5x 24 VDC on the terminals, 5x ground on the terminals
General information
B&R ID code
0x2680
Status indicators
Operating state, module status
Diagnostics
Module run/error
Yes, using LED status indicator and software
Fuse monitoring
Yes, using LED status indicator and software
Power consumption
Bus
0.12 W
Internal I/O
-
External I/O
1.15 W
Additional power dissipation caused by actuators (resistive) [W]
-
Certifications
CE
Yes
UKCA
Yes
CRA (Cyber Resilience Act)
In preparation
ATEX
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
UL
cULus E115267 Industrial control equipment
HazLoc
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNV
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCS
Yes
LR
ENV1
KR
Yes
ABS
Yes
BV
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
KC
Yes
Input power supply
Nominal input voltage
24 VDC -15% / +20% external, ground external
Fuse
Integrated 6.3 A, slow-blow, can be replaced
Reverse polarity protection
No
Output power supply
Nominal output voltage
24 VDC, ground
Permissible contact load
10 A
Behavior on short circuit
On 24 VDC power supply
Integrated fuse
On GND power supply
No protection available
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation elevation above sea level
0 to 2000 m
No limitation
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529
IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation
-25 to 60°C
Vertical mounting orientation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical properties
Note
Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch
12.5+0.2 mm
Material number:
X20PD0016
Description:
Integrated exchangeable microfuse
Monitoring of the fuse
Potential for routing as needed
Distribution of the load and electronics supply
Isolation from the internal I/O supply
The potential distributor module provides 5x 24 VDC and 5x ground connections (from an external supply) at the terminals. There is no connection to the internal I/O supply, so this module only serves to distribute an external supply for the load and electronics supply. The externally fed 24 VDC supply is provided on the terminal connections through a replaceable microfuse. The 24 VDC feed and the functionality of the fuse are monitored.