Please choose country and language

General information
Terminals Robust screw terminals
Status indicators
Cutoff in fuse mode LED, red
Operation LED, green
Overload LED, red
Certifications
Terminal block
Connection cross section
Flexible 0.5 to 4 mm² / 20 to 10 AWG
Inflexible 0.5 to 6 mm² / 20 to 10 AWG
Input
Input voltage 3 AC 340-576 V, 47-63 Hz
DC 450-820V
Input current 3 x 1.5A
External overcurrent protection Each phase internally fused
External fuse for line protection if necessary
Transient immunity Active transient filter, therefore resistant to transients acc. to VDE 0160 / W2
Output (including logic)
Output noise suppression Unit complies with EN 61000-6-3 (class B)
Output power 490 W
Nominal voltage DC 24-28 V (default: 24.5 V ±0.5%)
Power back immunity 35 V
Protection functions Output protected against short circuit, open line and overload
Overvoltage protection At 33 V ±10%: switches to hiccup mode
Permissible output load
TU = 0 to 45°C 24.5 V / 25 A (612 W) or 28 V / 22 A (616 W)
TU = 0 to 60°C 24.5 V / 20 A (490 W) or 28 V / 18 A (504 W)
Efficiency, reliability
Efficiency Typ. 92% (24.5 V / 20 A, Vin<sub>nom</sub>)
MTBF 504,000 h
Losses Typ. 42 W (24.5 V / 20 A, Vin<sub>nom</sub>)
Ambient conditions
Temperature
Operation 0 to 70°C
Storage -25 to 85°C
Relative humidity
Operation Max. 95%
Mechanical properties
Installation Easy snap-on mounting onto the DIN rail
Dimensions
Width 150 mm
Height 124 mm
Depth 121 mm (+ rail)
Weight 1800 g
Ventilation/Cooling Normal convection, no fan required
Material number:
0PS320.1
Description:
24 VDC Power Supply, 3 phases, 20 A, Input 400..500 VAC (3 phases), Wide Range, DIN Rail Mounting
Documentation Version (Date) Download
Datasheet 0PS320.1 PDF / 326 KB