Short description
I/O module 4 analog inputs ±10 V
General information
B&R ID code 0xAB1B
Status indicators I/O function for each channel, supply voltage, bus function
Diagnostics
Inputs Yes, using status LED and software
I/O power supply Yes, using status LED and software
Connection type
X2X Link M12, B-keyed
Inputs 4x M12, A-keyed
I/O power supply M8, 4-pin
Power consumption
Internal I/O 3 W
X2X Link power supply 0.75 W
Certifications
CE Yes
KC Yes
EAC Yes
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Power consumption
Sensor power supply Max. 12 W
Analog inputs
Input ±10 V
Input type Differential input
Digital converter resolution 16-bit
Conversion time 400 µs for all inputs
Output format INT
Output format
Voltage INT 0x8001 - 0x7FFF / 1 LSB = 0x0001 = 305.2 µV
Input impedance in signal range 20 MΩ
Input protection Protection against wiring with supply voltage
Permissible input signal Max. ±30 V
Output of digital value during overload
Undershoot 0x8001
Overshoot 0x7FFF
Conversion procedure Successive approximation
Max. error at 25°C
Gain 0.12%
Offset 0.06%
Max. gain drift 0.01 %/°C
Max. offset drift 0.0075% / °C
Common-mode rejection
DC >50 dB
50 Hz >50 dB
Common-mode range ±11 V
Crosstalk between channels <-70 dB
Nonlinearity <0.0062%
Isolation voltage between input and bus 500 VEff
Input filter
Cutoff frequency 1 kHz
Slope 40 dB
Sensor power supply
Voltage I/O power supply minus voltage drop for short circuit protection
Voltage drop for short-circuit protection at 500 mA Max. 2 VDC
Summation current Max. 0.5 A
Short-circuit proof Yes
Electrical properties
Electrical isolation
Channel isolated from bus

Channel not isolated from channel
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 190 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm
Material number:
X67AI1233
Description:
  • 4 analog inputs ±10 V
  • 16-bit digital converter resolution
  • Open/Short circuit detection
  • Configurable digital input filters
  • Very short cycle times
  • Optimal shield grounding on all channels

The module is equipped with 4 inputs with 16-bit digital converter resolution. The input signal range is ±10 V.

Automation Studio HW Upgrades Version (Date) Download
V2.7 HW Upgrade (X67AI1233) EXE / 1 MB
V3.0 HW Upgrade (X67AI1233) EXE / 2 MB
V4.0 HW Upgrade (X67AI1233) EXE / 1 MB
Certificates Version (Date) Download
E115267 UL CoC X67 PDF / 84 KB
TÜV 05 ATEX 7201 X PDF / 129 KB
Documentation Version (Date) Download
Datasheet X67AI1233 PDF / 441 KB
X67 System User´s Manual PDF / 19 MB
E-CAD (Electro or EPLAN Templates) Version (Date) Download
X67 EPLAN P8 EXE / 85 MB
X67 EPLAN P8 from V2.4 EXE / 105 MB
M-CAD (Mechan. Templates) Version (Date) Download
3D File DXF/STEP X67 ZIP / 1 MB