nominal clock frequency
|
|
Min.
|
2 kHz
|
Max.
|
16 kHz
|
Short-term overload torque (typical value)
|
170 to 200% of the rated motor torque
|
Braking torque
|
|
With braking resistor
|
100% of the rated motor torque continually, up to 150% for 60 s
|
Without braking resistor (typical value)
|
100% of the rated motor torque
|
Max. motor cable length
|
|
Shielded cable
|
50 m
|
Non-shielded cable
|
100 m
|
Motor control profiles
|
Standard profile (voltage/frequency ratio - U/f characteristic curve) Performance profile (flux vector control without encoder) Pump/fan profile (quadratic characteristic curve Kn²), Energy saving profile (especially for ventilation)
|
Main protective functions of inverter
|
Thermal protection against overheating Protection against short circuits between motor phases Protection against mains phase failure on a 3-phase supply Protection against motor phase failures Overcurrent protection between motor phases and ground Overvoltage and undervoltage protection on the mains supply
|
Motor protection
|
Thermal protection integrated in the inverter through continually calculating the l²t value
|