Please choose country and language

Short description
I/O module 2 relays with 1 normally open contact each, 230 VAC / 6 A, 24 VDC / 6 A
General information
B&R ID code 0xD205
System requirements
Automation Studio 3.0.81.15 or later
Automation Runtime 3.00 or later
SafeDESIGNER 2.70 or later
Safety Release 1.2 or later
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using status LED and software
Outputs Yes, using status LED and software
Blackout mode
Scope Module
Function Module function
Standalone mode No
Max. I/O cycle time 1 ms
Power consumption
Bus 0.26 W
Internal I/O 1.15 W
Electrical isolation
Channel - Bus Yes
Channel - Channel Yes
Certifications
CE Yes
EAC Yes
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
DNV GL In preparation
Functional safety cULus FSPC E361559
Energy and industrial systems
Certified for functional safety
ANSI UL 1998:2013
Functional safety IEC 61508:2010, SIL 3
EN 62061:2013, SIL 3
EN ISO 13849-1:2015, Cat. 4 / PL e
IEC 61511:2004, SIL 3
Functional safety EN 50156-1:2004
Relays
EN 50155 Yes
EN 50205 Yes
Safety characteristics
EN ISO 13849-1:2015
MTTFD 2500 years
Mission time Max. 20 years
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
PFH / PFHd
Module <1*10-10
openSAFETY wired Negligible
openSAFETY wireless <1*10-14 * Number of openSAFETY packets per hour
PFD <2*10-5
Proof test interval (PT) 20 years
Safe relay channels
EN ISO 13849-1:2015
Category Cat. 1 if the relay channel is used individually,
Cat. 4 if 2 relay channels are connected in series
PL PL c if the relay channel is used individually,
PL e if 2 relay channels are connected in series
B10d
DC1, 24 VDC 6 A / 780,000
AC1, 230 VAC 6 A / 780,000
AC15, 230 VAC 3 A / 1,960,000
DC13, 24 VDC 5 A / 780,000
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
SIL CL SIL 1 if the relay channel is used individually,
SIL 3 if 2 relay channels are connected in series
I/O power supply
Nominal voltage 24 VDC
Voltage range 24 VDC -15% / +20%
Integrated protection Reverse polarity protection
Relay outputs
Variant 2 relays, each with 1 normally open contact, internal high-side and low-side control
Diagnostic status Contact position determined by positively driven contacts
Max. switching frequency 10 Hz
Switching delay
0 → 1 <50 ms
1 → 0 <50 ms
Isolation voltage between channel and bus Safe disconnection of 300 VAC per EN 50178
Isolation voltage between channel and channel Tested at 1350 VAC
Contact resistance (without terminal block) 20 mΩ
Contact service life See "Contact service life".
Short-circuit protection, overload protection External 6 A gL/gG fuse (blow-out fuse), LS automat C characteristic 1.6 A
Switching voltage range 5 to 24 VDC, 5 to 230 VAC
Switching current range 5 mA to 6 A
Coil voltage 24 VDC -15% / +20%
Short-circuit proof Yes, 1000 A (with specified short-circuit / overload protection)
Max. inrush current 30 A for 20 ms
Overvoltage category per EN 60664-1 II
Max. switching capacity
AC1 230 VAC / 6 A
AC15 230 VAC / 3 A
DC1 24 VDC / 6 A
DC13 24 VDC / 5 A / 0.1 Hz
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level 0 to 2000 m, no limitation
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation 0 to 60°C
Vertical mounting orientation 0 to 50°C
Derating See section "Derating".
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x safety-keyed terminal block separately.
Order 1x safety-keyed bus module separately.
Spacing 25+0.2 mm
Material number:
X20SO2530
Description:
  • 2 safe relay outputs
  • Output type "Relay"
  • Relay module for 230 VAC / 24 VDC
  • Switching current 6 A
  • Normally open contact
  • Single-channel isolated outputs

This module is equipped with 2 safe relay outputs.

The module can be used for controlling floating actuators in safety-related applications up to PL e or SIL 3.

Safety relays are installed in the module. The positively driven feedback contacts are evaluated internally by the module. Safe digital output channels provide protection against automatic restart when network errors occur.

This module is designed for X20 12-pin terminal blocks.

Mandatory Accessories
Bus modules
X20BM33 X20 bus module, for X20 SafeIO modules, internal I/O power supply continuous
X20BM36 X20 bus module, for X20 SafeIO modules, with node number switch, internal I/O power supply continuous
Terminal blocks
X20TB72 X20 terminal block, 12-pin, safety-keyed, 240 VAC, red
Automation Studio HW Upgrades Version (Date) Download
V3.0 HW Upgrade (X20SO2530) EXE / 980 KB
V4.0 HW Upgrade (X20SO2530) EXE / 2 MB
V4.6 HW Upgrade (X20SO2530) EXE / 1,011 KB
Certificates Version (Date) Download
244665 CSA HazLoc Certificate of Compliance X20, X67 PDF / 56 KB
E115267 UL CoC X20 PDF / 825 KB
FS Certificate mapp Safety PDF / 5 MB
FS EN 50156 Zertifikat SafeLOGIC, SafeIO PDF / 314 KB
FS Zertifikat SafeDESIGNER, SafeLOGIC, SafeIO PDF / 420 KB
FTZU 09 ATEX 0083X PDF / 697 KB
Documentation Version (Date) Download
Data sheet X20(c)SOx530 - Legacy PDF / 1 MB
Data sheet X20(c)SOx530 - mapp Safety PDF / 1 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X20 EPLAN P8 from V2.4 EXE / 161 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D file STEP X20Sxxx - Terminal block left side ZIP / 19 KB
DFX File I/O Slice ZIP / 4 KB
Dimensions PDF X20 I/O Slice PDF / 45 KB
Tools / Utilities / Examples Version (Date) Download
Sistema library ZIP / 263 KB

Please choose country and language

B&R Logo