Short description
| POWERLINK compact link selector | Connects POWERLINK devices to a redundant POWERLINK network |
General information
| Diagnostics | |
| Module status | Yes, using LED status indicator |
| Bus function | Yes, using LED status indicator |
| Certifications | |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL |
cULus E115267 Industrial control equipment |
| HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
| KC | Yes |
| Status indicators | Module status, bus function |
| Power consumption | 2 W |
Interfaces
| Transfer | |
| Physical layer | 100BASE-TX |
| Half-duplex | Yes |
| Full-duplex | No |
| Autonegotiation | Yes |
| Auto-MDI/MDIX | Yes |
| Type | POWERLINK compact link selector |
| Variant | 2x shielded RJ45 |
| Line length | Max. 100 m between 2 stations (segment length) |
| Transfer rate | 100 Mbit/s |
| Hub propagation delay | 0.96 to 1 µs |
Electrical properties
| Electrical isolation | Power supply isolated from POWERLINK (IF1 and IF2) |
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | - |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Malzeme numarası:
X20HB8884Açıklama:
- Connecting POWERLINK devices to the POWERLINK cable redundancy system
- Integrated compact link selector function
POWERLINK is a standard protocol for Fast Ethernet with hard real-time properties. The Ethernet POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed. www.ethernet-powerlink.org
Systems with redundant cabling can be implemented easily using POWERLINK. Unlike ring redundancy, cable redundancy does not require cable looping, which can sometimes be problematic. This allows the creation of all types of tree structures. When using a device with the link selector function, data is always transferred via the highest quality network lines. The link selector function is integrated in the module compact link selector. This makes it easy to connect any POWERLINK device to a redundant POWERLINK network.
Daha fazla bilgi:
Technology information: Redundancy
User's manual: Redundancy for control systems
Zorunlu aksesuarlar
System modules for X20 hub systems
System modules for X20 redundancy systems
| X20HB2885 | X20 Compact link selector, 2x RJ45, order bus base, power supply module and terminal block separately! |
System modules for expandable bus controllers
Terminal blocks
| X20TB12 | X20 Compact link selector, 2x RJ45, order bus base, power supply module and terminal block separately! |
| Automation Studio donanım yükseltmeleri | Sürüm (Tarih) | İndirme |
|---|---|---|
| V4.0 HW Upgrade (X20HB8884) | EXE / 890 KB |
| Dökümantasyon | Sürüm (Tarih) | İndirme |
|---|---|---|
| Datasheet X20(c)HB8884 | PDF / 2 MB | |
| Redundancy for control systems | PDF / 9 MB | |
| X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
| X20 System User´s Manual | PDF / 49 MB |
| E-CAD (Elektro veya EPLAN şablonları) | Sürüm (Tarih) | İndirme |
|---|---|---|
| X20 EPLAN P8 from V2.4 | EXE / 160 MB |
| M-CAD (Mechan. Şablonlar) | Sürüm (Tarih) | İndirme |
|---|---|---|
| 3D File STEP/DXF X20BC and X20IF Module | ZIP / 1 MB |